www.dimplex.de
EN-11
English
12
12 Device Information
1
Type and order code
LIH 22TE
LIH 26TE
2
Design
2.1
Degree of protection according to EN 60 529 for compact devices
and heating components
IP21
IP21
2.2
Installation Location
Indoors
Indoors
3
Performance data
3.1
Operating temperature limits:
Heating water flow/return flow
°C / °C
Up to 75 / above 18
Up to 75 / above 18
Air
°C
-25 to +35
-25 to +35
3.2
Temperature spread
of heating water
at A2 / W35
7.1
5.0
8.4
5.0
3.3
Heat output / COP
at A-7 / W35
1
kW / ---
1. This data indicates the size and capacity of the system according to EN 255 and EN 14511. For an analysis of the economic and energy efficiency of the system, other parameters,
such as, in particular, the defrosting capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following
meaning: 2 °C external air temperature and 55 °C heating water flow temperature.
11.0 / 2.6
11,0 / 2.3
13.0 / 2.8
12.9 / 2.6
at A2 / W35
1
kW / ---
13.6 / 3.1
13.5 / 3.0
15.9 / 3.2
15.7 / 3.0
at A-7 / W75
1
kW / ---
16.1 / 1.7
16.0 / 1.6
18.1 / 1.8
18.0 / 1.7
at A7 / W35
1
kW / ---
15.4 / 3.4
15.2 / 3.2
19.8 / 3.8
19.5 / 3.6
at A10 / W35
1
kW / ---
16.5 / 3.5
16.3 / 3.3
20.4 / 3.9
20.2 / 3.7
3.4
Sound power level device / outdoors
dB(A)
62 / 68
62 / 68
3.5
Sound pressure level at a distance of 1 m (indoors)
dB(A)
58
58
3.6
Heating water flow
with an internal pressure differential of
m³/h / Pa
1.8 / 3700
2.3 / 6000
1.8 / 3700
2.7 / 8200
3.7
Air flow rate
with an external static pressure differential of
m³/h / Pa
9000 / 0
9000 / 0
m³/h / Pa
8000 / 25
8000 / 25
3.8
Refrigerant; total filling weight
type / kg
R404A / 3.3
R404A / 3.7
R134a / 2.7
R134a / 3.1
3.9
Lubricant; total filling weight (R404A)
type / litres (R404A)
Polyolester / 1.9
Polyolester / 1.9
type / litres (R134a)
Polyolester / 1.77
Polyolester / 1.77
4
Dimensions, connections and weight
4.1
Device dimensions
H x W x L cm
171 x 75 x 103
171 x 75 x 103
4.2
Device connections to heating system
Inch
G 1 1/4" external
G 1 1/4" external
4.3
Air duct inlet and outlet (min. internal dimensions)
L x W cm
72.5 x 72.5
72.5 x 72.5
4.4
Weight of the transportable unit(s) incl. packing
kg
382
389
5
Electrical connection
5.1
Nominal voltage; fuse protection
V / A
400 / 25 T
400 / 25 T
5.2
Nominal power consumption
1
A2 W35
kW
4.4
4.48
5.0
5.16
5.3
Starting current with soft starter
A
25
30
5.4
Nominal current A2 W35 / cos
ϕ
A / ---
8.0 / 0.8
8.1 / 0.8
9.0 / 0.8
9.3 / 0.8
6
Complies with the European safety regulations
2
2. See CE declaration of conformity
2
7
Additional model features
7.1
Defrosting
Automatic
Automatic
Type of defrosting
Reverse cycle
Reverse cycle
Defrosting tray included
Yes (heated)
Yes (heated)
7.2
Heating water in device protected against icing
3
3. The heat circulating pump and the heat pump manager must always be ready for operation.
Yes
Yes
7.3
Performance levels
2
2
7.4
Controller internal/external
Internal
Internal
Содержание LIH 22TE
Страница 2: ......
Страница 26: ...EN 12 English 12 ...
Страница 38: ...FR 12 Français 12 ...
Страница 44: ...A VI Anhang Appendix Annexes 3 2 3 2 Last Load Charge ...
Страница 52: ...A XIV Anhang Appendix Annexes 6 ...
Страница 53: ...www dimplex de A XV Anhang Appendix Annexes 6 ...
Страница 54: ...A XVI Anhang Appendix Annexes 6 ...
Страница 55: ...www dimplex de A XVII Anhang Appendix Annexes 6 ...