- 4 -
Note: If no entries are made for 30 seconds while programming is in progress, the control
reverts to the normal temperature display.
Set Other Functions
1.
Long press the SET button about 3 seconds until LCD display
2.
Press
and
to adjust the temperature
3.
Short press SET button to set next function.
4.
Long press SET button to save and exit.
After setting, Csp value and Hsp value will show the result that it could confirm whether you
have set up correctly.
Csp(Cooling start point) =SV(set value) +CD (cooling differential)
Hsp(Heating start point)=SV(set value)-HD(heating differential)
Note: Please do not connect any load (heating or cooling equipment) before you set
parameters.
How to restore default settings
Keep pressing SET key until connect the power to this device, controller will restore factory
setting after BI-BI-BI sound.
Function range and setting
CODE
Function
Setting Range
Default Setting
SV
Temperature
Setting
va
lue
-40-120
℃
25
℃
-40-248
℉
77
℉
HD
Heating Differential
0.3-15
℃
2.0
℃
1-30
℉
3.0
℉
CD
Cooling Differential
0.3-15
℃
2.0
℃
1-30
℉
3.0
℉
AH
High
Temperature
Alarm
-40-120
℃
120
℃
-40-248
℉
248
℉
AL
Low Temperature Alarm -40-120
℃
-40
℃
-40-248
℉
-40
℉
DP
Time of Compressor
Delay Starting
0~10minutes
3minutes
CA
Temperature Calibration-15-15
℃
0
℃
-15-15
℉
0
℉
CF
Temperature Unit
℃
/
℉
℃