BI-ANNUAL MAINTENANCE

Further to the bi-annual maintenance, do the following:

•  Inspect racks/cabinets for corrosion or loss of integrity
•  Check/record if ventilation is sufficient.
•  Check/record battery room temperature
•  Check battery for cracks
•  Check ground connections

6. Transport

Be sure that all cells are protected against short-circuit. Be sure to document and transport all cells or batteries according to 

local department of transportation rules and regulations.

7. Recycling

Discover’s lead acid batteries are recyclable products. All Discover Factory Warehouses and servicing dealers are qualified to 

accept and handle all used lead acid batteries. Contact Discover

® 

or your servicing dealer for details.

8. Troubleshooting and Frequently Asked Questions

The following is a list of common concerns and questions regarding system setup, battery charging and maintenance procedures. 
Please refer to these as general guidelines. For further assistance with your specific system setup, please contact your installer.

WHAT CAUSES THE BATTERY  TERMINAL TO MELT?
Battery terminals melting is most common because of improper connections causing high resistance and heat generation.

•  Loose connections
•  Over-tightened connections
•  Improper sized cables (too small).
•  Corroded connections
•  Improper use of washers/lock washers.
•  Too many connections on the same terminal

WHY DO THE BATTERIES BULGE?
In some cases bulging can happen and is normal during battery charging.

•  If case bulging is a concern upon receipt of a new product, please notify your Distributor immediately
•  In the case of excessive bulging- your batteries may have been exposed to temperatures of over 50°C (122°F) or may have 

been overcharged. Both conditions may cause the plates/chassis to swell and expand. If this occurs, the batteries may fail 
prematurely.

•  The batteries may have frozen due to excessive exposure to cold temperatures.

To prevent bulging, you need to take the following precautions:

•  Use the right type of charger and charge algorithm that is fully compatible with the battery
•  Ensure proper polarity when connecting the charger to the battery
•  Don’t short-circuit the battery
•  Don’t expose battery to temperatures of over 55°C (131°F) and prevent battery from freezing

WHAT CAUSES A BATTERY TO LOSE CAPACITY?
Every lead acid loses capacity over its lifetime. A loss of capacity may indicate the battery is cycled out and reached its end of life.
Capacity loss may also occur due to sulphation, overheating, or over-discharging. If there is capacity loss, the battery bank may no 
longer support an increase in load. To prevent premature capacity loss:

•  Use the right type of charger and charge algorithm that is fully compatible with the battery.
•  Verify the temperature sensors are properly mounted and the operation settings are adjusted to the appropriate battery 

temperature.

WHY ISTHE CHARGING CURRENTTOTHE BATTERY BANK SO LOW?
The charging current will decrease as the batteries become fully charged. If the charge current is low, the end of charge cycle may
have been reached. Verify that the charger is near the end of the Absorption phase or in Float voltage phase. If so, low current is
normal at this stage of charging.

•  The battery bank self-regulates charge current. The voltage can be controlled and adjusted to a high or low setting, however 

the amp output to the battery bank cannot be controlled and will drop as the batteries reach a full state of charge.

•  When the charge current decreases to 2% of the battery C20 capacity, the charge is essentially complete.

Содержание SOPzV

Страница 1: ...s Strings 4 3 4 Electrical Connections 5 4 Operation 5 4 1 Charging 5 4 1 1 Charge Parameters 6 4 1 2 Balancing Charge 6 4 1 3 Commissioning Charge 6 4 2 Discharging 7 4 3Temperature Limits 7 4 4 Char...

Страница 2: ...eries No responsibility is assumed by Discover for any consequences arising out of the use of this material Visit discoverbattery com for the most recent version of published documents Read instructio...

Страница 3: ...other types of batteries Do not expose battery to high temperatures Do not install with other battery types or brands 2 Delivery and Storage 2 1 Receiving Inspection Inspect for missing components Ch...

Страница 4: ...s 1 5 times the depth of the row Racks or cabinets shall be located 100mm 4in from the wall Be sure to provide adequate space and lighting for inspection maintenance testing and battery replacement Sp...

Страница 5: ...facturer and even the application It is extremely vital that a battery is charged with an appropriate charge profile Not doing so may cause the battery pack to be chronically under or over charged res...

Страница 6: ...hen short charging times are used then balancing charges are required at frequent intervals preferably every month Balancing charges are also required after incidents of excessive stress for the batte...

Страница 7: ...battery is designed to perform optimally at temperatures between 15 25 C At lower temperatures the battery capacity is lower and at elevated temperatures the life is reduced A maximum ambient operatin...

Страница 8: ...C 122 F or may have been overcharged Both conditions may cause the plates chassis to swell and expand If this occurs the batteries may fail prematurely The batteries may have frozen due to excessive...

Страница 9: ...ly under the conditions of use without exceeding its temperature rating Battery Capacity The power a battery can deliver from full charge at standard temperature and at a specified usually C10 dischar...

Отзывы: