DMX DECODER

 INSTALLATION GUIDE

Visit the on-line product page at www.DiodeLED.com for additional product specifications & warranty information. 

DMX 4-CHANNEL DECODER SPECIFICATION SHEET 

F

or full specifications.

Wire 

Gauge

10 W

.42 A

20 W

.83 A

30 W

1.3 A

40 W

1.7 A

50 W

2.1 A

60 W

2.5 A

70 W

2.9 A

80 W

3.3 A

100 W

4. 2 A

18 AWG

134 ft.

68 ft.

45 ft.

33 ft.

27 ft. 

22 ft. 

19 ft.

17 ft.

14 ft.

16 AWG

215 ft.

109 ft.

72 ft.

54 ft.

43 ft.

36 ft.

31 ft.

27 ft.

22 ft.

14 AWG

345 ft. 

174 ft.

115 ft.

86 ft. 

69 ft.

57 ft.

49 ft.

43 ft. 

36 ft.

12 AWG

539 ft.

272 ft.

181 ft.

135 ft.

108 ft. 

90 ft.

77 ft.

68 ft.

56 ft.

10 AWG

784 ft.

397 ft.

263 ft.

197 ft.

158 ft.

131 ft.

112 ft.

98 ft.

82 ft.

Wire 

Gauge

10 W

.83 A

20 W

1.7 A

30 W

2.5 A

40 W

3.3 A

50 W

2.1 A

60 W

4.2 A

18 AWG

34 ft.

17 ft.

11 ft.

8 ft. 

6 ft.

5 ft.

16 AWG

54 ft. 

27 ft.

18 ft.

13 ft.

10 ft.

9 ft.

14 AWG

86 ft.

43 ft.

29 ft.

21 ft.

17 ft.

14 ft.

12 AWG

134 ft. 

68 ft.

45 ft.

34 ft.

27 ft.

22 ft.

10 AWG

199 ft.

99 ft.

66 ft. 

49 ft.

39 ft.

33 ft.

24V Voltage Drop & Wire Length Distance Chart

12V Voltage Drop & Wire Length Distance Chart

Wire 

Gauge

10 W

.83 A

20 W

1.7 A

30 W

2.5 A

40 W

3.3 A

50 W

2.1 A

     60 W

     4.2 A

18 AWG

34 ft.

17 ft.

11 ft.

8 ft. 

6 ft.

5 ft.

16 AWG

54 ft. 

27 ft.

18 ft.

13 ft.

10 ft.

9 ft.

14 AWG

86 ft.

43 ft.

29 ft.

21 ft.

17 ft.

14 ft.

12 AWG

134 ft. 

68 ft.

45 ft.

34 ft.

27 ft.

     22 ft.

10 AWG

199 ft.

99 ft.

66 ft. 

49 ft.

39 ft.

33 ft.

Example: 12V Voltage Drop & Wire Length Distance Chart 

Determine load size. Let’s assume load 

is 55 W. Round up to nearest load.

1

Determine distance from driver to load. 

Let’s assume the distance is 20 ft.

2

It’s recommended to install 12 AWG to 

eliminate excess voltage drop.

3

VOLTAGE DROP CHARTS

For best performance and lumen output, ensure proper wire gauge is installed to compensate for voltage drop of low voltage circuits. 

ADDITIONAL RESOURCES

Содержание DI-1810

Страница 1: ...ctions or warranty will be void SAFETY WARNINGS QUICK SPECS MODELS INSTALLATION 1 TURN POWER OFF AT CIRCUIT BREAKER 2 Input Output Max Load DI 1810 also DI 1918 12 24VDC 12 24VDC 4CH x 5A 4CH x 96W 12V 4CH x 192W 24V SHOCK HAZARD May result in serious injury or death Turn power OFF at circuit breaker prior to installalation DETERMINE LOCATION TO INSTALL COMPONENTS V V V CH1 R CH2 G CH3 B CH4 W 0 5...

Страница 2: ...annel Address CH1 001 CH2 002 CH3 003 CH4 004 1cH 001 Only Channel Address CH1 001 CH2 001 CH3 001 CH4 001 2cH 001 002 Only Channel Address CH1 001 CH2 002 CH3 001 CH4 002 3cH 001 003 Only Channel Address CH1 001 CH2 002 CH3 003 CH4 001 OPERATION PROFESSIONAL USE ONLY SETTING PWM FREQUENCY DIMMING TYPE The PWM frequency dimming type can be adjusted for special applications 0 5 0 9 0 9 1 2 3 0 5 0 ...

Страница 3: ...o driver specifications for additional information InstallacompatibleClass2constantvoltagedriver Itisrecommended to load the driver no more than 80 its labeled rating for maximum longevity Refer to driver specifications for a compatible junction box See fixture specifications for maximum series run limits The following diagram is provided as an example system design CAT5 RJ45 connections data cabl...

Страница 4: ...5 A 40 W 3 3 A 50 W 2 1 A 60 W 4 2 A 18 AWG 34 ft 17 ft 11 ft 8 ft 6 ft 5 ft 16 AWG 54 ft 27 ft 18 ft 13 ft 10 ft 9 ft 14 AWG 86 ft 43 ft 29 ft 21 ft 17 ft 14 ft 12 AWG 134 ft 68 ft 45 ft 34 ft 27 ft 22 ft 10 AWG 199 ft 99 ft 66 ft 49 ft 39 ft 33 ft 24V Voltage Drop Wire Length Distance Chart 12V Voltage Drop Wire Length Distance Chart Wire Gauge 10 W 83 A 20 W 1 7 A 30 W 2 5 A 40 W 3 3 A 50 W 2 1...

Отзывы: