4.2 Set-Up

Remove the three M12 transport restraint screws fixing the
unit to the pallet.

Remove pallet and install the three M12 supporting feet (in
plastic bag attached to the cylinder barrel nipple).

Position the hot-water heat pump and align vertically by ad-
justing the device feet! Then tighten the counternuts on the
device feet.

5 Installation

5.1 Connecting the Water Pipes

The nominal pipe widths for the on-site sanitary installation must
be determined by taking into account the available water pres-
sure and any pressure drops expected to occur in the pipework.
Water installations must be executed according to DIN 1988 (see
Appendix “Hydraulic Block Diagram” – for example, a pressure
reducing valve must be used if water pipe pressure is impermis-
sibly high); also observe local regulations for domestic water in-
stallations!
Both rigid and flexible water pipes are possible. Observe corro-
sion  behaviour  of  the  pipework  materials  to  prevent  damage
caused by corrosion (see Section: Start-Up).

NOTE

º

Hot water, cold water and circulation connections:
These pipe nipples contain plastic inserts which serve to protect against
corrosion (in particular to the pipe nipple flange surfaces). These plastic
inserts remain in their positions after the water pipes have been installed.

ATTENTION!

!!

When installing the on-site pipework, ensure the pipes do not get
contaminated (flush pipes before connecting hot-water heat pump)!

5.2 Connecting the Condensed 

Water Pipe

The condensed water hose is fed through the foil cladding at the
rear  of  the  device.  It  should  be  routed  so  that  the  condensate
produced (during heat pump operation) can flow away freely.

NOTE

º

There is a pressureless seal valve which must 

also be relocated

 when

shortening the condensed water hose (valve can be easily removed and
replaced into the hose). 

This valve is of special importance if longer air hoses are fitted to
the device or if a filter is installed on the exhaust air side. The
condensate should be drained into a siphon (see maintenance
information Cap. 7.1 on page 7).

5.3 Electrical Connection

The hot-water heat pump is wired ready for use; power is sup-
plied via connection cables plugged into an earthed wall socket
(~230 V, 50 Hz). This socket has to remain accessible after in-
stallation.

External heating element control

It is possible to optionally activate the heating element parallel to
the  "heating  element"  switch  on  the  operating  panel  of  the  hot
water heat pump via an external switch (e.g. timer). For this con-
nection, a floating contact on the external switchgear is required.
Furthermore, an cable (min. 2 x 1.0 mm

2

 / max. cable outside di-

ameter 10 mm) must be inserted into the device and attached to
connection 6 and 7 of terminal strip X5.

approx. 1.5 ** m

approx.  
0.1 * m

approx. 2.0 * m

*    Dimensions with spigot DN 125 (and bush) – air outlet side
**  Space requirement with service clearance (recommended)

X5 (6 + 7) Connection for external heating element control (optional)

7

X5

7

6

PE

N

L

3

2

1

6

PE

N

X3

L

3

2

1

Содержание BWP 20A

Страница 1: ...20A Montage und Gebrauchsanweisung Installation and Operating Instruction Instruction d installation et d utilisation Warmwasser W rmepumpef r Innenaufstellung Hot Water Heat Pump for Indoor Installat...

Страница 2: ......

Страница 3: ...Wasserleitungen DE 6 5 2 Anschluss der Kondensatleitung DE 6 5 3 Elektrischer Anschluss DE 6 6 Inbetriebnahme DE 6 6 1 Warmwasserkreislauf DE 6 6 2 Bedienung der Warmwasser W rmepumpe DE 7 7 Wartung...

Страница 4: ...Richtlinien einge halten Siehe auch CE Konformit tserkl rung Der Sachkundige hat daf r zu sorgen dass vor Beginn von Instandhaltungs Instandsetzungsarbeiten an k ltemittelf h renden Teilen das K ltem...

Страница 5: ...g aufrecht erhalten werden H here Wassertemperatur Ist die erforderliche Warmwassertemperatur h her als die von der W rmepumpe erreichbare Temperatur ca 60 C so kann diese mittels Heizstab auf max 85...

Страница 6: ...Schaltwertes 12 1 5 C R ckschaltwert 3 K 1 5 wird die Warmwasserbereitung durch die W rmepumpe und der L ftungsbetrieb unterbrochen bzw wird die W rmepumpe ab geschaltet 3 Lagerung und Transport 3 1...

Страница 7: ...Ger t Die Verbindung zur Warmwasser W rmepumpe erfolgt optional mit isolierten Luftleitungen der NW 125 die eine L nge von insgesamt 10 m nicht berschreiten d rfen Bei geringeren Raumh hen und nicht...

Страница 8: ...rmepumpe ist anschlussfertig vorverdrah tet die Stromversorgung erfolgt ber die Netzanschlussleitung zu einer Schutzkontaktsteckdose 230 V 50 Hz Auch nach der Installation muss diese Steckdose zug ng...

Страница 9: ...den eingestellten Sollwert so wird die W rmepumpe aktiviert bis die gew nschte Warmwassertempe ratur erreicht ist In Schalterstellung I ist die W rmepumpe in Bereitschaft und geht in Betrieb sobald ei...

Страница 10: ...ge Reinigen des Verdampfers ACHTUNG Verletzungsgefahr durch scharfkantige Lamellen Lamellen d rfen nicht deformiert oder besch digt werden Bei der etwaigen Verwendung von Luftfiltern sind diese regelm...

Страница 11: ...rk verun reinigt zugesetzt sind Kondensat l uft nicht ab Wasser unter dem Ger t Bitte berpr fen Sie ob das Dichtlippenventil am Kondensatschlauchende verunrei nigt oder verstopft ist reinigen Sie es g...

Страница 12: ...umpenbetrieb 1 5 K C 23 bis 60 4 3 Aufheizzeit von 15 C auf 45 C bei L20 F50 h 7 2 4 4 Leistungsaufnahme elektr Zusatzheizung W 1500 4 5 Mittlere Leistungsaufnahme 1 bei 45 C W 256 4 6 Mittlere Heizle...

Страница 13: ...rtlichen Versorgungsunternehmen oder unsere Montage und Gebrauchsanweisung sowie die in den Projektierungsunterlagen enthaltenen Hinweise zu Wartungsarbeiten oder Einbindungssche men nicht beachtet w...

Страница 14: ...DE 12 451903 66 07 FD 9908 www gdts one Deutsch BWP 20A...

Страница 15: ...stallation EN 5 5 1 Connecting the Water Pipes EN 5 5 2 Connecting the Condensed Water Pipe EN 5 5 3 Electrical Connection EN 5 6 Start Up EN 6 6 1 Hot Water System EN 6 6 2 Hot Water Heat Pump Operat...

Страница 16: ...and design of the hot water heat pump complies with all relevant EU directives see also CE decla ration of conformity The technician must ensure that the refrigerant is flushed adequately to allow mai...

Страница 17: ...perature reaches 60 C the heat pump switches off An additional hot water temperature increase can only be done by switching on the heating element The heating element controller is factory set to 65 C...

Страница 18: ...y be positioned around the ventilator case and fixed to the water pipe nipples If the pump is transported in this manner or with a sack barrow the max tilt angle of 45 must not be exceeded see illustr...

Страница 19: ...ntaminated flush pipes before connecting hot water heat pump 5 2 Connecting the Condensed Water Pipe The condensed water hose is fed through the foil cladding at the rear of the device It should be ro...

Страница 20: ...the desired temperature level has been reached Hot water tempera tures above 45 C can extend the heating up period consid erably 6 2 Hot Water Heat Pump Operation Control panel Temperature indicator...

Страница 21: ...inspection for possible leakage in the water system or stopping up of the condensate outflow should take place a few days after the maintenance work has been carried out Do not carry out any maintena...

Страница 22: ...d or whether any air filters are heavily contaminated clogged Condensate cannot flow away there is water under the device Please check whether the seal valve in the condensed water hose is contaminate...

Страница 23: ...4 3 Heating up period from 15 C to 45 C at L20 F50 h 7 2 4 4 Power consumption supplementary electrical heating W 1500 4 5 Mean power consumption 1 at 45 C W 1 Heating up of nominal volume from 15 C t...

Страница 24: ...EN 10 451903 66 07 FD 9908 www gdts one English BWP 20A...

Страница 25: ...uites d eau FR 5 5 2 Raccordement de la conduite d coulement des condensats FR 5 5 3 Branchements lectriques FR 5 6 Mise en service FR 6 6 1 Circuit d eau chaude FR 6 6 2 Commande de la pompe chaleur...

Страница 26: ...lement la d claration de conformit CE La personne qualifi e doit s assurer que avant les travaux d entretien et de mise en tat sur les parties contenant du fluide frigorig ne ce fluide soit bien limin...

Страница 27: ...dysfonctionnement de la pompe chaleur la car touche chauffante lectrique assure le maintien de la pro duction d eau chaude Temp rature d eau plus lev e Si la temp rature requise de l eau est sup rieu...

Страница 28: ...autoris e condition de transporter la PAC avec pr caution Les temp ra tures de transport et de stockage admises sont de 20 60 C 3 2 Transport au chariot l vateur avec et sans fourche Lors du transpor...

Страница 29: ...e dans les conduites d eau Respecter en outre les consignes locales relatives aux installations d eau potable Les conduites d eau peuvent tre de type rigide ou flexible Tenir compte du comportement la...

Страница 30: ...squ chappe ment complet de l air V rifier l tanch it de la totalit du circuit Pr voir l alimentation en tension Activer le commutateur Pompe chaleur voir figure La temp rature d eau chaude souhait e p...

Страница 31: ...assure la production d eau chaude Remarque R gulateur de la cartouche chauffante Le r gulateur de la cartouche chauffante constitue en outre un deuxi me dispositif de r gulation ind pendant du r gula...

Страница 32: ...ture de l air aspir ou la temp rature ambiante est 18 C le r gulateur de temp rature n a pas actionn l arr t de la pompe chaleur la temp rature de l eau chaude ne se monte pas d j 60 C voire plus La p...

Страница 33: ...mont e en temp rature de 15 C 45 C si L20 F50 h 7 2 4 4 Consomm de puissance chauffage lectrique d appoint W 1500 4 5 Puissance moyenne 1 45 C W 1 Op ration de r chauffement du contenu nominal de 15...

Страница 34: ...FR 10 451903 66 07 FD 9908 www gdts one Fran ais BWP 20A...

Страница 35: ...A II 2 Prozess Schaltbild Process circuit diagram Sch ma de c blage du processus A III 2 1 Legende Legend L gende A III 3 Hydraulisches Einbindungsschema Hydraulic Block Diagram Sch ma d int gration h...

Страница 36: ...ats Extr mit du flexible avec vanne Kaltwasserzulauf R3 4 Au engewinde 1 Nennweite Au endurchmesser 125 1 5 Das Ventil darf NICHT entfernt werden Kondensatschlauch 17 mm au en L nge ca 1 5 m Nominal w...

Страница 37: ...urregler WP HP temperature controller R gulateur de temp rature PC 8 Schutztemperaturbegrenzer Protection temperature limiter Limiteur de temp rature de protection 9 Temperaturregler Heizstab Heating...

Страница 38: ...t valve Soupape de contr le 4 R ckflussverhinderer Return flow inhibitor Clapet anti reflux 5 Manometeranschlussstutzen Pressure gauge connecting stubs Tubulures de raccordement manom tre 6 Entleerung...

Страница 39: ...www gdts one 451903 66 07 FD 9908 A V BWP 20A Anhang Appendix Annexes 4 Stromlaufplan Circuit Diagram Sch ma lectrique...

Страница 40: ...rit cartouche lectrique chauffante K2 Anlaufrelais Verdichter Starting relay for compressor Relais de d marrage pour compresseur K3 Lastrelais Ventilator Verdichter Load relay ventilator compressor Re...

Страница 41: ...www gdts one 451903 66 07 FD 9908 A VII BWP 20A Anhang Appendix Annexes...

Страница 42: ...A VIII 451903 66 07 FD 9908 www gdts one Anhang Appendix Annexes BWP 20A...

Страница 43: ...www gdts one 451903 66 07 FD 9908 A IX BWP 20A Anhang Appendix Annexes...

Страница 44: ...tschland GmbH Gesch ftsbereich GDTS Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 9245...

Отзывы: