32-Port DC Smart Switch
11
You may also enter a screen refresh delay in this section. If
Enable
screen refresh
is checked, and a delay value is entered, your
browser should periodically update the status screen.
Wrong Password Lockout
After three failed login attempts, the switch may be set to ignore
login attempts for a period of time (0-60 Minutes).
Power Loss Recovery Modes
The power loss recovery mode setting has a very important setting
that determines operation after a power failure:
1. Turn all circuits off (all systems will be switched off until
manually turned on later, possibly by a script).
2. You can automatically turn all circuits on using the
sequence delay timer described above.
3. You can return to the same power settings that were
used prior to the power loss. ie. 1 On, 2 Off, etc. The ON
Sequency delay timer is used here as well.
Note: If you have written a power-on script, the recovery mode
takes effect before script execution begins. Scripts start after self-
test, approximately 30 seconds after power-up.
User Defined Links
Add hyperlinks to other power controllers, your own web pages,
or remote web sites by entering URLs in the
Setup
page. For
example, enter “Site Two Power Controller” in the description field
and a URL of “192.168.0.250” These links appear on the left side
of the web pages.
Access Control
The administrator can grant users access to only certain circuits.
To set permissions, login as admin first, then create a permissions