EN-10 452163.66.40 · FD 9512
www.dimplex.de
English
LA 60TUR+
12 Device information
1
Type and order code
LA 60TUR+
2
Design
Heat source
Air
2.1
Model
Universal reversible with additional heat exchanger
2.2
Controller
WPM EconR-E wall-mounted
2.3
Thermal energy metering
Integrated
2.4
Installation location
Outdoors
2.5
Performance levels
2
3
Operating limits
3.1
Heating water flow
°C
up to 60
1
±2 / from 18
Cooling water flow
°C
+7
2
+9
3
to +20
Air (heating)
°C
-20 bis +40
Air (cooling)
°C
+10
2
+15
3
to +45
4
Flow / sound
4.1
Heating water flow / internal pressure differential
according to 14511
A7/W35-30
m³/h / Pa
10.5 / 16100
A7/W45-40
m³/h / Pa
10.2 / 15200
A7/W55-47
m³/h / Pa
6.1 / 5800
minimal
m³/h / Pa
5.3 / 4500
4.2
Minimum cooling water flow rate / internal pressure
differential
m³/h / Pa
10.8 / 17000
4.3
Flow rate of additional heat exchanger /
internal pressure differential
4
m³/h / Pa
6.5 / 47100
4.4
Sound power level energy according EN 12102
Normal operation / reduced operation
dB(A)
up to 74 / up to 70
4.5
Sound pressure level at a distance of 10 m (air outlet side)
5
Normal operation / reduced operation
dB(A)
up to 45 / up to 41
4.6
Air flow ((Controlling range EC fan) m³/h
10000 - 22000
5
Dimensions, weight and filling quantities
5.1
Device dimensions
6
H x B x L mm
2300 x 1900 x 1000
5.2
Weight of the transportable unit(s) incl. packaging
kg
966
5.3
Device connections for heating system
Inches
R 2“
5.4
Device connections for additional heat exchanger
(waste heat recovery)
Inches
R 1 1/4“
5.5
Refrigerant / total filling weight
Typ / kg
R417A / 31.0
5.6
Lubricant / total filling quantity
Typ / litres
Polyolester (POE) / 8.28
5.7
Volume of heating (cooling) water in device
Liquefier / intermediate heat exchanger
litres
18.8 / 6.2
6
Electrical connection
6.1
Supply voltage / fuse protection / RCD type
3~/PE 400 V (50 Hz) / C50A / B
6.2
Control voltage fuse protection
--- / ---
6.3
Degree of protection according to EN 60 529
IP24
6.4
Starting current limiter
Soft starter
6.5
Rotary field monitoring
No
6.6
Starting current
A
78
6.7
Nominal power consumption at A7/W35 /
max. consumption
7
kW
14.95 / 29.9
6.8
Nominal current at A7 / W35 / cos
A / ---
28.8 / 0.75
6.9
Power consumption of compressor protection
(per compressor)
W
70
;
thermostatically controlled
6.10 Power consumption of fan maximal
W
Up to 3.1
7
Complies with the European safety regulations
See CE declaration of conformity