System Programming
Digitize Inc.
30
700271-0001 Rev. G 05/13
5.8
Function 5 Open Loop Wait Time
The Open Loop Wait Time is the amount of time (in seconds) that the DET-16 panel will
wait before declaring the Telegraph Loop “Open”. Open Loop Wait Time can be set from 1
to 64 seconds.
Default Setting:
Ground Wait Time: 40 Seconds
5.9
Function 6 Free Loop Wait Time
Free Loop Wait Time is the time (in seconds) that the panel must wait before declaring the
Telegraph Loop “quiet” or inactive. Free Loop Wait Time can be set from 1 to 64 seconds.
Default Setting:
Free Loop Wait Time: 10 Seconds
5.10
Function 7 Bulldog Loop Wait Time
Bulldog Loop Wait Time is the time (in minutes) that the panel will wait for a “Quiet” or
inactive loop, before Bulldogging the loop and transmitting. The Bulldog Loop Wait Time is
active when the panel has any pending transmission and the Telegraph Loop is “Busy”.
Default Setting:
Bulldog Loop Wait Time: 5 Minutes
5.11
Function 8 Buzzer Timeout
Function 8, Buzzer Timeout sets how long the buzzer will remain on before automatically
turning itself off. Timeout can be set from 0 to 9.9 minutes. Timeout is disabled when set to
0.