SETTING 5 – SPACE HEATING SETTINGS
HEAT
█
, OFF
Press
S E L E C T
Press
▲▼
Set Temperature
1 8 °C
Press
S E T
to Store
Setting 6 Press
▼
SETTING 4 – SPACE HEATING SETTINGS
HEAT
█
, H20, Hi
Press
S E L E C T
Press
▲▼
Set Temperature
3 2 °C
Press
S E T
to Store
Setting 5 Press
▼
Settings
Menu
– Parameter
Sets the low water flow temperature to be used in
conjunction with high ambient air temperature required for
weather compensation.
32°C
– Sets the low water flow temperature which
corresponds with the high ambient air temperature entered
in SETTING 2 ABOVE.
Sets the high ambient air temperature at which space
heating is blocked and no demand occurs.
18°C
– No space heating request processed above 18°C
ambient.
Sets the low ambient air temperature when the inline flow
boiler is utilised, bivalent point of the system. Used in
conjunction EN14511, CIBSE Table 2 & MIS3005.
-2°C
– Sets the bivalent point for the flow boiler. The inline
flow boiler will only support the heat pump below -2°C.
Parameter adjustable -15°C to 20°C
16
SETTING 6 – SPACE HEATING SETTINGS
HEAT
█
, out, ON
Press
S E L E C T
Press
▲▼
Set Temperature
-2 °C
Press
S E T
to Store
Setting 7 Press
▼
Содержание LA MI
Страница 1: ...LA MI Settings Function Programming Overview 8 60381 0 1 ...
Страница 3: ...Setting The Time 3 ...
Страница 6: ...Pre Configuration 6 ...
Страница 13: ...System Settings Menu Setting Parameters 13 ...
Страница 18: ...Heat Pump On Running 18 ...
Страница 20: ...Operating Mode Heater Enable Selection 20 ...
Страница 25: ...LA MI Advanced Settings Timer Programming Overview 25 ...
Страница 34: ...Completed 34 ...