background image

GB-H-152 GAS BOOSTER PACKAGE OPERATION AND MAINTENANCE MANUAL 

© 2008 DH Instruments, a Fluke Company

 

Page 18

 

 

Check that the booster drive adjust regulator (2) is set to a pressure of 0.15 MPa (20 psig) or higher 
and that minimum flow requirements are met (see Section 1.4, 2.2). 

 

Check there are no restrictions in the shop drive air supply circuit.  Remove any restrictions.  If a filter 
is installed on the shop drive air circuit, it may cause a flow restriction. 

 

Check that there are no leaks in the shop drive air circuit.  Repair any leaks. 

5.4

 

PRESSURE GENERATES TOO SLOWLY OR NOT AT ALL 

 A slow running booster will cause the pressure to be generated slowly.  Ensure the booster is running 
properly before continuing (see Section 5.2). 

 

Check that the test gas (high pressure) supply to the 

SUPPLY IN 

port is not below 4.8 MPa (700 psi).  

If the supply is too low, increase supply pressure.  Speed of pressure generation is directly related to 
the pressure of the test gas supply.  For example, pressure is generated twice as quickly with the test 
gas supply at 14 MPa (2 000 psi) than with the supply at 7 MPa (1 000 psi). 

 

Check that there are no restrictions in the test gas supply line to the booster.  If a restriction exists, 
remove it.  Possible restrictions include a valve not fully opened, a regulator with a low flow constant 
(CV), an inline filter, small diameter tubing, etc. 

  Check that the booster inlet and outlet check valves in the high pressure booster piston are 

operating properly.  Close the booster drive shutoff valve (4).  Adjust the high pressure Regulator (6) 
to zero pressure by rotating the knob counter-clockwise until no spring force is felt. 

 

Open the booster drive shutoff valve (4).  The booster should cycle several times then stall.  If the 
booster does not stall when the test gas supply pressure is above 2 MPa (300 psi) and the shop drive 
air pressure is below 0.25 MPa (40 psig), the check valves are the most likely cause.  Contact a 

DHI

 

Authorized Service Provider if faulty check valves are suspected. 

5.5

 

BOOSTER RUNS CONTINUOUSLY 

The booster is a pneumatically operated pump.  The reciprocating action is caused by an imbalance of 
forces within the pump due to the opposing drive air pressure and the high pressure instrument gas 
supply that is being boosted.  If the booster runs continuously, it means that forces do not equalize. 

 

Check that the test gas supply is present at the 

SUPPLY IN

 port (5) and is at least 1/25 of the desired 

booster output pressure.  Generally, test gas supply needs to be at least 4 MPa (600 psi).  If not, 
ensure that supply meets required specifications (see Section 2.2). 

  Check that the high pressure circuit connected to the 

HIGH PRESSURE OUT

 port is not open to 

atmosphere. 

 

Check that there are no leaks in the high pressure line from the output of the booster at the check 
valve to the point-of-use.  Repair any leaks.  If driver air supply pressure is above 0.25 MPa (40 psig), 
adjust to below this limit.  If booster stops running, increase test gas supply. 

  Check that the inlet and outlet check valves in the high pressure booster piston are 

operating properly.  Close the booster drive shutoff valve (4).  Adjust the high pressure regulator (6) 
to zero pressure by rotating the knob counter-clockwise until no spring force is felt. 

 

Open the booster drive shutoff valve (4).  The booster should cycle several times then stall.  If the 
booster does not stall when the test gas supply pressure is above 20 MPa (300 psi) and the drive air 
pressure is below 0.25 MPa (40 psig), the check valves are the most likely cause.  Contact a 

DHI

 

Authorized Service Provider if faulty check valves are suspected. 

 

Содержание GB-H-152-100M

Страница 1: ...2008 DH Instruments a Fluke Company GB H 152 70M and GB H 152 100M Gas Booster Packages Operation and Maintenance Manual...

Страница 2: ...ated only by personnel who have been instructed in proper safety practices 2008 DH Instruments a Fluke Company All rights reserved Information in this document is subject to change without notice No p...

Страница 3: ...2 INSTALLATION 7 3 OPERATION 9 3 1 GENERAL OPERATING PRINCIPLE AND INFORMATION 9 3 1 1 PNEUMATICALLY OPERATED GAS BOOSTER PUMP 11 9 3 1 2 BOOSTER DRIVE SHUTOFF VALVE 13 10 3 1 3 ACCUMULATOR 9 10 3 1 4...

Страница 4: ...G 17 5 1 GENERAL INFORMATION 17 5 2 BOOSTER WILL NOT RUN 17 5 3 BOOSTER RUNS TOO SLOWLY 17 5 4 PRESSURE GENERATES TOO SLOWLY OR NOT AT ALL 18 5 5 BOOSTER RUNS CONTINUOUSLY 18 5 6 CANNOT ACHIEVE PRESSU...

Страница 5: ...Instruments a Fluke Company T TA AB BL LE ES S Table 1 GB H 152 70M and GB H 152 100M Parts List 5 Table 2 DHI Authorized Service Providers 22 F FI IG GU UR RE ES S Figure 1 GB H 152 Top and Side View...

Страница 6: ...GB H 152 GAS BOOSTER PACKAGE OPERATION AND MAINTENANCE MANUAL 2008 DH Instruments a Fluke Company Page iv N NO OT TE ES S...

Страница 7: ...ny A AB BO OU UT T T TH HI IS S M MA AN NU UA AL L Manual Conventions CAUTION is used in throughout the manual to identify user warnings and cautions NOTE is used throughout the manual to identify ope...

Страница 8: ...GB H 152 GAS BOOSTER PACKAGE OPERATION AND MAINTENANCE MANUAL 2008 DH Instruments a Fluke Company Page vi N NO OT TE ES S...

Страница 9: ...essure supply The gas booster boosts a lower pressure usually supplied from a bottle to higher pressure The high pressure gas is stored in an accumulator volume to assure stable supply to the PPCH G G...

Страница 10: ...nregulated 4 Booster drive air shut off valve booster ON OFF 5 Test gas supply connection 6 High pressure gas output regulator 7 Regulated high pressure gas output connection 8 Carrying handle 2 9 Hig...

Страница 11: ...pressure gas regulator 7 High pressure regulated gas output gauge 8 Regulated high pressure gas output connection 9 High pressure gas accumulator 10 High pressure gas accumulator drain 11 Gas booster...

Страница 12: ...sure GB H 152 70M GB H 152 100M 0 70 to 100 MPa 400 to 15 000 psi 0 35 to 120 MPa 200 to 17 400 psi Operating media air helium nitrogen Pressure connections Drive air supply Shop drive out Test gas pr...

Страница 13: ...from the fittings and inspect for damage and contamination Inspect for any missing components or accessories using Table 1 Should any items be missing contact DHI or you local supplier Table 1 GB H 15...

Страница 14: ...lator and high pressure regulator it is preferable to generate the highest pressure that can be achieved and regulate it down to the appropriate supply pressure for the PPCH G range to which the boost...

Страница 15: ...sired location o Close both regulators 2 and 6 by rotating the knobs counter clockwise until no spring force is felt The drive adjust 2 and high pressure adjust 6 regulators have a stop that prevents...

Страница 16: ...sing the GB H 152 with a PPCH G pressure controller calibrator use the hardware provided in the GB H 152 interconnect kit Connect the 1 5 m 1 8 in nipple with DH500 tips between the GB H 152 HIGH PRES...

Страница 17: ...e air applied to the pump The pump operates automatically provided drive air is supplied to the drive air regulator 15 and the regulator is set to at least 140 kPa 20 psig Operation is continuous unti...

Страница 18: ...and plug on the bottom of the accumulator cylinder act as a drain to purge the cylinder should liquids accumulate in it The GB H 152 supply gas should be dry the drain does not imply that it is accept...

Страница 19: ...he test gas supply The gas booster pump will not stop the flow of gas to the input of the high pressure regulator Test gas supply pressure is always present at the inlet of the high pressure regulator...

Страница 20: ...e air powers the booster pump To calculate the appropriate regulator setting divide the booster ratio of 152 into the desired maximum output pressure For example for a maximum output pressure of 80 MP...

Страница 21: ...circuit when the regulator is adjusted the pressure will increase when flow is reduced 3 3 3 DECREASING PRESSURE The high pressure adjust regulator is a venting type Therefore it is possible to regul...

Страница 22: ...GB H 152 GAS BOOSTER PACKAGE OPERATION AND MAINTENANCE MANUAL 2008 DH Instruments a Fluke Company Page 14 N NO OT TE ES S...

Страница 23: ...the tap 18 on the filter bowl 12 and drain out the liquid Reduce pressure before opening the tap 2 Drain high pressure accumulator If it is suspected moisture may have entered the high pressure circui...

Страница 24: ...GB H 152 GAS BOOSTER PACKAGE OPERATION AND MAINTENANCE MANUAL 2008 DH Instruments a Fluke Company Page 16 N NO OT TE ES S...

Страница 25: ...e proper pressure and flow value see Section 2 2 Check that the booster drive adjust regulator 2 is set to a pressure of 0 15 MPa 20 psig or higher and that minimum drive air flow requirements are met...

Страница 26: ...several times then stall If the booster does not stall when the test gas supply pressure is above 2 MPa 300 psi and the shop drive air pressure is below 0 25 MPa 40 psig the check valves are the most...

Страница 27: ...short tubing runs some users may find it beneficial to return the GB H 152 to a DHI Authorized Service Provider for repair rather than performing the troubleshooting and repair themselves see Table 2...

Страница 28: ...0 5 MPa 75 psi Open the booster drive shutoff valve 4 quickly If the booster begins to operate normally close the booster drive shutoff valve 4 and reset regulators to previous settings Repeat the pr...

Страница 29: ...t prepaid after receiving authorization from DHI or its Authorized Service Provider The buyer assumes all liability vis vis third parties in respect of its acts or omissions involving use of the produ...

Страница 30: ...NORMAL SUPPORT REGION DH Instruments a Fluke Company 4765 East Beautiful Lane Phoenix AZ 85044 5318 USA Tel 602 431 9100 Fax 602 431 9559 cal repair dhinstruments com Worldwide Minerva Meettechniek B...

Отзывы: