700135-0000 Rev. O
21
4 PROGRAMMING
4.1 PROGRAM INITIALIZATION
Upon power-up, the DGM panel will display the program revision number. Next the
panel will display the number of boards installed. Each one of the possible extra
boards represents eight zones. Verify that all of the input zones on the panel are on
the display. Press the CLR/SIL button to continue. The time will appear on the
display along with any alarm and fault conditions that the DGM finds during its
initialization process. Data communications will not be established until the CLR/SIL
button is pressed. If the CLR/SIL button is not pressed, the system will continue
normal operation after one minute.
NOTE:
The SYSTEM 3505 PRISM LX must be properly programmed to accept any
new DGM panels. You must also instruct the SYSTEM 3505 PRISM LX what type
of driver is being used and to what line you are adding the DGM panel (line
number is zero if no line driver rack is installed). The SYSTEM 3505 PRISM LX must
be RESTARTED when any DGM is added to or removed from the system. You may
also press SET at the SYSTEM 3505 PRISM LX MUX menu to add or delete DGM
panels. The SYSTEM 3505 PRISM LX must have program revision 5.4.0 or higher for
this capability.
The TRANSMITTER LED should now be flashing to indicate that the SYSTEM 3505
PRISM LX has recognized the new DGM and that the DGM is responding. If the
DGM is not responding or does not perform as desired, check the programmable
functions section for proper DGM setup.
The RESET LED will flash momentarily every several seconds to indicate that all
elements in the panel are operating correctly.
Each DGM panel is equipped with a keypad and LCD display panel which allow the
user to view and set each of the functions on the DGM panel. When the DGM panel
is used with a SYSTEM 3505 PRISM LX that is equipped with a program revision of
5.4.0 or higher, the DGM panel functions are automatically downloaded from the
SYSTEM 3505 PRISM LX. For this reason, changes in the panel settings can and
should be made from the SYSTEM 3505 PRISM LX. However, there are times when
the DGM panel options need to be set in the field. The remainder of this chapter
explains how each of the functions operates and how to set functions properly.
4.2 PROGRAM ACCESS
To add, delete, or display the functions available to the DGM, you must first gain
access to the programming area. To accomplish this, the following sequence is
required:
STEP 1: Use the keypad t
o enter the system password: “123456”.
STEP 2: Press ENTER.
Содержание DGM-32/64
Страница 4: ......
Страница 6: ......
Страница 10: ......
Страница 16: ...DGM INSTALLATION AND MAINTENANCE MANUAL 6 700135 0000 Rev O Figure 1 1 DGM 32 64 and DGM 32 64 RF...
Страница 18: ...DGM INSTALLATION AND MAINTENANCE MANUAL 8 700135 0000 Rev O...
Страница 56: ...DGM INSTALLATION AND MAINTENANCE MANUAL 46 700135 0000 Rev O...