to terminal 1 and the negative pole (0 V) to terminal 2 – see fi gure 2 and 3. While making the connections the cable 
must not be energised!
The level meter is connected to an evaluating device using a suitable two-core cable with an external diameter of 
6-8 mm (recommended cross section of cores: 0,5 – 0,75 mm

2

). A shielded cable must only be used if the lead is 

longer than 30 m or in the case of parallel lead togheter with power lines.
For supplying we advice a stabilized supply unit of safe voltage 12-30 VDC (SELV type), which can be part of the 
connected evaluating device (for the ULM-55N type) or through an intrinsically-safe isolating repeater with supply 
voltage 12-30 VDC, e.g. IRU-420 (for the ULM-55Xi type).

IV.  Putting the unit into operation

 

The ULM-55N type: switch on the power supply (12-30 VDC).

 

The ULM-55Xi type: switch on the intrinsically safe isoating repeater (IRU-420).

V. Setting 

up

 

The level meter is set up by following steps. Use the adjusting elements located under the cap nut to set the 

unit up – see fi gure 4.

Procedure:

1.  Level meter is connected to the supply line via a miliampere meter (controller, etc.).
2.  Disconnect the connector for access to adjusting elements and unscrew the cap nut (mind the internal wires). 

Connect again the connector. 

3.  Empty the tank to the minimum level or put the level meter to the corresponding distance. Set the static current  

by 

"4 mA"

 trimer to 4 mA.*

 

Turning to the right (clockwise) increases the current, while turning to the left decreases the current.

4. Fulfi ll the tank to the maximum level or put the level meter to the corresponding distance. Set the static current 

by 

"20 mA"

 trimer to 20 mA.*

 

When it is impossible to fulfi ll the maximum level, then can be used any known (detectable) level and then set 

appropriate current by next calculation:

 

I out = 4 + (0,16 x the level height in %)   [mA]

5.  To achieve maximum accuracy, it is advisable to re-check the setting of both limit values.

 * 

 

The trimmers do not have stop pieces – they can be turned approximately 15 times.

(top view of the internal electronic part)

Figure 2: The inside of the GDM connector

Figure 3: Connection scheme 

+U

0V

shielding

Figure 4: Adjusting elements

blue wire

(-)

brown wire

(+)

green-yellow wire 

(shielding)

trimer 4 mA

(minimum level 

setting)

trimmer 20 mA

(maximum level 
setting)

Содержание ULM-55N

Страница 1: ...nalis transferred to the output current 4 20 mA If continuing echo fault happens the current of the level meter slowly falls down to the value 3 8 mA When the level is moving in the dead zone see the catalogue s data the output current rises up to the alarm value 21 mA This value is kept untill the level meter doesn t register the continuous motion of the level away from the dead zone to the nomin...

Страница 2: ...dure 1 Level meter is connected to the supply line via a miliampere meter controller etc 2 Disconnect the connector for access to adjusting elements and unscrew the cap nut mind the internal wires Connect again the connector 3 Empty the tank to the minimum level or put the level meter to the corresponding distance Set the static current by 4 mA trimer to 4 mA Turning to the right clockwise increas...

Страница 3: ... 4 mA VI Usage operation and maintenance The level meter requires no operating personnel In the case of operation the optional local connected display informs operating personnel about the measured level The maintenance of the unit includes a check up on the good condition of the level meter and the supply cable Depending on the nature of the measured substance we recommend to inspect the cleanlin...

Страница 4: ...rsion Year of production first two digits and serial number remaining three digits xx xxx Ex labelling in the hexagon rgerhgType II1 2GExiaIIBT5 Number of the spark safety certificate Limit operating parameters Ui 30 VDC Ii 132 mA Pi 0 99 W Ci 370 nF Li 0 9 mH Range of head working temperatures ta 30 70 C ta 20 60 C zone 0 Protection IP65 IP67 CE labelling Number of the authorised person inspectin...

Отзывы: