1 Please Read 

Immediately

1.1

Important Information

ATTENTION!

The well water must comply with the required water quality standards.

ATTENTION!

The heat pump is not secured to the wooden pallet.

ATTENTION!

The heat pump must not be tilted more than 45° (in any direction).

ATTENTION!

Do not use the holes in the panel assemblies for lifting the device!

ATTENTION!

Flush the heating system prior to connecting the heat pump.

ATTENTION!

Observe the clockwise rotating field when connecting the mains cable (if
rotating field is not clockwise, the heat pump will not work properly and
will be very noisy).

ATTENTION!

The heat pump must be started up in accordance with the installation and
operating instructions of the heat pump controller.

ATTENTION!

We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump.

ATTENTION!

Any work on the heat pump may only be performed by authorised and
qualified after-sales service technicians.

ATTENTION!

Disconnect all electrical circuits from the power source prior to opening
the device.

1.2

Legal Regulations and 
Directives

This heat pump conforms to all relevant DIN/VDE regulations
and EU directives. Refer to the EC Declaration of Conformity in
the appendix for details.

The heat pump must be connected to the power supply in com-
pliance with all relevant VDE, EN and IEC standards. Any further
connection requirements stipulated by local utility companies
must also be observed.

The heat pump is to be connected to the heat source system and
the heating system in accordance with all applicable regulations.

Persons, especially children, who are not capable of operating
the device safely due to their physical, sensory or mental abilities
or their inexperience or lack of knowledge, must not operate this
device without supervision or instruction by the person in charge. 

Children must be supervised to ensure that they do not play with
the device.

1.3

Energy-Efficient Use of the 
Heat Pump

By operating this heat pump you are helping to protect our envi-
ronment. Both the heating system and the heat source must be
properly designed and dimensioned to ensure efficient operation.
It is particularly important to keep water flow temperatures as low
as possible. All connected energy consumers should therefore
be suitable for low flow temperatures. Raising the heating water
temperature by 1 K corresponds to an increase in energy con-
sumption of approx. 
2.5 %. Low-temperature heating systems with flow temperatures
between 30 °C and 50 °C are particularly well-suited for energy-
efficient operation.

2 Purpose of the Heat 

Pump

2.1

Application

The water-to-water heat pump is designed for use in existing or
newly built heating systems. Water is used as the heat transfer
medium. It can be supplied by wells or other water systems.

In order to eliminate the risk of corrosion at the evaporator, the
well water must be evaluated regarding the corrosion behaviour
of metallic materials according to DIN 50930.

Details can be found in the project planning and installation man-
ual for heat pumps for heating purposes.

ATTENTION!

The well water must comply with the required water quality standards.

2.2

Operating Principle

A well pump conveys the water to the evaporator of the heat
pump. There the heat is transferred to the refrigerant in the refrig-
erating circuit.

The refrigerant is drawn in by the electrically driven compressor,
compressed and “pumped” to a higher temperature level. The
electrical power needed to run the compressor is not lost in this
process. Most of it is absorbed by the refrigerant as well.

Subsequently, the refrigerant is passed through the condenser
where it transfers its heat energy to the heating water.

Depending on the set operating point (thermostat setting), the
heating water is thus heated up to a max. of 60 °C.

Содержание WI 14TE

Страница 1: ...to Water Heat Pump for Indoor Installation Pompe chaleur eau eau pour installation int rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Insta...

Страница 2: ...E 4 5 2 Sound Emissions E 4 6 Installation E 4 6 1 General Information E 4 6 2 Heating System Connection E 4 6 3 Heat Source Connection E 4 6 4 Electrical Connection E 5 7 Commissioning E 5 7 1 Genera...

Страница 3: ...this device without supervision or instruction by the person in charge Children must be supervised to ensure that they do not play with the device 1 3 Energy Efficient Use of the Heat Pump By operatin...

Страница 4: ...ted to the switch box It is important to en sure that the integrated motor protection is sufficient for the pump provided by the customer 1 Evaporator 2 Switch box 3 Liquifier 4 Compressor 4 Transport...

Страница 5: ...heating water system to the heat pump the heating system must be flushed to remove any impurities residue from sealants etc Any accumulation of deposits in the liquifier could cause the heat pump to c...

Страница 6: ...up is performed correctly it should only be carried out by an after sales service technician authorised by the manufacturer This may be a condition for extending the guaran tee see Warranty Service 7...

Страница 7: ...loyers liability insurance associations must be adhered to If in doubt contact the manufacturer of the chemicals 8 3 Cleaning the Heat Source System A dirt trap is inserted in the heat source inlet of...

Страница 8: ...er flow rate at an internal pressure differential of heat source m h Pa 2 0 6200 1 9 5600 3 3 19000 3 2 13000 4 0 12000 3 6 9500 5 0 20000 4 8 17900 7 0 16000 6 7 14900 3 7 Refrigerant total filling w...

Страница 9: ...it Diagrams Sch mas lectriques A VIII 3 1 Steuerung Control Commande WI 9TE WI 22TE A VIII 3 2 Last Load Charge WI 9TE WI 22TE A IX 3 3 Klemmenanschlussplan Terminal Connection Plan Sch ma de connexio...

Страница 10: ...GH 7 H WHUQDO WKUHDG RQQHFWLRQV RQ WKH KHDW VRXUFH VLGH 7 H WHUQDO WKUHDG DWHU ILOWHU ZLWK H WHUQDO WKUHDG 7 H WHUQDO WKUHDG DWHU ILOWHU ZLWK H WHUQDO WKUHDG 5DFFRUGV F Wp FKDXIIDJH 7 LOHWDJH H WpULHX...

Страница 11: ...3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D DOWZDVVHUHLQWULWWVWHPSHUDWXU LQ ROG ZDWHU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX IURLGH HQ DOWZDVVHUGXUFKIOXVV LQ P K ROG ZDW...

Страница 12: ...UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D DOWZDVVHUHLQWULWWVWHPSHUDWXU LQ ROG ZDWHU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX IURLGH HQ DOWZDVVHUGXUFKIOXVV LQ P K ROG ZDWHU IORZ UDWH LQ P K pEL...

Страница 13: ...LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D DOWZDVVHUHLQWULWWVWHPSHUDWXU LQ ROG ZDWHU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX IURLGH HQ DOWZDVVHUGXUFKIOXVV LQ P K ROG ZDWHU IORZ UDWH LQ...

Страница 14: ...UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D DOWZDVVHUHLQWULWWVWHPSHUDWXU LQ ROG ZDWHU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX IURLGH HQ DOWZDVVHUGXUFKIOXVV LQ P K ROG ZDWHU IORZ UDWH LQ P K pEL...

Страница 15: ...LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D DOWZDVVHUHLQWULWWVWHPSHUDWXU LQ ROG ZDWHU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX IURLGH HQ DOWZDVVHUGXUFKIOXVV LQ P K ROG ZDWHU IORZ UDWH LQ...

Страница 16: ...A VIII Anhang Appendix Annexes 3 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 3 1 Steuerung Control Commande WI 9TE WI 22TE 1HW 0DLQV 5pVHDX...

Страница 17: ...VRFLpWp GLVWULEXWULFH G pOHFWULFLWp 1HW 0DLQV 5pVHDX 9HUGUDKWXQJ lQGHUQ Q QODJHQ RKQH 98 6SHUUH NDQQ GLH GLUHNWH LQVSHLVXQJ I U GLH UXQQHQSXPSH HQWIDOOHQ KDQJH ZLULQJ 6 VWHPV ZLWKRXW XWLOLW EORFN GR Q...

Страница 18: ...RX HL VWDE PPHUVLRQ KHDWHU 7KHUPRSORQJHXU RQWDNW RIIHQ 3 JHVSHUUW RQWDFW RSHQ 3 GLVDEOHG RQWDFW RXYHUW 3 EORTXpH LH XQNWLRQ YRQ LVW ZlKOEDU 7KH IXQFWLRQ RI FDQ EH VHOHFWHG 3RVVLELOLWp GH VpOHFWLRQHHU...

Страница 19: ...9 Contacteur pour E9 K22 EVU Sperrsch tz Utility blocking contactor Contacteur de coupure du fournisseur d nergie K23 SPR Hilfsrelais SPR auxiliary relay Relais auxiliaire SPR M1 Verdichter Compressor...

Страница 20: ...A XII Anhang Appendix Annexes 3 5 3 5 Steuerung Control Commande WI 27TE 1HW 0DLQV 5pVHDX...

Страница 21: ...ZLWKRXW XWLOLW EORFN GR QRW UHTXLUH D GLUHFW LQIHHG IRU WKH ZHOO SXPS 0RGLILHU OH FkEODJH O DOLPHQWDWLRQ GLUHFWH GH OD SRPSH GH SXLWV Q HVW SDV REOLJDWRLUHPHQW QpFHVVDLUH SRXU OHV LQVWDOODWLRQV VDQV...

Страница 22: ...X HL VWDE PPHUVLRQ KHDWHU 7KHUPRSORQJHXU LH XQNWLRQ YRQ LVW ZlKOEDU 7KH IXQFWLRQ RI FDQ EH VHOHFWHG 3RVVLELOLWp GH VpOHFWLRQHHU OD IRQFWLRQ GH WHU 6SHUUHLQJDQJ RQWDNW RIIHQ 3 JHVSHUUW U FNH EHL HGDUI...

Страница 23: ...rculating pump Circulateur de chauffage M15 2 Heizkreisumw lzpumpe 2nd heating circuit circulating pump 2e circulateur circuit de chauffage M16 Zusatzumw lzpumpe Auxiliary circulating pump Circulateur...

Страница 24: ...A XVI Anhang Appendix Annexes 4 4 Hydraulisches Prinzipschema Hydraulic Plumbing Diagram Sch ma hydraulique 4 1 Darstellung Schematic View Repr sentation...

Страница 25: ...xible connection hose Tuyau de raccord flexible W rmepumpe Heat pump Pompe chaleur Pufferspeicher Buffer tank R servoir tampon W rmepumpenregler Heat pump controller R gulateur de pompe chaleur Elektr...

Страница 26: ...A XVIII Anhang Appendix Annexes 5 5 Konformit tserkl rung Declaration of Conformity D claration de conformit...

Страница 27: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Отзывы: