The LSET setting allows the user to choose
which function controls the electronic switch
connected to the LOAD terminal. The user can
also select whether that switch is on or off when
the function is active. (i.e. select normally open
or normally closed)
For example, if LSET is set to 8, then the load
switch would turn
on
if the battery voltage is
lower than the alarm voltage setting (ALRM).
This could be used to turn on an alarm light.
SET/MODE/LSET
# Function
Terminal is:
0 Low battery
disconnect
on when function
wants to disconnect
battery
1 Low battery
disconnect
(default)
off when function
wants to disconnect
battery
2 Generator
control
on when function
wants to run generator
3 Generator
control
off when function
wants to run generator
4 Event control
on when event is on
5 Event control
off when event is on
6 2nd battery
charge control
on when battery 2
should charge
7 2nd battery
charge control
off when battery 2
should charge
8 Alarm output
on when battery
voltage < alarm setting
9 Alarm output
off when battery
voltage < alarm setting
10 Shunt control
(Must be selected
for PWM control
of the LOAD-
terminal)*
off when function
wants to disconnect
the shunt load
(ON for regulation)
11 Shunt control
(PWM must not
be set to 2 or 3)*
on when function
wants to disconnect
shunt load (OFF for
regulation)
* Don’t use LSET=11 with PWM, as design does
not allow inversion of PWM signal.
SET/MODE/GSET
# Function
Terminal is:
0
Low battery
disconnect
on when function wants
to disconnect battery
1
Low battery
disconnect
off when function wants
to disconnect battery
2
Generator
control (default)
on when function wants
to run generator
3
Generator
control
off when function wants
to run generator
4
Event control
on when event is on
5
Event control
off when event is on
6
2nd battery
charge control
on when battery 2
should charge
7
2nd battery
charge control
off when battery 2
should charge
8
Alarm output
on when battery voltage
< alarm setting
9
Alarm output
off when battery voltage
< alarm setting
10 Shunt control** off when function wants
to disconnect shunt load
(ON for regulation)
11 Shunt control** on when function wants
to disconnect shunt load
(OFF for regulation)
** Note: PWM is not available on G Terminal
7
If LSET is set to 9, then the load switch would
turn
off
when the battery voltage goes below the
ALRM setting. This could be used to turn off a
load to reduce the drain on the battery.
The GSET setting allows the user to choose
which function controls the general purpose “G”
relay, and whether it is on (closed) or off (open)
when the function is active.