Digital Loggers 32-Port DC Скачать руководство пользователя страница 11

32-Port DC Smart Switch

11

You may also enter a screen refresh delay in this section. If 

Enable 

screen refresh

 is checked, and a delay value is entered, your 

browser should periodically update the status screen.

Wrong Password Lockout

After three failed login attempts, the switch may be set to ignore 

login attempts for a period of time (0-60 Minutes).

Power Loss Recovery Modes

The power loss recovery mode setting has a very important setting 

that determines operation after a power failure:

1.   Turn all circuits off (all systems will be switched off until 

manually turned on later, possibly by a script).

2.  You can automatically turn all circuits on using the 

sequence delay timer described above.

3.  You can return to the same power settings that were 

used prior to the power loss. ie. 1 On, 2 Off, etc. The ON 

Sequency delay timer is used here as well.

Note: If you have written a power-on script, the recovery mode 

takes effect before script execution begins. Scripts start after self-

test, approximately 30 seconds after power-up.

User Defined Links

Add hyperlinks to other power controllers, your own web pages, 

or remote web sites by entering URLs in the 

Setup

 page. For 

example, enter “Site Two Power Controller” in the description field 

and a URL of “192.168.0.250” These links appear on the left side 

of the web pages.

Access Control

The administrator can grant users access to only certain circuits. 

To set permissions, login as admin first, then create a permissions 

Содержание 32-Port DC

Страница 1: ...USER S GUIDE 32 Port DC Smart Switch...

Страница 2: ...busses A B are provided with separate 50A input breakers Outputs 1 16 are powered from bus A Ouputs 17 32 are powered from bus B On each output a self restetting PTC protects against overcurrent Progr...

Страница 3: ...k battery life HTTPS WiFi support SNMPV1 3 SSH and Lua scripting Field Upgradeable Firmware Firmware is field upgradeable via Ethernet Package Contents DC Smart Switch 32 with input compression lugs a...

Страница 4: ...r cycle your switch to initially establish a connection Ping the default address 192 168 0 100 to confirm that a network connection is established If you don t receive a response proceed to the IP Set...

Страница 5: ...k Connection and select Properties Proceed to step 2 Windows Vista Open Start right click on Network then on properties Double click Network and Sharing Center click Manage Newtork Connections A Netwo...

Страница 6: ...om ip_setup Mac OS X Turn AirPort off temporarily Click the Apple logo then System Preferences then Network Select Built In Ethernet and then Configure Under the TCP IP tab select Manually and enter a...

Страница 7: ...confirm a valid network configuration An unreachable report from Ping indicates misconfigured network settings Once you have a connection the switch may be operated via a web browser To access the Pr...

Страница 8: ...off Access to specific circuits is determined by user name Admin controls all circuits Setup The setup page lets you set outlet names create web links adjust startup delays and set a power loss recove...

Страница 9: ...dvance Programmable Web Links User defined web links are provided Set names and destination URLs for these links on the Settings page These are convenient for connecting to other power controllers lin...

Страница 10: ...n screen status display after changing settings Screen refresh rate is adjusted in two places on the Setup page and in your browser settings Setup Page The Setup page allows the admin to configure Con...

Страница 11: ...rn all circuits on using the sequence delay timer described above 3 You can return to the same power settings that were used prior to the power loss ie 1 On 2 Off etc The ON Sequency delay timer is us...

Страница 12: ...ic system for rebooting IP equipment without human intervention AutoPing will monitor a device If it stops responding AutoPing can cycle power to reboot it For example you might use AutoPing to monito...

Страница 13: ...5 times before giving up Device Reboot Delay After power cycling to reboot a device a waiting period will occur before the IP address is re checked by AutoPing This delay allows the device time to re...

Страница 14: ...firewall is recommended Mobile Device Access Non admin accounts have a simplified UI suitable for mobile devices with small screens Third party applications are available to control various DLI produc...

Страница 15: ...um rated current is 15A Open Source Code In compliance with the spirit of the GNU public license source code is provided for reference Purchasing a TLA and signing an NDA from Atheros Qualcom is highl...

Страница 16: ...32 Port DC Smart Switch digital loggers com Latest Manual AutoPing AC Model Scripting DLI Homepage 16...

Страница 17: ...nals 32x screw compression blocks 3A nominal Power Input 2x50A 12 72VDC positive or negative ground Operating Temperature 30 to 170 F 34 to 77 C Options Factory Custom breaker ratings External contact...

Страница 18: ...ers are valid for 15 days from date of issue This warranty does not cover products which are modified including firmware modifications subjected to rough handling or used in applications for which the...

Страница 19: ...32 Port DC Smart Switch 19 Web Enabled DIN Relay Related Products Call 408 330 5599 Web Power Switch Pro Smart PoE Injector 90 240VAC Smart PDU...

Страница 20: ...2695 Walsh Ave Santa Clara CA 95051 408 330 5599 digital loggers com...

Отзывы: