Rev 1.39 03.10.17
Firmware Version 143 ff.
Dingo 4040P Reference Manual
21
Fig. 7.4.3B - Temperature compensation curves
D
T
D
T
B
Battery
Battery
temperature
sensor
mounting
DT DTB
Neoprene
sponge
Fig. 7.4.3A - Attaching a Temperature Sensor to a battery
Connecting a Temperature
Sensor
The temperature sensor should
be connected to the T+ and T-
terminals on the green terminal
block (see p37). The sensor
wire with the stripe goes to
the T– terminal and the sensor
wire without the stripe goes to
T+ terminal. The wires may be
extended if necessary without
affecting the accuracy.
Note: The DTB (bolt-on metal
lug) has no electrical connection
to metal lug housing, so it can be
connected to either the negative
or positive battery terminal.
7
Temperature °C
V/C
ell
TEMPERATURE COMPENSATION CURVES
Normalised to 2.25V/cell
-20.00 -10.00 0.00 10.00 20.00 30.00 40.00 50.00 60.00
2.45
2.05
2.1
2.15
2.2
2.25
2.3
2.4
2.35
2,6
1,5
0,4
3,7
3,7
1,5
2,6
0,4
23°C
Autosense characteristics
below -16
o
C
-16°C (MIN)
Non-Autosense should be used
if battery temp likely to go below -12°C
Diagram Key
= Linear
= Gentle Curve
= Steeper Curve
= Limited Linear
2.5