- 4 -

Note: If no entries are made for 30 seconds while programming is in progress, the control
reverts to the normal temperature display.

Set Other Functions

1.

Long press the SET button about 3 seconds until LCD display

2.

Press

and

to adjust the temperature

3.

Short press SET button to set next function.

4.

Long press SET button to save and exit.

After setting, Csp value and Hsp value will show the result that it could confirm whether you
have set up correctly.
Csp(Cooling start point) =SV(set value) +CD (cooling differential)
Hsp(Heating start point)=SV(set value)-HD(heating differential)

Note: Please do not connect any load (heating or cooling equipment) before you set

parameters.

How to restore default settings

Keep pressing SET key until connect the power to this device, controller will restore factory
setting after BI-BI-BI sound.

Function range and setting

CODE

Function

Setting Range

Default Setting

SV

Temperature

Setting

va

lue

-40-120

25

-40-248

77

HD

Heating Differential

0.3-15

2.0

1-30

3.0

CD

Cooling Differential

0.3-15

2.0

1-30

3.0

AH

High

Temperature

Alarm

-40-120

120

-40-248

248

AL

Low Temperature Alarm -40-120

-40

-40-248

-40

DP

Time of Compressor
Delay Starting

0~10minutes

3minutes

CA

Temperature Calibration-15-15

0

-15-15

0

CF

Temperature Unit

/

Содержание DTC-102

Страница 1: ...Thermostat Manual DTC 102 www digit en com service digit en com...

Страница 2: ...ge 4 Setting Other Functions page 4 How to restore default setting page 5 Function range and setting page 5 Function Introduction page 5 Cooling Mode page 6 Heating Mode page 6 High Low Temperature Al...

Страница 3: ...ms are available Over temperature and sensor fault alarm Heating Cooling return difference could be set separately for refrigeration and heating to protect temperature controller from violent change C...

Страница 4: ...ifferential 4 CD Cooling Differential 5 AL Low Temperature Alarm 6 AH High Temperature Alarm 7 DP Time of Compressor Delay Starting 8 CA Temperature Calibration 9 Setting Mode 10 Cooling Mode 11 Heati...

Страница 5: ...the desired temperature unit 3 Long press SET button for 3S again to save and exit Notice When temperature unit value has been changed all the setting value will be recovered to factory settings Set t...

Страница 6: ...ating start point SV set value HD heating differential Note Please do not connect any load heating or cooling equipment before you set parameters How to restore default settings Keep pressing SET key...

Страница 7: ...HD 30 so Csp SV CD 27r Hsp SV HD 22 C When current temperature PVS 27 Csp the temperature controller enter cooling mode and the cooling equipment start working When the temperature is less than 25 SV...

Страница 8: ...rigeration operations is less than preset delay lime the equipment won t start refrigeration until achieve the preset delay time Delay time will be recorded at the moment that refrigeration stops 5 te...

Страница 9: ...Compressor is working Now PV current temperature is higher or equal to Csp Cooling Start Point you could enter Setup Mode directly or wait 3 minutes until it doesn t flash green light before setting t...

Страница 10: ...oducts are guaranteed to the original owner for one year against defects in workmanship and materials Please contact us service digit en com www digit en com support WARNING Do Not Overload This unit...

Отзывы: