- 5 -

Function Introduction

1.

Cooling Mode

When PV(Current Temperature) ≥ Csp(Cooling Start Point), the temperature controller enter

cooling mode. The LCD will show

,the cooling LED is light on the panel, the cooling relay is

closed, then the cooling socket will output voltage, and the cooling equipment start working.

When LED and

flash, it means the cooling equipment enter compressor delay protection

status. When PV≤SP,

on LCD will disappear, the cooling LED lights out, the cooling relay is

opened, and the cooling equipment stop working.

Eg

:

Setting SV=25°C, CD=2°C, HD=30 so Csp=SV+CD=27r, Hsp=SV-HD=22-C. When

current temperature PVS≥27

(Csp), the temperature controller enter cooling mode, and the

cooling equipment start working. When the temperature is less than 25

(SV) , it stops cooling.

In addition, when current temperature PV≤22

(Hsp) , it enters heating mode. When the

temperature is more than 25

(SV) , it stops heating.

2.

Heating Mode

When PV(Current Temperature) ≤ Hsp(Heating Start Point), the temperature controller enter
heating mode. The LCD will show

,the heating LED is light on the panel, the heating relay is

dosed, then the heating socket will output voltage, and the heating equipment start working.
When PV≥SP,

on LCD will disappear, the heating LED lights out, the heating relay is opened,

and the heating equipment stop working.

Содержание DTC-102

Страница 1: ...Thermostat Manual DTC 102 www digit en com service digit en com...

Страница 2: ...ge 4 Setting Other Functions page 4 How to restore default setting page 5 Function range and setting page 5 Function Introduction page 5 Cooling Mode page 6 Heating Mode page 6 High Low Temperature Al...

Страница 3: ...ms are available Over temperature and sensor fault alarm Heating Cooling return difference could be set separately for refrigeration and heating to protect temperature controller from violent change C...

Страница 4: ...ifferential 4 CD Cooling Differential 5 AL Low Temperature Alarm 6 AH High Temperature Alarm 7 DP Time of Compressor Delay Starting 8 CA Temperature Calibration 9 Setting Mode 10 Cooling Mode 11 Heati...

Страница 5: ...the desired temperature unit 3 Long press SET button for 3S again to save and exit Notice When temperature unit value has been changed all the setting value will be recovered to factory settings Set t...

Страница 6: ...ating start point SV set value HD heating differential Note Please do not connect any load heating or cooling equipment before you set parameters How to restore default settings Keep pressing SET key...

Страница 7: ...HD 30 so Csp SV CD 27r Hsp SV HD 22 C When current temperature PVS 27 Csp the temperature controller enter cooling mode and the cooling equipment start working When the temperature is less than 25 SV...

Страница 8: ...rigeration operations is less than preset delay lime the equipment won t start refrigeration until achieve the preset delay time Delay time will be recorded at the moment that refrigeration stops 5 te...

Страница 9: ...Compressor is working Now PV current temperature is higher or equal to Csp Cooling Start Point you could enter Setup Mode directly or wait 3 minutes until it doesn t flash green light before setting t...

Страница 10: ...oducts are guaranteed to the original owner for one year against defects in workmanship and materials Please contact us service digit en com www digit en com support WARNING Do Not Overload This unit...

Отзывы: