Dimplex SmartRad Fan Convector

SRX 080M, SRX 120M, SRX 140M & SRX 180M

The product complies with the European Safety Standards EN60335-1 and the European Standard Electromagnetic Compatibility (EMC) EN55014, EN60555-2

and EN60555-3. These cover the essential requirements of EEC Directives 2006/95/EC and 2004/108/EC

DE

EN

srx_en-de_ba   12/10/A

Содержание SRX 080M

Страница 1: ...The product complies with the European Safety Standards EN60335 1 and the European Standard Electromagnetic Compatibility EMC EN55014 EN60555 2 and EN60555 3 These cover the essential requirements of EEC Directives 2006 95 EC and 2004 108 EC DE EN srx_en de_ba 12 10 A ...

Страница 2: ... 30 125 MIN 590 MIN 535 150 MIN 150 MIN 235 MIN 100 MIN a d b c J A E B F C G D H K 1 2 3 4 82 A B C D SRX 080 503 324 396 386 SRX 120 670 492 564 564 SRX 140 740 562 634 624 SRX 180 911 732 804 794 50 15 150 50 220 ...

Страница 3: ...P N L1 P N L1 5 6 ...

Страница 4: ... 1063 1378 1 411 691 955 1251 3 806 1394 2016 2668 3 689 1164 1557 2070 2 591 1010 1447 1894 2 530 894 1215 1606 1 379 641 907 1174 1 357 599 828 1083 3 587 1012 1460 1926 3 530 902 1190 1580 2 413 704 1005 1309 2 387 655 884 1163 1 237 399 564 728 1 231 387 534 694 35 C 45 C 55 C 65 C 35 30 C 45 40 C 55 47 C 65 50 C 3 551 918 1284 1649 3 1495 2856 3925 4628 2 487 812 1136 1460 2 893 1760 2424 287...

Страница 5: ...Casing cover b Control panel c Air outlet guard d 1 m connection cable Fan convectors may only be used in central heating systems with a closed control circuit The heating system must be operated as a dual pipe system The devices must be of a sufficient rating such that they can compensate for heat losses in the room Technical data SRX 80 SRX 120 SRX 140 SRX 180 Heat output kW at flow temperature ...

Страница 6: ...e forwarded to any downstream devices via the control conductor see fig 6 on the right The control conductor does not have to be in phase with the supply connection If the control conductor is not used it must be properly insulated WARNING if you switch over to controlled operation the mains voltage is on this conductor WARNING do not ground the control conductor When taking out of service e g for...

Страница 7: ...w temperature higher on heating system Insufficient water flow rate through device Adjust flow rate hydraulic balance To do this close ther mostat valves on the other heaters Dirt on heat exchanger Clean heat exchanger see Maintenance section Cleaning outer surfaces The heater must be switched off and cooled for cleaning The surfaces of the heater can be cleaned by wiping with a soft damp cloth an...

Страница 8: ...erden Das Gerät saugt auf der Unterseite Luft an Diese wird im Wärmetauscher erwärmt und nach oben ausgeblasen Abb 1 a Gehäuseabdeckung b Bedienfeld c Luftaustrittsgitter d Anschlussleitung 1 m Die Gebläsekonvektoren dürfen nur in Zentralheizungsanlagen mit geschlossenem Regelkreis verwendet werden Die Heizungsanlage muss als Zweirohrsystem ausgeführt sein Die Geräte müssen ausreichend dimensionie...

Страница 9: ...tete Geräte weitergegeben Betrieb mit Programmierkassette Die Steuersignale der im Pilotgerät eingesteckten Programmier kassette werden über den Steuerleiter an eventuell nachge schaltete Geräte weitergegeben siehe Abb 6 rechts Der Steuerleiter muss nicht phasengleich zum Netzanschluss sein Wird der Steuerleiter nicht verwendet muss dieser fachge recht isoliert werden ACHTUNG beim Umschalten auf g...

Страница 10: ...reichender Wasserdurchfluss durch das Gerät Durchflussmenge einstellen hydraulischer Abgleich Hier für die Thermostatventile an den weiteren Heizkörpern zu drehen Schmutzablagerungen am Wärmetauscher Wärmetauscher reinigen siehe Abschnitt Wartung Außenflächen reinigen Zur Reinigung muss das Heizgerät ausgeschaltet und abgekühlt sein Die Oberflächen des Heizgerätes können durch Abwischen mit einem ...