DTK-120X12 (120VAC 20A + 12 Low Voltage Circuit Series Surge Protective Device)

Read All Instructions Before Beginning Installation!

CAUTION:  Risk  of  Electric  Shock - Only  intended  for installation in accordance with 

National Electric Code, ANSI/NFPA-70, Article 398.

Warning: 

Turn  power  off  at  the  main circuit  breaker  panel  before beginning install.

Note:  Connect  this  device in series between the 120VAC power supply and the load that requires 

protection.  Use 12 AWG Stranded,  Cu only conductors with  a  3/8”  strip length when terminating 

the wires at the power lugs.  The conductors used  to connect the SPD, to the supply or buss and to 

ground, shall not be any longer than necessary and shall avoid unnecessary bends.

1. Remove (4)  screws securing the cover, save screws. 

2. Remove cover.

3. Connect a Ground (green or bare conductor) to the 

EARTH

 lug at the 

LINE

 side.

4. Connect the Neutral (white conductor) supply wire to the 

NEUT

 lug at the 

LINE

 side.. 

5. Connect the Phase (black conductor) supply wire to the 

LINE IN

 lug at the 

LINE 

side.

6. Connect the Ground, Neutral and Phase wires from the 

LOAD

 side to the control panel, or your   

    equipment’s AC inputs.

Note: 

Tightening torque for the 120VAC power connections is 20 in-lb.

7. Use 3/4” conduit fittings for the AC circuit and a 1/2” conduit fitting for dry contacts. Best practice  

    dictates the use of separate conduit feeds to isolate the unprotected “

LINE

” wiring from protected  

    “

LOAD

” wiring  

8. After all connections have been made and no hazards exist, proceed to the  Low Voltage Surge 

    Module Wiring Diagram.

NC         C          NO

DRY CONTACT

)

NEUTRAL(-)

LOAD: 120VAC, 1AMP (MAX)

                30VDC, 2AMP (MAX)

EXAMPLE MONITORING CIRCUIT

DRY CONTACT CIRCUIT INFORMATION

EARTH

NEUT

LINE IN

EARTH

NEUT

LINE OUT

DITEK

Surge Protection

R

NC C NO

EXAMPLE REMOTE MONITORING

USING FACP FOR NOTIFICATION

EARTH

NEUT

LINE

120VAC TO FACP

TO FACP AUXILIARY CONTACTS OR

ADDRESSABLE MONITOR MODULE

120VAC, 20AMP 

SINGLE POLE BREAKER

TO BE FIELD VERIFIED

NC  C  NO

-LINE SIDE

-INPUT

-UNPROTECTED 

120VAC, 20AMP

    -LOAD SIDE

    -OUTPUT

    -PROTECTED 

120VAC, 20AMP

POWER LUGS

#12 AWG

INPUT/LINE

LOAD

LINE

Wiring Diagram-120VAC Protection Circuit

POWER LUGS

#12 AWG

OUTPUT/LOAD

#30-12 AWG

Содержание Deflector Series

Страница 1: ...TK DFXXXM SPD TYPE 2CA Electrical Ratings XXXVAC 20A 50 60 Hz Single Phase Nominal Discharge Current Rating In 10kA SCCR 10kA MCOV Rating 150 L N 150 L G VPR 600 L N 600 L G Suitable for use on a circ...

Страница 2: ...isant au plus 10 000 A eff WARNING SHOCK HAZARD DO NOT OPEN AVERTISSEMENT RISQUE DE CHOC NE PAS OUVRIR C U R US DITEK R DTK 2MHLP DTK 2MHTP 5 12 24 36 48 75 130 MODULAR SURGE PROTECTION VOICE DATA SIG...

Страница 3: ...pply wire to the LINE IN lug at the LINE side 6 Connect the Ground Neutral and Phase wires from the LOAD side to the control panel or your equipment s AC inputs Note Tightening torque for the 120VAC p...

Страница 4: ...this device in series between the field wiring and the control panel supply wiring These Low Voltage protection circuits are equipped with a removable plug and header assembly Simply remove the plug...

Страница 5: ...ng These Low Voltage protection circuits are equipped with a removable plug and header assembly Simply remove the plug from the header terminate your wires then replace the plug making sure it seats a...

Страница 6: ...odule is installed the audible alarm will be cancelled The red polarizing keys insure that the correct voltage module will mate with its correct base WARNING When the DTK 120M module has gone end of l...

Страница 7: ...ow voltage surge module into the corresponding position according to your connection circuits When a DTK 2MHTP tele communications surge module has expired gone end of life there will be interference...

Страница 8: ...Center 1720 Starkey Road Largo Fl 33771 1 800 753 2345 www diteksurgeprotection com Doc INT 100190 001 Part No 191635 Rev 2 DTK 120X12 THIS PAGE LEFT INTENTIONALLY BLANK Drawn By B Aycock 5 7 2020 Rev...

Отзывы: