General
A robust, durable wall mounting fan heater designed to coordinate with the Dimplex
range of Air Curtains, providing environmental heating in commercial and light
industrial environments.
The heater works by gradually raising the air temperature in the building and should
be positioned so as best to achieve an even temperature distribution. The product
has an output of 6kW
Wall Mounting
Remove the wall mounting bracket from the back of the heater and using it as a
guide (see
Fig. 2
) mark off the hole positions on a suitable wall (a minimum height
of 2.1 metres is required from the fl oor level to the bottom of the bracket). Solid
brick or concrete block walls must be drilled and plugged. Fix the wall mounting
bracket to the wall and assemble the heater to the extension tube using a bolt and
wing nut fi tted into hole 1 shown in
Fig. 3a
. Rotate the heater as shown in
Fig. 3b
,
and fi x the heater into position using the remaining bolt and wing nut in hole 2. Pivot
and rotate the heater into the desired position and tighten all three wing nuts. A
6mm Allen key can be used as an aid to tightening the bolts.
Model
Heat
Output
(kW)
Electrical Sup-
ply
Electrical Load
(per phase)
(A)
Weight (kg)
Min installed
Height (M)
CFS60E
3 / 6
16.5
2.1
220-240V ~1PN
26.0
Electrical Connections
The installation of this appliance should be carried out by a competent electrician
and be in accordance with the current IEE wiring regulations.
Only cable with a minimum CSA (cross sectional area) of 4.0mm2 must be used on
this appliance.
Electrical power and control connections are made by removing the control housing.
The control housing (‘Y’ in Fig 4) is detached by removing the two screws and
hinging the housing as shown (see step 1 in Fig 4). The bottom panel (‘x’ in Fig 4) is
detached by removing two screws and lifting off as shown (see steps 2 & 3 in Fig. 4).
NOTE:
A suitable local isolating switch must be provided in the electrical
supply circuit as close as possible to the heater with at least 3mm
clearance on each pole
Feed appropriate supply cable (see ‘a’ in Fig 5) to terminal blocks ‘c’. Make electrical
connections as shown in Fig 7 and fi x cable in back panel using cable gland.