background image

22

6.

Make sure that the water pressure is not too high (over 150 PSI). Use a pressure regulator if
necessary.

PROGRAMMING PROBLEMS:

The valves will come on using the “Manual Run” feature but will not water automatically.

Check the following:

1.

The Rain Stop is active. To reactivate the program schedule, go into the Main Menu-Rain
Stop/Restart and cancel the Rain Stop (see Rain Stop, page 8-9).

2.

No programming schedules have been entered yet. Go into Main Menu Setup Schedule and
enter a program (see Programming Schedule, page 13-15).

3.

You programmed the controller, but did not ACTIVATE the programs. Go into Main Menu Setup
System and activate the desired programs (see Activating Programs, page 17).

4.

The programmed runtime of the stations is set to “0” duration. Go into Main Menu Setup
Schedule and alter runtime (see Selecting a Watering Duration, page 14).

5.

You are not using a sensor, but you programmed the system for sensor operation. Go into
Main Menu and then Uplink System to check that sensors are unused (see programming,
page 18).

6.

A sensor is hooked up to the system and is in a state that inhibits watering.

7.

If some valves will not operate in a manual run, enter Uplink System and set the Open
checkmark in the Active CCT test screen. Then repeat the manual run and then check the
status. If there is an open circuit (wire break) it will be reported. Repeat with the short
checkmark set, to look for short circuits (wires touching).

8.

If the valves operate correctly in a manual run but not in a scheduled program check that the
following settings are correct:

• Active Programs screen.

• Sensor – Sensor in Use, Sensor Location and Sensor Governs screens.

• Month stop – Turn Month off and Month Selection screens

• Schedule start times, runtimes per program set correctly

9.

If a program runs but starts unexpectedly check the schedule settings. If a new program starts
before the old program has completed it will be stacked to commence later. The handset gives
warnings if runtimes and starts overlap but the LEIT X or XRC controller does not.

10. Make sure there is enough time between the programs and/or start times to meet your

watering time in budget (up to 200% possible) (see Monthly Budgets, page 9).

11. The password has been changed or forgotten: Please call DIG Customer Service with the

Serial Number of your controller.

GROUPING

Considerations when setting up and making changes to grouped programs:

1.

If a valve that was grouped is reset to 0:00, the valve will be skipped.

2.

If the lead valve of a group is set to 0:00, the next valve must be given a run time to lead the
group. (If not, the orphaned group will attach to the preceding valve.)

3.

If Valve #1 is a group leader and is set to 0:00, since there is no preceding valve, the group
would remain orphaned. A default run time of 0:01 is returned to Valve #1 to prevent this
occurrence.

If the provided solutions have not solved your problems, please call DIG 800-322-9146 for
technical support.

Please note that tampering with the controller, or even attempting to take it apart, will VOID any
warranty your product might be eligible for.

21

SERVICE CALL (INSTALLATION TROUBLESHOOTING)

CHECK THE LEIT CONTROLLER AND HANDSET

1.

The LEIT XRC controller functions exactly the same as the LEIT X and LEIT XR controller except
for the addition of radio setup. The handset and XRC radios MUST be set up prior to operation
with Client Code, ID and Group address using the key for the XRC.

2.

The XRC controller must be situated in a position of adequate light. The radio cannot maintain
proper functionality in a shaded position such as adjacent to a wall, unless it is on the “sunny”
side of the wall. If light levels drop too low the radio will turn itself off to guarantee correct
controller operation. When the radio is off, less power is used as the controller is charging.
The radio's internal circuitry will turn itself on again when sufficient light has charged the
controller to the appropriate power level. At low light levels the radio will periodically turn on
and off. For best results schedule Time on as late as possible and Time off as early as possible
in UPLINK SYSTEM.

3.

The radio will function better if it is located at a higher elevation. If there is a choice do not
situate it in a hollow.

4.

To communicate, the controllers and handsets MUST have the same Client Code. This is the
user's unique identification code, which prevents interference from other users in the area.

5.

For LEIT Link Multi-Pro handsets, only one group, is permissible therefore all controllers must
be set to group 1 (default).

6.

For LEIT Link Master handsets, the handset can communicate with controllers, which have
been arranged in functional groups and setup accordingly.

7.

If two controllers in the same group are set to the same ID, communication may be disrupted
if both controllers are in range of the handset. The same occurs if two handsets are set to the
same ID and are in use at the same time. All controllers and handsets in the same group must
have a unique ID.

8.

The handset needs to be kept in a charged state. After 500 – 1000 charge cycles the internal
batteries may need replacement.

9.

To verify that the controller is operating correctly, insert the LEIT key and scroll to Check
Status mode. Verify if the controller accumulated the time correctly for past and current
month.

TROUBLESHOOTING YOUR CONTROLLER

ELECTRICAL PROBLEMS:

With the LEIT Key plugged into the controller, if after 2 minutes there is no visible display check
the following:

1.

Check the battery in the LEIT Key and replace if necessary.

2.

Make sure the LEIT Key is plugged in all the way.

Some or all valves fail to operate when using “Manual Run”. (Systems NOT USING a master
Valve/Pump)

Check the following:

1.

Make sure that the red (hot) wires of the actuators are spliced to the hot field wires leading to
the controller.

2.

Make sure all the white (common) wires of the actuators are connected to the common field
wire leading back to the controller.

3.

Insert all field wires (with 3/10” of insulation stripped from the end of the wires) firmly into the
controller connector and tighten the appropriate screws so as to ensure good connection.

4.

Make sure that the wires are corrosion free, the joints are tight and made waterproof.

5.

Make sure that there is adequate water pressure.

Содержание LEIT Link

Страница 1: ...I N S T R U C T I O N M A N U A L Website E http www digcorp com e mail dig digcorp com 041906 DIG CORP 26 401 Printed in the USA 1210 Activity Drive Vista CA 92081 USA Controller Group ID ID Locatio...

Страница 2: ...tered trademarks LEIT XRC LEIT Link Master and LEIT Link Multi Pro are each trademarks of DIG Corporation FCC compliance Important Note To comply with FCC RF exposure compliance requirements the anten...

Страница 3: ...rates 99 controllers in one group The LEIT Link Remote Control Handset is a 2 way radio communication device that operates in the ISM band 902 928 MHz 868 869 Europe The LEIT Link is a practical solut...

Страница 4: ...INK HANDSET AND LEIT XRC CONTROLLER IMPORTANT In order to establish 2 way communication between the LEIT Link handset and the LEIT XRC controllers a simple set up process using Radio Setup in both uni...

Страница 5: ...n entered into the controller The handset can be used to modify this description which is described later in detail in the Uplink System section Press to continue 5 To set the time for the handset und...

Страница 6: ...ed with the LEIT key and if any other handsets are active Press to review each screen and to exit If the LEIT XRC controller has no activity the first screen on the right indicates that the controller...

Страница 7: ...to the next feature SETTING UP A MONTHLY BUDGET FOR ALL PROGRAMS Instead of changing the duration for each program you can use the Uplink Monthly Budget feature to increase or decrease the amount of...

Страница 8: ...K Valve01 Use This YR 06 1682 34 OK YR 05 TOT Valve 0Yes 0No OK Valve01 Use last YR 05 1040 66 OK Total Use Last YR 05 3010 86 OK NOV05 Tot Valve 0Yes 0No OK DEC05 Tot Valve 0Yes 0No OK Connect ID 12...

Страница 9: ...he watering time for this group leader will be applied to all consecutive valves that show the letter G in the Valve Runtime screen Valve 01 0 02 Start OK Valve 2 G0 00 Runtime OK Valve 1 0 12 Runtime...

Страница 10: ...t2 next Sched 12 50pm OK UPLINK SETUP SYSTEM Connect ID 09 Controller OK 15 To remove the letter G from a valve in the group In the Valve Runtime screen press the or to underscore the letter G icon lo...

Страница 11: ...cation in which the sensor is connected via the SKIT 8821 4 adapter Active CCT Test 0Short 0Open OK Valve01 Options 0MV P Budget OK Sensor Location 0 MV P 0Other OK Sensor In Use 0 Yes 0 No OK Active...

Страница 12: ...is blinking wait for a confirmation If communication is established the following screens will confirm the changes If communication is not established the No Response Try Again screen will appear with...

Страница 13: ...ranty your product might be eligible for 21 SERVICE CALL INSTALLATION TROUBLESHOOTING CHECK THE LEIT CONTROLLER AND HANDSET 1 The LEIT XRC controller functions exactly the same as the LEIT X and LEIT...

Отзывы: