IDEAL
-
P
KOSMOS SERIE
www.ditel.es
16
The third menu corresponds to the relay output. For more
details on the operating modes, consult the section
corresponding to this output later in this manual.
The parameters to configure are the following:
ACTIVATION MODE:
If the analog setpoint generator is enabled (see the
configuration section of the analog output below), the alarm
relay can be configured to activate according to:
in:
A value of the input signal.
out:
A value of the analog output.
diF:
The absolute value of the difference in engineering
units between input and output.
MODE OF ACTION:
Hi:
Activation of the relay by high level.
Lo:
Activation of the relay by low level.
HiLo:
Activation of the relay within the window defined by
the high ('
SPHi
') and low ('
SPLo
') levels.
For both the '
Hi
' mode and '
Lo
' mode, the setpoint value must
be entered in points by 4 digits within the display range. For
the '
HiLo
' mode, the high level setpoint and the low level
setpoint must be entered.
NOTE: It is not possible to change the position of the decimal
point, this position is determined by the one that has been
configured in the '
dSP
' display menu.
STATE OF RELAY IN REST:
no
: Normally open contact.
nc
: Contact normally closed.
TIMING AND HYSTERESIS:
dLy
:
Programmable delay from
0
to
99.9
s.
HyS
:
Hysteresis in points throughout the display range
Setpoint configuration menu
no
nc
dLy
HyS
00.0
00.00
SETPOINT CONFIGURATION
SEtP
in
out
diF
Hi
Lo
HiLo
0000
SPHi
0000
SPLo
0000