Step Four: Verify DLA Hardware

Locate Heartbeat

www.digitallumens.com

374 Congress Street, Suite 600

Boston, MA USA 02210

+1 (617) 723-1200

All Rights Reserved © 2010-2015

Digital Lumens Incorporated 

Subject to change without notice.

DOC-000390-00 Rev A 10-15

Once the fully installed DLA unit, including adapter and sensor, is powered ON, you can verify that the equipment is receiving 

power by locating the DLA heartbeat. Look at the sensor lens: Every 30 seconds, you should see a blinking red LED indicator.

Note that until the DLA unit is programmed using Commissioner software, the DLA unit will use the following settings, which 

effectively tell the connected light fixture(s) to remain ON at 100%, with no occupancy sensing:

•  Active Light Level: 100%

•  Inactive Light Level: 100%

•  Occupancy Sensor Delay: Sensor Inactive 

Heartbeat Indicator

Step Three: Update the Sticker Book

Guidelines

•  Each DLA comes with an extra metallic serial number label.
•  It is critical that you adhere the label to the sticker book, which represents the facility’s  

floor plan. Place the label in the box that corresponds to the relative location of the DLA 

within the facility. 

•  Note that without an accurate and complete sticker book, the facility’s lighting management 

software cannot be programmed and the installation process may be delayed.

•  The project manager will provide access to the sticker book.  











































































































Blank page from a sticker book  

created using a CAD program

Содержание DLA-E

Страница 1: ...0V LED drivers DLA sensors communicate wirelessly with the LightRules system to receive commands and send data DLA adapters measure fixture power consumption They also convert the digital commands fro...

Страница 2: ...g tile around the sensor housing and then secure using the 2x supplied Phillips screws Note Place the flat side of the collar against the tile f Replace the bezel g Make power and data connections see...

Страница 3: ...and put aside the extra serial number label b Make power and data connections see Step Two on page 7 c Insert the sensor housing up through the existing cutout in the Philips EvoKit SR fixture d Slide...

Страница 4: ...e d Cut a 5in 7mm or greater hole in the ceiling panel and run the power and data wires through the opening e Make power and data connections see Step Two on page 8 f Secure the housing using suitable...

Страница 5: ...bove b Remove and put aside the extra serial number label c Detach the lens assembly by turning it counter clockwise d Remove the hex nut e The DLA I requires a 1in trade size knockout 1 3 to 1 4 in 3...

Страница 6: ...A I Philips SR Wiring DALI Yellow DALI Yellow White DC Black DC Red L N Black White Philips Xitanium SR LED Driver to LEDs Connect with up to three 3x additional drivers DLA R DLA S or DLA I DALI Wiri...

Страница 7: ...Power and Data Connections cont DLA E Wiring Example Philips EvoKit SR Wiring DLA E DALI Yellow DALI Yellow White DC Black DC Red L N Black White Philips Xitanium SR LED Driver To LEDs Note Use 18 to...

Страница 8: ...ttings which effectively tell the connected light fixture s to remain ON at 100 with no occupancy sensing Active Light Level 100 Inactive Light Level 100 Occupancy Sensor Delay Sensor Inactive Heartbe...

Отзывы: