10
ConTroller InsTallaTIon
sensor InsTallaTIon
LEGEND
1. “MINI CLIK” RAIN SENSOR.
2. DIG PLASTIC PIPE CAP – 1” CAP PART NO. 23-001 OR 1.5”
CAP PART NO. 23-153 WITH HOLE FOR WIRES.
3. DRILL TWO 3/16 HOLES IN PIPE FOR SENSOR BRACKET.
4. (2) #8-32 MACHINE SCREWS WITH WASHER, LOCK
WASHER AND NUT.
5. 1” OR 1.5” GALVANIZED PIPE 6 TO 10 FEET HIGH.
6. 12”x12” CONCRETE BASE 8” DEEP MINIMUM.
7. 1” OR 1.5” PIPE ELBOW.
8. FINISH GRADE.
9. 6” ROUND VALVE BOX.
10. PART NO. SKIT ADAPTER 8821-4 USE WITH EACH SENSOR.
11. TO CONTROLLER OR VALVE.
12. (4) DRY SPLICE WATERPROOF CONNECTORS.
13. NORMALLY CLOSED WIRE FROM SENSOR.
14. COMMON WIRE FROM SENSOR.
15. 1” OR 1.5” NIPPLE.
16. GRAVEL.
RAIN SENSOR ASSEMBLY
COLUMN MOUNTED
w
LEGEND
1. MODEL XRC WITH RADIO REMOTE
4 TO 28 STATIONS.
2. TERMINAL STRIP
3. 12 OR 14 GAUGE WIRE.
4. PROGRAMMING KEY. MODEL #: LEIT KEY
5. 35” STEEL MOUNTING COLUMN.
MODEL NUMBER: MCOLXS (SHORT)
50” STEEL MOUNTING COLUMN.
MODEL NUMBER: MCOLXL (LONG)
6. FINISH GRADE.
7. 6-1/2” OF BACKFILL SOIL.
8. POURED CONCRETE BASE – 1-1/2 CU.FT. INSTALL PER
MANUFACTURER’S INSTALLATION GUIDE.
9. DIRECT BURIAL CONTROL WIRES TO CONTROL VALVES.
LIGHT ENERGIZED IRRIGATION CONTROLLER
LEIT CONTROL X AND XRC
q
Figure C
electrical equipment relay interFace connection
LEGEND
1. FINISH GRADE
2. 6” ROUND VALVE BOX
3. RKIT ADAPTER PART NO. 8810-S. USE WITH EACH SENSOR
4. RED WIRE TO THE MV/PUMP TERMINAL OR ANY STATION
TERMINAL
5. WHITE WIRE TO THE COMMON TERMINAL
6. DRY SPLICE WATERPROOF CONNECTORS (4)
7. TO AC/DC EQUIPMENT OR PUMP START RELAY