![DeZurik PMV P36C Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/dezurik/pmv-p36c/pmv-p36c_manual_2490643013.webp)
DeZURIK
PMV P36C and P41C Positioners
used with DeZURIK Pneumatic Actuators
August 2012
Page 13
D10327
Installing I/P Unit On Positioner
(Continued)
6. Install the I/P unit on the top of the positioner, making sure the four O-rings are in the correct
places. See Figure 10b.
7. Tighten the I/P unit with the three screws. See Figure 10a.
Figure 10 – I/P Unit On Positioner
8. Connect input signal cable to port lE and tighten the cable gland (see Figure 10e).
9. Adjust the O-ring on the I/P unit housing to desired position; sealed or drained (see Figure 10c).
10. Install a plug or a gauge in port P, and make sure the filter plug is tightened (see Figure 10d).