INSTALLATION

Revised By: R. Mitchell 11-6-17

Approved By: R. Mitchell 11-6-17

Illustrations Page

NEUTRAL

NEUTRAL

LINE

LINE

GROUND

INPUT

OUTPUT

120 VAC Power To 

Protected Equipment.

120 VAC Power In.

Enclosed In Conduit.

Supply Wiring

3' Of Conductor 

Length

EXPECTED SYSTEM VOLTAGES

120 VAC

VOLTAGES

L-N

0

L-G

N-G

120

120

SPD

GND.

(G)  GRN.

(L)  BLK.1

(N) WHT.

IN

SUPPLY

OUT

EQUIPMENT

(G)  GRN.

(L)  BLK.1

(N) WHT.

NO         C          NC

DRY CONTACT

)

NEUTRAL(

-

)

LOAD: 48VDC, 0.6AMP (MAX)

EXAMPLE MONITORING CIRCUIT

EXAMPLE REMOTE MONITORING

USING FACP FOR NOTIFICATION

DTK-TSS4D

25 Amp Max

DTK-TSS4D DRY CONTACT OPERATION

The Dry Contacts are a SPDT Form 1C circuit rated 48VDC/0.6A, designed for low voltage or control 

signals only, and activate if the Phase leg loses its surge protection. The Dry Contacts are accessed 

by a three position terminal block (#16-28 AWG). The positions are marked Common (C), 

Normally Open (NO), and Normally Closed (NC). If the surge protection is lost, the contacts will 

reverse; Normally Open will close and Normally Closed will open. 

There is no change to the Common (C)

 