DGM INSTALLATION AND MAINTENANCE MANUAL
700135-0000 Rev. O
3
By adding the following suffixes to the base number, your DGM will be shipped with
the desired interface.
- RS232 indicates communications protocol is RS-232.
- Fiber indicates communications will be via fiber optic cable.
- RF indicates communications is to be via two-way polling radio.
- Modem indicates communications will be via audio modem.
Regardless of what style is selected, the SYSTEM 3505 Prism Lx must be equipped
with the proper interface to handle the selected communications protocol. A
DIGITIZE Multiplex system can mix and match any communications protocol
available.
1.3.4 COLOR
Each DGM is available in a choice of two colors. By adding the following suffixes to
your base number, your DGM will be shipped with the correct color:
-R indicates a RED enclosure
-B indicates a BROWN enclosure
1.3.5 EXTERNAL KEYPAD
In addition to the standard internal keypad, you may order up to 16 optional external
keypads to provide Entry Zone monitoring at each DGM. (Programming capabilities
are available only at the internal keypad). Keypads are connected to the DGM via a
standard four wire telephone cable (two data wires and two power wires). Power is
provided by the panel itself.
The keypad is ordered as P/N. 425168-000. It features 12 buttons, RED and
GREEN LEDs, and an audible beeper. It is mounted in a single width electrical outlet
box at a maximum distance of 25 feet.
For extended distance mounting, the optional Keypad Line Driver Card is available
(P/N. 450525-0001). This option extends the distance of the keypad to 1000 feet.
1.4 SPECIFICATIONS
1.4.1 ELECTRICAL
Primary Power Input
120 VAC
Operating Power Consumption (pri)
150 milliamps (max)
Standby Battery (BATT)
12.6 Volt Sealed Lead Acid
Standby
60 Hours
1.4.2 INPUTS
-
AC Power (terminal block provided)
- Low Voltage AC from transformer secondary (AC PWR IN)