Electrical
WARNING: The installation of this appliance should be carried out by a competent
electrician and be in accordance with the current IEE wiring regulations
and any local or insurance regulations.
The CXD2000VE & CXD2000HE are designed for use on a 230-240V AC single phase
supply.
An all-pole isolating switch with a minimum separation of 3mm in each pole must be
fitted to facilitate isolation. This switch must either be positioned inside a building or
have an IP rating against water ingress suitable for external installation.
The appliance must be supplied through a residual current device (RCD) having a rated
residual operating current not exceeding 30mA.
The appliance must be connected to a socket-outlet having an earthing contact.
We recommend that a cable with a minimum specification of H07RN-F polychloroprene
sheathed or similar be used with a minimum temperature rating of 90°C.
Wiring Diagram
13