7 DHW Heating

The heat pump manager automatically calculates the maximum
possible hot water temperature in heat pump operation. The
desired domestic hot water temperature can be set in the menu

“Settings – Domestic hot water – Hot water set temp”

.

Hot water temperature - HP maximum

To attain the highest possible heat pump ratio during DHW
preparation, the controller automatically calculates the maximum
possible hot water temperature in heat pump operation based on
the current heat source temperature. The lower the heat source
temperature (e.g. external temperature, brine temperature), the
higher the attainable hot water temperature.

Hot water cylinder without flange heater

If the hot water set temperature exceeds the maximum attainable
domestic hot water temperature in heat pump operation, DHW

preparation is terminated once the so-called HP maximum
temperature is reached.

Hot water cylinder with flange heater

If the hot water set temperature exceeds the maximum attainable
hot water temperature in heat pump operation, DHW preparation
with the heat pump is terminated once the so-called HP
maximum temperature is reached, and the desired hot water
temperature is attained by reheating using the flange heater.

NOTE

Reheating with flange heater
After DHW preparation with the heat pump, the water can be further
heated to higher temperatures if the system is provided with a flange
heater. DHW heating does not take place again until the HP maximum
temperature is undershot. This ensures that basic heating can be carried
out by the heat pump.

7.1 Shut-Off Times for DHW Preparation

Besides the hot water temperature, shut-off-times for DHW
heating can also be programmed in the menu item 

“Settings –

Domestic hot water 

 Hot water block’’

. No DHW heating is

carried out during this period.

If a sufficiently large cylinder is available, we recommend
carrying out DHW heating or reheating during the night-time
hours. This means that the more favourable low tariff periods
normally available can be utilized.

7.2 Thermal Disinfection

In the menu item 

“Settings – Domestic hot water – Therm.

Disinfection”

, it is possible to carry out a thermal disinfection

with hot water temperatures of up to  85 °C in bivalent systems or

systems with hot water cylinders and integral flange heater. The
thermal disinfection can be carried out for each day of the week.
The start time is selectable.

Содержание WPM 2008 R

Страница 1: ...ger f r Nieder Mittel und Hochtemperatur W rme pumpen zum Heizen und K hlen WPM 2008 R Heat pump manager for low medium and high temperature heat pumps for heating and cooling Gestionnaire de pompe ch...

Страница 2: ...ets Het submenupunt Sprache met de pijltjestoetsen en selecteren en bevestigen door middel van de ENTER toets tot de cursor naar de instellingswaarde springt De gewenste taal met de pijltjestoetsen en...

Страница 3: ...anging the Settings E 3 3 3 Settings and Operating Data E 3 4 Operation E 4 5 Operating Modes E 5 6 Adjustment of Heating Operation E 5 7 DHW Heating E 6 7 1 Shut Off Times for DHW Preparation E 6 7 2...

Страница 4: ...ting circuit The heat pump manager is either installed in the heat pump casing or is delivered with the heat pump as a wall mounted controller It carries out regulation of both the heating system radi...

Страница 5: ...mes and stored data e g faults Displays see Chap 9 on p 14 Select the desired operating mode by repeatedly pressing the modus button text message The operating mode will change 10 seconds after alteri...

Страница 6: ...prevent unintentional adjustment of the heat pump manager press the button Esc for approx 5 seconds until KEY BLOCK ACTIVE appears on the display Cancel the keyboard block using the same procedure Tab...

Страница 7: ...er temperatures Shut off times can be compensated for by a temperature rise that begins 1 hour before the shut off time takes effect COOLING Selectable only when the cooling controller is connected se...

Страница 8: ...the so called HP maximum temperature is reached and the desired hot water temperature is attained by reheating using the flange heater NOTE Reheating with flange heater After DHW preparation with the...

Страница 9: ...he modus button Summer Auto Party Vacation HG2 Cooling Duration of party mode in hours After the set period has elapsed the system returns automatically back to automatic operation again 0 to 4 to 72...

Страница 10: ...ings to raise the heating characteristic curve of heating circuit 2 3 Sets the time during which the temperature in heating circuit 2 3 is to be raised 00 00 to 23 59 Sets the temperature value by whi...

Страница 11: ...o 23 59 Sets the desired hot water temperature which is to be reached during thermal disinfection 60 C to 45 C to 85 C For each day of the week it is possible to select whether thermal disinfection is...

Страница 12: ...s are to be active when the temperature is lowered Operations to lower the temperature that exceed a week day are activated or deactivated at the end of each day accordingly N T1 T2 Y Sets the date ye...

Страница 13: ...of heating circuit 2 measured on the sensor This temperature is among other things the controlled variable for heating circuit 2 HC2 or cooling operating with silent cooling only with reversible HP D...

Страница 14: ...on Silent cooling 2 room stations Indicates if a request for cooling has been made Cooling function Cooling operation Displays the current domestic hot water set temperature Domestic hot water Sensors...

Страница 15: ...runtime of 2nd heat generator Bivalent or mono energy Total runtime of the brine circulating pump or well pump The runtime is greater than the total of the compressor runtimes because of pump forerun...

Страница 16: ...ion is carried out by the utility company The heat pump was switched off by an external utility blocking signal on input ID4 The heat pump starts after completion of the primary pump forerun This can...

Страница 17: ...a time delay of 5 minutes The heat pump remains switched off during this period Despite a pending request the chiller is unable to cool because antifreeze frost protection was activated This state is...

Страница 18: ...following heat pump faults may appear on the display Low pressure Hot gas thermostat Antifreeze Compressor load A plant fault indicates a defect or a false setting in the heat pump system Inform your...

Страница 19: ...ales service addresses please refer to the Installation and Operating Instructions for Heat Pumps Pour les conditions de garantie et les adresses SAV se r f rer aux instructions de montage et d utilis...

Отзывы: