HPL 6S-TU(R)W 

English

9 Cleaning / maintenance

9.1 Maintenance

To protect the paintwork, avoid leaning anything against the de-
vice or putting objects on the device. External heat pump parts
can be wiped with a damp cloth and commercially available do-
mestic cleaner.

NOTE

Never use cleaning agents containing sand, soda, acid or chloride, as
these can damage the surfaces.

To prevent faults due to sediment in the heat exchanger of the
heat pump, ensure that the heat exchanger in the heating system
cannot be contaminated. Should operating malfunctions due to
contamination still occur, however, the system should be cleaned
as described below.

9.2 Cleaning the heating system

The ingress of oxygen into the heating water circuit may result in
the  formation  of  oxidation  products  (rust),  particularly  if  steel
components  are  used. These enter the  heating system via  the
valves, the circulating pumps and/or plastic pipes. A diffusion-re-
sistant installation is therefore essential, especially with regard to
the complete piping.

NOTE

We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump. We recommend equipping diffusion-open heating systems
with an electrophysical anti-corrosion system (e.g. ELYSATOR system).

Residue from lubricants and sealants may also contaminate the
heating water.
In the event of severe contamination leading to a reduction in the
performance of the liquefier in the heat pump, the system must
be cleaned by a heating technician.
Based on current information, we recommend using a 5% phos-
phoric acid solution for cleaning purposes. However, if cleaning
needs to be performed more frequently, a 5% formic acid solu-
tion should be used.
In both cases, the cleaning fluid should be at room temperature.
We recommend flushing the heat exchanger in the direction op-
posite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating sys-
tem  circuit,  we  recommend  connecting  the  flushing  device  di-
rectly to the flow and return of the liquefier of the heat pump.
It is then important that the system be thoroughly flushed using
appropriate  neutralising  agents  to  prevent  any  damage  from
being caused by cleaning agent residue remaining in the system.
Acids must be used with care and the regulations of the employ-
ers liability insurance associations must be adhered to.
The instructions of the cleaning agent manufacturer must always
be observed.

9.3 Cleaning the air system

The evaporator, fan and condensate drain should be cleaned of
contamination (leaves, twigs, etc.) before each new heating pe-
riod. Do this by opening the heat pump as described in Chapter .

ATTENTION!

Before opening the device, ensure that all circuits are disconnected from
the power supply!

To prevent the evaporator and the condensate tray from being
damaged, do not use hard or sharp objects when cleaning.
Under  extreme  weather  conditions  (e.g.  snow  drifts),  ice  may
form on the air intake and air outlet grids. If this happens, the ice
must be removed from the vicinity of the air intake and air outlet
grids to ensure that the minimum air flow is maintained.
To ensure proper drainage from the condensate tray, it must be
regularly inspected and cleaned, if necessary.

10 Faults / troubleshooting

This heat pump is a quality product and is designed for trouble-
free operation. Should a fault occur, however, it will be indicated
on  the  heat  pump  manager  display.  In  this  case,  consult  the
"Faults and troubleshooting" page in the operating instructions of
the heat pump manager. If you cannot correct the fault yourself,
please contact your after-sales service technician.

ATTENTION!

Work on the heat pump must only be performed by authorised and
qualified after-sales service technicians! 

11 Decommissioning / 

disposal

Before  removing  the  heat  pump,  disconnect  it  from  the  power
source and close all valves. The heat pump must be dismantled
by  trained  personnel.  Observe  all  environmental  requirements
regarding the recovery, recycling and disposal of materials and
components in accordance with all applicable standards. Partic-
ular attention should be paid to the proper disposal of refrigerants
and refrigerant oils.

Содержание HPL 6S-TURW

Страница 1: ...llation and Operating Instruction Instruction d installation et d utilisation Luft Wasser W rmepumpe f r Au enaufstellung mit Hydro Tower HWK 332Econ5S Air to Water Heat PumpforOutdoor Installation wi...

Страница 2: ......

Страница 3: ...ort DE 5 6 Aufstellung DE 5 6 1 Allgemein DE 5 6 2 Kondensatleitung DE 6 7 Montage DE 6 7 1 Allgemein DE 6 7 2 Heizungsseitiger Anschluss DE 6 7 3 Elektrischer Anschluss DE 8 8 Inbetriebnahme DE 8 8 1...

Страница 4: ...nungsfrei geschaltet sind ACHTUNG Arbeiten an der W rmepumpe d rfen nur vom autorisierten und sachkundigen Kundendienst durchgef hrt werden 1 2 Bestimmungsgem er Gebrauch Dieses Ger t ist nur f r den...

Страница 5: ...mpfers zu gew hrleisten Die W rmepumpe ist nicht f r den erh hten W rmebedarf w h rend der Bauaustrocknung ausgelegt deshalb muss der zus tz liche W rmebedarf mit speziellen bauseitigen Ger ten erfolg...

Страница 6: ...r HWK 332Econ5S mit W rmepumpenmanager F r den Betrieb Ihrer reversiblen Luft Wasser W rmepumpe ist der im Lieferumfang enthaltene Hydro Tower mit W rme pumpenmanager zu verwenden Der Hydro Tower bild...

Страница 7: ...indern Ist dies nicht der Fall k nnen zu s tzliche d mmende Ma nahmen notwendig werden Des Wei teren sollte die W rmepumpe so aufgestellt werden dass die Luftausblasrichtung des Ventilators quer zur H...

Страница 8: ...Dazu sind die beiden Schrauben zu l sen Die Bleche lassen sich durch leichtes Kippen nach vorne nach oben herausneh men 7 2 Heizungsseitiger Anschluss Die heizungsseitigen Anschl sse an der W rmepump...

Страница 9: ...cksichtigung f hrt zu Funktionsst rungen Mindestheizwasserdurchsatz Der Mindestheizwasserdurchsatz der W rmepumpe ist in jedem Betriebszustand der Heizungsanlage sicherzustellen Bei einer Unterschreit...

Страница 10: ...tiv und darf nicht abgeklemmt werden 8 Inbetriebnahme 8 1 Allgemein Um eine ordnungsgem e Inbetriebnahme zu gew hrleisten sollte diese von einem vom Werk autorisierten Kundendienst durchgef hrt werden...

Страница 11: ...s Verfl ssigers der W rme pumpe anzuschlie en Danach muss mit geeigneten neutralisierenden Mitteln gr ndlich nachgesp lt werden um Besch digungen durch eventuell im System verbliebene Reinigungsmittel...

Страница 12: ...m h 2700 2700 5 Abmessungen Gewicht und F llmengen 5 1 Ger teabmessungen ohne Anschl sse H x B x L mm 945 x 1350 x 600 945 x 1350 x 600 5 2 Ger teanschl sse f r Heizung Zoll G 1 A G 1 A 5 3 Gewicht de...

Страница 13: ...h EN 14511 F r wirtschaftliche und energetische Betrachtungen sind weitere Einflussgr en insbesondere Abtauverhalten und Regelung zu ber cksichtigen Diese Angaben werden ausschlie lich mit sauberen W...

Страница 14: ...DE 12 452163 66 68 FD 9705 www dimplex de Deutsch HPL 6S TU R W...

Страница 15: ...eferer bezogene Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzu f hren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesserung wird...

Страница 16: ...DE 14 452163 66 68 FD 9705 www dimplex de Deutsch HPL 6S TU R W...

Страница 17: ...nsport EN 5 6 Installation EN 5 6 1 General EN 5 6 2 Condensate pipe EN 6 7 Assembly EN 6 7 1 General EN 6 7 2 Connection on heating side EN 6 7 3 Electrical connection EN 8 8 Commissioning EN 8 8 1 G...

Страница 18: ...ATTENTION Operating the heat pump at low system temperatures may cause the heat pump to break down completely ATTENTION Before opening the device ensure that all circuits are disconnected from the po...

Страница 19: ...tion required when a building is being dried out For this reason the additional heat consumption should be met using special de vices provided by the customer For drying out a building in au tumn or w...

Страница 20: ...of the switch box 3 3 Hydro tower HWK 332Econ5S with heat pump manager The hydro tower with heat pump manager included in the scope of supply must be used to operate the reversible air to water heat...

Страница 21: ...asures may be necessary Furthermore the heat pump should be set up so that the air outlet direction of the fan is per pendicular to the main wind direction to allow unrestricted de frosting of the eva...

Страница 22: ...n be removed to allow accessing the inside of the device Loosen the screws for this purpose The panels can be removed toward the top when slightly tilted 7 2 Connection on heating side The heating sys...

Страница 23: ...ead to malfunctions Minimum heating water flow rate The minimum heating water flow rate through the heat pump must be assured in all operating states of the heating system If the minimum heating water...

Страница 24: ...he return sensor R2 installed in the heat pump is active when the compressor is running and must not be disconnected 8 Commissioning 8 1 General To ensure that commissioning is performed correctly it...

Страница 25: ...we recommend connecting the flushing device di rectly to the flow and return of the liquefier of the heat pump It is then important that the system be thoroughly flushed using appropriate neutralising...

Страница 26: ...operation reduced operation3 4 dB A 56 52 56 52 4 5 Sound pressure level at a distance of 10 m air outlet side 5 Normal operation reduced operation3 4 dB A 28 24 28 24 4 6 Air flow Normal operation m...

Страница 27: ...dicate the size and capacity of the system according to EN 14511 For an analysis of the economic and energy efficiency of the system other parameters in particular the defrosting capacity and regulati...

Страница 28: ...EN 12 452163 66 68 FD 9705 www dimplex de English HPL 6S TU R W...

Страница 29: ...b timent FR 5 5 Transport FR 5 6 Installation FR 5 6 1 G n ralit s FR 5 6 2 Conduite d coulement des condensats FR 6 7 Montage FR 6 7 1 Raccordement c t chauffage FR 6 7 2 Branchements lectriques FR...

Страница 30: ...es temp ratures syst me plus basses risque d entra ner une d faillance totale ATTENTION Avant d ouvrir l appareil s assurer que tous les circuits lectriques sont bien hors tension ATTENTION Les travau...

Страница 31: ...nement continu pour garantir un d givrage optimal de l vaporateur La pompe chaleur n tant pas con ue pour le besoin en cha leur lev requis pour le s chage d une construction celui ci devra tre assur p...

Страница 32: ...t la tour hydraulique com bin e compris dans les fournitures doivent tre utilis s pour le fonctionnement de votre pompe chaleur air eau r versible La tour hydraulique combin e sert d interface entre l...

Страница 33: ...s pi ces d amen e d eau de refroidir Si tel n est pas le cas des mesures d absorption acoustique suppl men taires seront ventuellement n cessaires Par ailleurs la pompe chaleur doit tre install e de m...

Страница 34: ...ts Il est possible de retirer toutes les t les de surface pour acc der l int rieur de l appareil D visser pour cela les deux vis Les t les inf rieures peuvent tre sorties par le haut en les penchant l...

Страница 35: ...ctions de service du gestionnaire de pompe chaleur Un non respect entra ne des dysfonctionnements D bit minimum d eau de chauffage Le d bit minimum d eau de chauffage doit tre garanti dans la pompe ch...

Страница 36: ...QUE La sonde retour R2 int gr e la pompe chaleur est active lorsque le compresseur fonctionne et ne doit pas tre d connect e 8 Mise en service 8 1 G n ralit s Pour garantir une mise en service en r gl...

Страница 37: ...raccorder l appareil de nettoyage directement sur le d part et le retour du condenseur de la pompe chaleur Il faut ensuite soigneusement rincer la tuyauterie l aide de pro duits neutralisants ad quat...

Страница 38: ...ctionnement r duit3 4 dB A 56 52 56 52 4 5 Niveau de pression sonore 10 m de distance c t vacuation d air 5 Fonctionnement normal fonctionnement r duit 3 4 dB A 28 24 28 24 4 6 D bit d air Fonctionnem...

Страница 39: ...tre 22 C et 5 C temp rature d part croissante de 45 C 60 C 2 Ces indications caract risent la taille et la puissance de l installation selon EN14511 D autres crit res notamment le comportement au d gi...

Страница 40: ...FR 12 452163 66 68 FD 9705 www dimplex de Fran ais HPL 6S TU R W...

Страница 41: ...aleur mono nerg tique avec un circuit de chauffage ballons tampon et d eau chaude sanitaire A VII 3 2 Elektroschema f r monoenergetische W rmepumpenheizungsanlage mit einem Heizkreis Puffer und Warmwa...

Страница 42: ...WLRQ VXU HPSODFHPHQW GpJDJp HL ZDVVHUYRUODXI 1 62 HL ZDVVHUU FNODXI 1 62 XUFKI KUXQJVEHUHLFK OHNWUROHLWXQJHQ HDWLQJ ZDWHU IORZ 1 62 HDWLQJ ZDWHU UHWXUQ IORZ 1 62 HHGWKURXJK DUHD OHFWULFDO OLQHV LUFXLW...

Страница 43: ...SXPS RQVRPPDWLRQ GH SXLVVDQFH LQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH...

Страница 44: ...N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSH...

Страница 45: ...I X D K F X D H G H U X W D U p S P H 7 lUPHTXHOOHQHLQWULWWVWHPSHUDWXU HDW VRXUFH LQOHW WHPSHUDWXUH 7HPSpUDWXUH G HQWUpH GH OD VRXUFH GH FKDOHXU t t t t s D d HL XIW DVVHU lUPHSXPSHQ VWHOOW GLH PLQLP...

Страница 46: ...W D U H S P H W U H W D Z J Q L O R R W Q H P H V V L K F v D U I D U H G X D H G H U X W D U p S P H 7 lUPHVHQNHQHLQWULWWVWHPSHUDWXU HDW VLQN LQOHW WHPSHUDWXUH 7HPSpUDWXUH G HQWUpH GH GLVVLSDWLRQ WK...

Страница 47: ...ation hydraulique 3 1 Monoenergetische W rmepumpenheizungsanlage mit einem Heizkreis Puffer und Warmwasserspeicher Mono energy heat pump heating system with one heating circuit buffer tank and hot wat...

Страница 48: ...he W rmepumpenheizungsanlage mit einem Heizkreis Puffer und Warmwasserspeicher Electical circuit diagram for a mono energy system with one heating circuits buffer tank and hot water cylinder Sch ma le...

Страница 49: ...er und Warmwasserspeicher Mono energy heat pump heating system with three heating circuits buffer tank and hot water cylinder Installation de chauffage par pompe chaleur mono nerg tique avec trois cir...

Страница 50: ...rmepumpenheizungsanlage mit drei Heizkreise Puffer und Warmwasserspeicher Electical circuit diagram for a mono energy system with three heating circuits buffer tank and hot water cylinder Sch ma lect...

Страница 51: ...tionnaire de pompe chaleur E10 1 Tauchheizk rper Immersion heater R sistance immerg e M13 Heizungsumw lzpumpe Hauptkreis Heat circulating pump for main circuit Circulateur de chauffage circuit princip...

Страница 52: ...XWH PRGLILFDWLRQ HIIHFWXpH VXU O OHV DSSDUHLO V HQWUDvQH O DQQXODWLRQ GH OD YDOLGLWp GH FHWWH GpFODUDWLRQ H HLFKQXQJ lUPHSXPSHQ HVLJQDWLRQ HDW SXPSV pVLJQDWLRQ 3RPSHV j FKDOHXU 7 S HQ 3 6 78 7 SH V 3...

Страница 53: ...www dimplex de 452163 66 68 FD 9705 A XIII HPL 6S TU R W Anhang Appendix Annexes...

Страница 54: ...A XIV 452163 66 68 FD 9705 www dimplex de Anhang Appendix Annexes HPL 6S TU R W...

Страница 55: ...www dimplex de 452163 66 68 FD 9705 A XV HPL 6S TU R W Anhang Appendix Annexes...

Страница 56: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Отзывы: