B-4
Power System Troubleshooting
Figure B-2
Brief Data Packet Structure
BXB-0277-92
1
2
3
4
5
6
7
8
9
Checksum
Power Supply State (PSS)
0 = Normal AC operation
1 = UPS mode
2 = Breaker open
3 = No AC voltage
4 = Keyswitch off
5 = Nonfatal fault
6 = Fatal fault
B = Broken
F = Fault (red zone)
W = Warning (yellow zone)
0 = Normal operation
(green zone)
0 = Battery pack not installed
E = Battery pack failure
B = UPS inhibit
C = Charger inhibit
Z = Battery at end of life
L = Battery discharged
- = Discharging
+ = Charging
X = Charge mode longer than 24 hours
F = Fully charged
Heatsink Status (HSS)
Battery Pack State (BPS)
Test Status (TS)
0 = Battery pack not installed
W = Battery pack not ready
(only if test requested)
A = Test aborted
T = Test in progress
F = Fail
P = Pass
Remaining Battery Capacity (Minutes)
Identification
A = Slot A
B = Slot B
C = Slot C