DLEV1
Operating Instructions
- 19 -
5.3.8 13A Mains Socket
•
The mains socket on the front of the DLEV1 provides a direct
connection to L1, N and PE conductors of the charging station.
The connection between the adaptor and the charge station is
made via the interchangeable Type 1 or Type 2 connector plug.
•
The mains socket output is intended for measuring purposes
only and offers the ability to connect directly to an electrical
multifunctional tester with a 13A mains lead (Figure 2).
•
The max current is limited to 10A, the mains socket is protected
against overload with 10A/250V,5x20mm fuse.
5.3.9 Measurement Input Terminals L1, L2, L3, N & PE
•
Measuring terminals are directly connected to L1, L2, L3, N and
PE conductors of the tested charging station via the test cable.
•
These terminals may be used for measuring purposes only, it is
not allowed to draw current over a longer period or supply
anything else.
•
An appropriate electrical multifunctional tester is needed.
5.3.10 Load Test Using 13A Mains Socket
•
The mains socket on the front of the DLEV1 can also be used to
connect a load to check if the electric charge points and power
monitoring meter works and counts in the right manner (load
test).
•
To power the loading appliance, the CP state will need to be
switched to position C or D with the PP state switched to any
current position other than NC.
•
An external load can be connected for measuring purposes
only, it is not allowed to supply anything else.
•
The max current is limited to 10A, the mains socket is protected
against overload with 10A/250V,5x20mm fuse.