background image

 

3. OPERATION 

 

Page 13 

©1998-2008 DH Instruments, a Fluke Company 

3

3

.

.

 

 

O

O

P

P

E

E

R

R

A

A

T

T

I

I

O

O

N

N

 

 

3.1

 

GENERAL OPERATING PRINCIPLE AND INFORMATION 

 

  Refer to Figure 3. 

The purpose of the GB booster is to automatically boost gas pressure to very high pressure. 
The value of very high pressure that is generated depends on the drive air pressure setting.  The unit 
generates high pressure using a Pneumatically Operated Gas Booster Pump and a Drive Air 
Control Kit. 

GAS BOOSTER PUMP 

The booster pump is a Pascal press utilizing two pistons connected together on the same axis having a 
normal area ratio of 75:1 (GB-75) or 152:1 (GB-152).  The booster is a two-stroke, single stage 
reciprocating pump that generates gas pressures 75 or 152 times greater than the shop drive air applied 
to the pump.  The pump operates automatically, provided drive air is supplied to the 

 

DRIVE ADJUST regulator

 and the regulator is set to at least 140 kPa (20 psig).  Operation is continuous 

until the outlet pressure is 75 (GB-75) or 152 (GB-152) times the shop drive air pressure. 
At this point, the opposing forces within the pump reach equilibrium and the pump stalls.  For example, 
using a GB-75 with the drive air pressure set to 500 kPa (73 psig), the pump will run until the high 
pressure output reaches 75 x 0.5 = 37.5 MPa (5 450 psig). 

1.  The Shop Drive Air section (low pressure) consists of a piston, cylinder, air cycling valve, pilot valve 

and vent section.  This section provides the reciprocating action and compression force needed to 
operate the booster and generate the high pressure gas.  Drive air is channeled to the appropriate 
side of the piston (compression or suction stroke) by the air cycling valve.  When the piston reaches 
full stroke, a pilot valve is mechanically activated causing the air cycling valve to change position.  
Shop drive air is routed to the opposite side of the piston reversing piston direction where a second 
pilot valve is activated repeating the process.  

2.  The high pressure section (high pressure) consists of a small piston and an inlet/outlet check valve 

assembly.  The small piston moves forward and backward with the air drive piston.  During the 
suction stroke (backward movement), the outlet check valve closes and the inlet check valve opens 
letting supply high pressure gas enter the compression chamber.  During the compression stroke, the 
inlet check valve closes and the outlet check valve opens letting boosted gas out of the pump. 

The compression ratio of the high pressure piston is 25:1 (for both models).  Maximum output 
pressure is limited by the instrument gas supply pressure.  For example, with 2 MPa (300 psi) 
applied, maximum output pressure cannot exceed 2 x 25 = 50 MPa (7 500 psi). 

3.2

 

OPERATION 

Once the gas booster has been set up and the initial start up is completed, operation is very simple. 

There are two possible operator actions: 

 

Setting the booster output pressure (see Section 3.2.1). 

 

Turning the booster ON and OFF (see Section 3.2.2). 

Содержание GB-152

Страница 1: ...1998 2008 DH Instruments a Fluke Company GB 75 and GB 152 Gas Booster With Control Kit Operation and Maintenance Manual...

Страница 2: ...ruments a Fluke Company All rights reserved Information in this document is subject to change without notice No part of this document may be reproduced or transmitted in any form or by any means elect...

Страница 3: ...SITE 8 2 2 2 GAS SUPPLIES 8 2 2 2 1 DRIVE AIR SUPPLY 8 2 2 2 2 HIGH PRESSURE INSTRUMENT GAS 9 2 3 INSTALLATION AND SETUP 9 2 3 1 GENERAL CONSIDERATIONS 9 2 3 2 INSTALLATION 10 2 3 2 1 BOOSTER INSTALLA...

Страница 4: ...NERAL INFORMATION 17 5 2 BOOSTER WILL NOT RUN 17 5 3 BOOSTER RUNS TOO SLOWLY 18 5 4 PRESSURE GENERATES TOO SLOWLY OR NOT AT ALL 18 5 5 BOOSTER RUNS CYCLES CONTINUOUSLY 19 5 6 CANNOT ACHIEVE DESIRED PR...

Страница 5: ...Instruments a Fluke Company T TA AB BL LE ES S Table 1 GB 75 or GB 152 Parts List 7 Table 2 DHI Authorized Service Providers 21 F FI IG GU UR RE ES S Figure 1 GB 152 Gas Booster 2 Figure 2 Drive Air C...

Страница 6: ...Fluke Company Page IV A AB BO OU UT T T TH HI IS S M MA AN NU UA AL L Manual Conventions CAUTION is used in throughout the manual to identify user warnings and cautions NOTE is used throughout the man...

Страница 7: ...0 psi minimum to higher pressure The booster is powered by drive air The high pressure output is equal to the drive air input times the boosting ratio of 75 or 152 The high pressure output is connecte...

Страница 8: ...OF THE COMPONENTS 1 2 1 GAS BOOSTER 1 High Pressure Instrument Gas Filter 2 High Pressure Instrument Gas Supply Port 3 Drive Air Supply Port from Drive Air Control Kit 4 Breather Port 5 Low Pressure...

Страница 9: ...Company 1 2 2 DRIVE AIR CONTROL KIT 1 Drive Air Supply Connection not visible 2 Drive Pressure Adjust Regulator 3 Drive Pressure Indication Gauge 4 Drive Air Shut Off Valve 5 Drive Air Out Connection...

Страница 10: ...Instruments a Fluke Company Page 4 Figure 3 System Schematic 1 Drive Air Regulator 5 High Pressure Outlet Port 2 Drive Air Gauge 6 Booster Pump 3 Drive Air Shutoff Valve 7 1 4 in PFA Tubing 4 High Pr...

Страница 11: ...pressure output is high pressure supply times 25 Supply Flow Rates Shop Drive Air High Pressure Supply Gas 425 to 2 125 slm 15 to 75 scfm 140 to 560 slm 5 to 20 scfm Pressure Connections Drive Air Su...

Страница 12: ...GB 75 AND GB 152 OPERATION AND MAINTENANCE MANUAL 1998 2008 DH Instruments a Fluke Company Page 6 N NO OT TE ES S...

Страница 13: ...spect all parts for damage If damage is noted report it to your Receiving Department for appropriate action Inspect for any missing components or accessories using Table 1 Should any items be missing...

Страница 14: ...ion 2 3 1 for additional recommendations 2 2 2 GAS SUPPLIES Two sources of compressed gas are required to operate the gas booster They are drive air see Section 2 2 2 1 and high pressure instrument ga...

Страница 15: ...valve turns the booster ON and OFF The Drive Air Control Kit is presented on a bracket meant to be mounted at a location convenient to the operator for example on the front of a work bench When select...

Страница 16: ...steps below n Identify an appropriate location for the Drive Air Control Kit bracket If the booster will regularly be turned ON OFF and or frequent adjustment of booster output pressure is desired th...

Страница 17: ...as the DHI GPC1 Gas Pressure Controller The booster high pressure OUT port is connected to the SUPPLY port of the GPC1 see the GPC1 Operation and Maintenance Manual To connect the booster high pressu...

Страница 18: ...UST regulator knob clockwise while observing the set pressure on the DRIVE gauge Set the drive pressure to the maximum desired high pressure output divided by the booster ratio 75 for GB 75 152 for GB...

Страница 19: ...air cycling valve pilot valve and vent section This section provides the reciprocating action and compression force needed to operate the booster and generate the high pressure gas Drive air is chann...

Страница 20: ...imes the booster ratio To correctly set the pressure gas flow must not occur If flow is present in the circuit when the regulator is adjusted the pressure will increase when flow is reduced If the set...

Страница 21: ...age 15 1998 2008 DH Instruments a Fluke Company 4 4 M MA AI IN NT TE EN NA AN NC CE E A AN ND D A AD DJ JU US ST TM ME EN NT TS S 4 1 MAINTENANCE GB 75 and GB 152 gas booster packages require no stand...

Страница 22: ...GB 75 AND GB 152 OPERATION AND MAINTENANCE MANUAL 1998 2008 DH Instruments a Fluke Company Page 16 N NO OT TE ES S...

Страница 23: ...position If not set the valve fully to the ON position Check that drive air pressure supply is actually present at the DRIVE ADJUST regulator inlet connection If not ensure drive air is supplied at th...

Страница 24: ...ow 2 MPa 300 psi If the supply is too low increase supply pressure Speed of booster pressure generation is directly related to the pressure of the high pressure instrument gas supply For example press...

Страница 25: ...at the high pressure circuit connected to the booster OUT port is not open to atmosphere or doesn t have a severe leak If the shop drive air supply pressure is above 500 kPa 75 psig for GB 75 or 250 k...

Страница 26: ...eplacement Recommended torque on a DH500 fitting gland is 15 Nm It is possible that a leak exists in the high pressure section of the gas booster These leaks are very difficult to isolate and detect I...

Страница 27: ...or goodwill even if DHI has been advised of the possibility thereof and regardless of whether such products are used individually or as components in other products Items returned to DHI under warrant...

Страница 28: ...GB 75 AND GB 152 OPERATION AND MAINTENANCE MANUAL 1998 2008 DH Instruments a Fluke Company Page 22 N NO OT TE ES S...

Отзывы: