background image

Hybrid Inverter Users’ Manual 

Page | 8   

 

 

t1: When you turn on the 1500 Watt Hybrid Inverter, in order to ensure full battery 

capacity, the MCU will automatically enter the bypass mode supplying, electricity to 
the load. In the meantime the AC charger and solar charger will continue to charge 
the battery. 

t2:

 

When the battery is fully charged to 15 volt, the MCU will turn OFF both the AC and 

solar charger. Otherwise the battery life span will be shortened by overcharging. The 
MCU will also switch to the inverter mode supply electricity to the load through the 
battery. (Users can also press the AC/DC priority switch to set the DC first mode as 
the battery discharges below 15 volt) 

 
t3: When the battery drops below 12.8 volt, the MCU will once again start up the solar 

charger instead of the AC charger in order to save energy. 

 
t4: When the load requirement is less than the energy provided by solar panels, the 

battery voltage will climb slowly. When it reaches 15 volt, the solar charger will turn 
OFF to avoid overcharging. 

 
t5: When the battery drops below 12.8 volt, the solar charger will start charging again. 
 
 
t6: If the load requirement is greater than the energy provided by the solar panels, the 

battery voltage will gradually decline. As soon as it is down to 11 volt, the built-in 

Содержание UP-8B5N

Страница 1: ...Hybrid Inverter Users Manual Page 1 1500 WATT HYBRID INVERTER SOLAR INVERTER AC MAINS Users Manual...

Страница 2: ...The 230 volt AC can NOT be converted to 12 volt DC to only charge the battery bank that is connected Do NOT place the inverter near flammable materials or any location which accumulate flammable fume...

Страница 3: ...Hybrid Inverter Users Manual Page 3 4 Names and Functions Front Panel Power Output and Back Panel Power Input...

Страница 4: ...LCD Display switch 5 How to Connect the Hybrid Inverter in Your Facilities 1 Connect the battery terminals with the battery as shown in Step 1 Please ensure the polarity is correct 2 Connect the solar...

Страница 5: ...erter and the power source Check the connections with exposed conductive parts Blown fuse in the inverter Replace the fuse No AC output voltage Over temperature protection Check for adequate ventilati...

Страница 6: ...ry is old or defective Replace the battery The battery capacity is too small Use a higher capacity battery Charger failure no charge voltage The battery voltage is too low to be charged Change the bat...

Страница 7: ...If the battery voltage drops to 12 8 volt the MCU will once again start charging t7 When the load requirement is less than the energy provided by the chargers the battery voltage will climb slowly On...

Страница 8: ...load through the battery Users can also press the AC DC priority switch to set the DC first mode as the battery discharges below 15 volt t3 When the battery drops below 12 8 volt the MCU will once ag...

Страница 9: ...keep loads running t10 When the battery drops below 12 8 volt the MCU will once again start up the solar charger instead of the AC charger in order to save energy t11 As the battery voltage falls as l...

Страница 10: ...120VAC 5V UL Continuous Power 1500W Overload Protection 1650 1900W Alarm 30S Surge Power 3000W Frequency 60 50 0 5Hz Switch Wave Form Pure Sine Wave THD Line load 3 Efficiency 80 Over Temperature Pro...

Страница 11: ...ge ragne 10 15VDC Charger output current 10A 12VDC 10 Max charge voltage 15VDC 0 3V Efficiency 80 Output short circit protection OK Reverse battery protection OK Battery high voltage protection 15VDC...

Отзывы: