IPP-S Installation guide Digipower Inc.
5
The figure shown C5, C8, C10 detect L2 current, the voltage is L2-N.
The figure shown C6, C11 detect L3 current, the voltage is L3-N.
Digital Input Wiring Diagram
Power Supply:
12 Vdc 0.8A
Input:
Channel Isolated
Range : Contact open(off) or closed (on)
Termination Connection:
14~28AWG,0.2~15mm
2
Digital Output Wiring Diagram
Output:
Range : Contact open(off) or closed (on)
Max. switching current: 16A
Max. switching voltage: 250VAC
Max. switching capacity: 4000VA
Termination Connection:
12 ~30AWG,0.2~4mm
2
Installation Notes
1.
The maximum voltage measurement is 400V.
2.
Check that the voltage and current phases are connected properly.
3.
Measuring the diameter of the conductor (the bare wire) with the insulation removed and selecting the suitable size of
detachable CT.
4.
Measuring voltage: Make sure the CT’s on phases and wires are correct as installation diagram.
5.
Measuring current: The positive output can be obtained when the direction of current carrying conductor is the same as the
direction of arrow marked on the CT.
6.
The installation of loads combination refers to Installation Diagram.
7.
The hardware setting refers to Installation Diagram.
8.
Working power supply: AC 115V/230V on terminal R & T, the pinout as shown in Installation Diagram.
9.
The software setting refers to Operation.
10.
Communication interface: RJ-45, TCP/IP