26
COMPLIANCE
UL 864 NFPA 72 (Chapter 9) Speci
Þ
cations
Control Units for Fire-Protective Signaling Systems
29.1 Zone Restoral Reports
The Restoral Reports option must be selected as YES or Disarm. See the XR500/XR500N Programming Guide
(LT-0679).
29.2 Power Fail Delay
The Power Fail Delay option must be selected as required by the service of the panel. For Central Station service:
6-12, for Remote Station service: 12-15. See the XR500/XR500N Programming Guide (LT-0679).
29.3 Sprinkler Supervisory
Any zone used for sprinkler supervisory must be programmed with “SPRINKLR XXX” as the zone name. The last three
characters in the zone name may be assigned a number to identify the zone. The Model 893A Dual Phone Line Module
must be used on all sprinkler supervisory systems.
29.4 DACT Systems
Two phone lines must be used. The two phone lines cannot be ground start or party lines. The 893A Dual Phone Line
Module is used to provide two phone line connections to the system. The 2ND Phone Line communication option must
be selected as DD. See the XR500/XR500N Programming Guide (LT-0679).
Two different phone numbers must be programmed for digital communication. See the XR500/XR500N Programming
Guide (LT-0679). The Test Time option must be programmed so that the XR500/XR500N sends a report every 24
hours. See the XR500/XR500N Programming Guide (LT-0679).
29.5 Local Protective Signaling Systems
The DMP Model 865, 866, or 867 Noti
Þ
cation Circuit Module must be used on the bell circuit for detection of shorts
and grounds. See sections 32.1 to 32.2 in this guide for wiring diagrams. Model 790 series keypads that are used to
display troubles for local
Þ
re alarm systems must be installed within a DMP Model 777 with 777S 1.0” spacer. Any
burglary or other off premises communication must be done with the Model 893A Dual Phone Line Module. For local
commercial
Þ
re installations, the 893A is required.
29.6 Remote Station Protective Signaling Systems
You must provide 60 hours of standby battery. See section 6.9 in this guide for standby battery calculations. Two
Radionics Model D127 Reversing Relay Modules provide two reversing polarity telephone connections. See the D127
Installation Instruction sheet for wiring details. A DMP Model 893A is used to provide two line dialer communication.
29.7 Fire Protective Signaling Systems using Internet/Intranet Networks
The XR500/XR500N Command Processor™ Panel must be programmed as described below for Fire Protective Signaling
Systems using NET Communication Type or an iCOM™ Internet Alarm Router for communication. Refer to the iCOM™
Internet Alarm Router Installation Sheet (LT-0587) for more information.
• UL AA must be programmed as NO
• RETRY TIME must be programmed as 1
• SUB CODE must be programmed as YES
• FAIL TIME must be programmed as 1
• CHECKIN must be programmed as 1
• NET TRBL must be programmed as YES