background image

- 34 -

There are four submenu in the Main Menu.

8.1.1 Main Menu

8.2 Sta�s�cs informa�on

Pic 8.5 Main Menu

Pic 8.6 Sta�s�cs

There are five submenu in the sta�s�cs.

Into each submenu through cursor.

E-Day

E-History

E-Month

E-Year

Test Data      《

MENU》Statistics

Statistics

Fault Record
ON/OFF
Setup
PV VA

MENU

Содержание SUN-60K-G

Страница 1: ...Grid tied PV String Inverter User Manual R SUN 60K G SUN 70K G SUN 75K G SUN 80K G ...

Страница 2: ...off 6 1 Start up the inverter 6 2 Shut off the inverter 18 18 18 7 Limiter function 19 7 1 Limiter function wiring diagram 7 2 Connect the limiter to inverter 19 20 23 7 4 Zero export function Option 7 3 Debugging Limiter 24 31 44 44 7 5 Notes while using zero export function 29 29 8 1 The initial interface 8 2 Statistics information 32 34 8 3 Fault Record 8 4 ON OFF setting 36 37 8 5 Parameter se...

Страница 3: ...inverter Documents must be stored carefully and be available at all mes Contents may be periodically updated or revised due to product development The informa on in this manual is subject to change without no ce The latest manual can be acquired via service deye com cn On grid inverter can convert solar panel DC power into AC power which can directly input to the grid Its appearance is shown below...

Страница 4: ...rid ed PV String Inverter x 1 DC power connectors including Inserted spring x 16 pairs Stainless steel an collision bolt M12 80 304 x 3 Wrench x 1 User manual User manual x 1 Installa on screws M5 12 x 2 Meter op onal x 1 Datalogger op onal x 1 Three Phase Smart Meter SET ESC SUN limiter op onal x 1 When ordering the sun limiter it will includes 3pcs CT Sensor Clamp x 3 19 20 ...

Страница 5: ...uc ons which if not correctly followed could result in burns Safety Hint Note symbol indicates important safety instruc ons which if not correctly followed could result in some damage or the destruc on of the inverter Warning Warning symbol indicates important safety instruc ons which if not correctly followed could result in serious injury or death Shock Hazard Prohibit disassembling inverter cas...

Страница 6: ...3 Local temperature of the inverter may exceed 80 while under opera ng Do not touch to avoid ge ng injured 4 All electrical installa on must be in accordance with local electrical standards and achieved permission of local power company 5 Please take appropriate an sta c measure 6 Please install where children can not touch Shock Hazard When PV module is exposed to sunlight the output will generat...

Страница 7: ...ica ng normal ac connec on Beside the AC indicator is the opera ng indicator green indica ng normal output The right indicator is alarm red indicates alarming Explanation Inverter detects DC input Low DC input voltage Grid Connected Grid Unavailable Under normal opera ng Stop opera ng Detected faults or report faults Under normal opera ng Indicator status DC AC NORMAL ALARM on off on off on off on off...

Страница 8: ...ght is Enter bu on ENTER Achieving below func ons by the four bu ons Three phase string inverter use 256 128 dot forma on display Display below content Page turning use UP and DOWN bu on Modify adjustable parameters use ESC and ENTER bu on 3 4 LCD Display Inverter opera on status and informa on Opera ng informa on Warning message and malfunc on display ...

Страница 9: ...freely To avoid overhea ng always make sure the flow of air around the inverter is not blocked Exposure to direct sunlight will increase the opera onal temperature of the inverter and may cause output power limi ng It is recommended that inverter installed to avoid direct sunlight or raining To avoid overhea ng ambient air temperature must be considered when choosing the inverter installa on loca o...

Страница 10: ...ne inverter must leave at least 500mm gap between each inverter And each inverter must be at least 500mm above and below And must install the inverter at the place where children cannot touch Please see picture 4 3 Consider whether the installa on environment is helpful to see the inverter LCD display and indicator status clearly Must offer a ven late environment if inverter installed in the air gh...

Страница 11: ... 09 4 2 Inverter of inverter 500mm 500mm Pic 4 3 Installa on Gap Pic 4 4 Mou ng bracket dimensions ...

Страница 12: ...n of the holes should be suitable for the expansion bolts 2 Make sure the bracket is horizontal and the moun ng holes are in the correct points Drilling the holes on the wall according the marks 3 Using the expansion bolts to fix the bracket to the wall Anchoring Mounting bracket M12 80 Stainless steel screws Inverter Pic 4 5 Inverter Installa on ...

Страница 13: ...se serious damages to the inverter Safety Hint Before connec ng inverter please make sure the PV array open circuit voltage is within the 1000V of the inverter Safety Hint Before connec on please make sure the polarity of the output voltage of PV array matches the DC and DC symbols Safety Hint Please use approved DC cable for PV system Pic 5 1 DC connector MC4 Pic 5 2 DC connector MC4 Cable type R...

Страница 14: ... 3 b Crimping metal terminals with crimping pliers as shown in picture 5 4 c Insert the contact pin to the top part of the connector and screw up the cap nut to the top part of the connector as shown in picture 5 5 Pic 5 3 Disassemble the connector cap nut 7mm 7mm Pic 5 4 Crimp the contact pin to the wire Pic 5 5 connector with cap nut screwed on ...

Страница 15: ...que material and the DC switch should be OFF otherwise the high voltage of the inverter may lead to life threatening condi ons Pic 5 6 DC input connec on 5 2 AC terminal connec on Warning The AC cable line L1 is connected to socket 1 L2 is connected to socket 2 L3 is connected to socket 3 the PE line is connected to the earth the N wire is connected to the socket of N Table 5 2 Recommened cable sp...

Страница 16: ...Pic 5 8 2 Connect the cable through the junc on box waterproof jacket and insert into the terminal The picture shows the connec on mode of three phase lines connected to the junc on box ground wire screwed on the inverter shell Pic5 9 and use hexagon screwdriver to presses the wiring harness to the connect terminal as shown in Pic5 10 Pic 5 7 AC junc on box Pic 5 8 AC terminal Pic 5 9 AC cable con...

Страница 17: ...tor as shown in Pic 5 11 5 2 3 Recommended current protector specifica ons Table 5 3 Recommended current protector specifica ons Pic 5 11 Tighten the AC junc on box Inverter SUN 60K G SUN 70K G SUN 75K G SUN 80K G Rated voltage 400 400 400 400 Rated output power KW 60 70 75 80 Current protection device A 120 150 150 150 ...

Страница 18: ... ground line Inverter has the func on of wireless remote monitoring inverter The inverter has Wifi func on and Wifi Plug in the accessories is used to realize the connec on between the inverter and the network The opera on installa on networking APP download are detailed in the WIFI PLUG instruc ons Figure 5 13 is the Internet monitoring solu on 5 4 Inverter monitoring connec on Warning Inverter has...

Страница 19: ...ws Insert the datalogger into the interface and fix it with a screw The configura on of the datalogger needs to be performed a er various electrical connec ons have been completed and the inverter DC power on When the inverter is on the DC power it is determined whether the datalogger is normally electrified The LED light shines out of the shell 5 4 1 Installa on of datalogger Pic 5 14 Datalogger ins...

Страница 20: ...inverter should fellow below steps 1 First switch on the AC breaker 2 Turn on the DC switch of the PV module and if the panel provides sufficient star ng voltage and power the inverter will start 3 When the AC voltage and DC voltage are normal the inverter start up is ready to begin The inverter will first check the internal parameters and the grid parameters while the liquid crystal will show that t...

Страница 21: ...en three sets of current sensor and one set of control terminals SUN limiter will collect voltage and current from these interfaces and send control signals to the inverter 7 Zero export func on via SUN limiter 7 1 SUN Limiter func on wiring diagram L1 L1 L L1 K L2 L L2 K L3 L L3 K L2 L3 N 20 Pic 7 1 SUN Limiter view When you are reading this we believe that you have completed the connec on accord...

Страница 22: ...e with a screwdriver 2 Connect SUN limiter to clamp senor Clamp senor can measure the current of the AC side it should be connected to the front side of the load domes c appliance ect to achieve this func on Only when the SUN limiter collects the voltage and current of the same phase can it judge the power of the phase So the clamp senor should be connected to the same phase as the before Open the...

Страница 23: ...nect the control line There are two numbers 1 and 2 on the interface of SUN limiter and the same on the waterproof terminal of the inverter Twist the waterproof terminal and connect the red line to number 1 and black line to number 2 shown as the picture A er that connect the terminal to the interface of the SUN limiter The other side of the line should be connected to the control terminal Load ...

Страница 24: ... 22 Pic 7 5 Waterproof terminal 1 2 Pic 7 6 Connect SUN limiter to inverter 1 2 limiter Pic 7 7 Connect terminal to inverter ...

Страница 25: ...select run param at this me please Input the default password 1234 through pressing the bu on up down confirm enter the opera on parameter se ng interface Shown as figure Pic 7 8 Zero export func on via SUN limiter se ng interface 7 3 Debugging Limiter Turn on the an backflow func on of the inverter refer to the manual then turn on the limiter s power supply and last turn on the inverter MENU Setup R...

Страница 26: ... Eastron SDM630 Modbus V2 which is able to measure the Max 100A current directly More details please refer to Pic 7 10 7 11 For the Eastron SDM630 MCT 40mA it needs external CT to measure the current The CT power range is from 5A 2000A More details about the Eastron SDM630 MCT please refer to Pic 7 12 7 13 Also the CHNT meter DTSU666 is supported it can measure the Max 80A current directly More de...

Страница 27: ... 6 7 8 Grid Pic 7 11 Connec on diagram of Eastron meter Solar Panel array Inverter meter AC Breaker Grid RS485 Communication Family load L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N N L3 L2 L1 VCC_5V 485_B 485_B 485_A 485_A GND GND RS 485 Male connector RS 485 Female connector 1 2 3 4 5 6 7 8 limiter1 limiter2 RS485 1 RS485 2 ...

Страница 28: ...limiter2 RS485 1 RS485 2 Pic 7 13 Connec on diagram of Eastron meter Solar Panel array Inverter meter AC Breaker Grid RS485 Communication Family load N L3 L2 L1 LA NA S2 S1 S2 S1 S2 S1 GND B A CT2 CT1 CT3 White line black line White line black line White line black line L1 L2 L3 N N L3 L2 L1 VCC_5V 485_B 485_A 485_A 485_B GND GND RS 485 Male connector RS 485 Female connector 1 2 3 4 1 2 3 4 5 6 7 ...

Страница 29: ... SET ESC 1 7 4 10 25 24 3 9 6 10 RS 485 CHNT DTSU666 3 6 9 10 1 4 7 10 Pic 7 15 Connec on diagram of CHINT meter Solar Panel array Inverter meter AC Breaker Grid RS485 Communication Family load 1 7 4 10 25 24 3 9 6 10 Three Phase Smart Meter SET ESC L1 L2 L3 N L1 L2 L3 N N L3 L2 L1 VCC_5V 485_B 485_B 485_A 485_A GND RS 485 Male connector RS 485 Female connector 1 2 3 4 limiter1 limiter2 RS485 1 RS...

Страница 30: ...y choosing up down bu on please press enter bu on to confirm when se ng done 5 Move the cursor to OK press enter to save the se ngs and exit the running parameters page otherwise the se ngs are invalid 6 If set up successfully you can return to the menu interface and display the LCD to home page by press the up down bu on If it displays meter power XXW the zero export func on se ng is completed Sho...

Страница 31: ...wo PV arrays are formed by the same number of PV panels of the same size which will make the inverter more responsive to limit the power 7 6 How to browse the load power of your PV grid e plant on monitoring pla orm If you want to browse load power of the system and how much energy KWH does it export to grid inverter output power is used to power the load firstly and then the surplus energy will fe...

Страница 32: ... 30 And then choose your system type as Self consump on Secondly go to plant page if it shows the PV power load power and grid power which means the configura on is correct ...

Страница 33: ... key to see the current DC voltage DC current AC voltage AC current inverter radiator temperature so ware version number and Wifi connec on state of the inverter 8 General Opera on System param Run param Protect param Comm param E Month E Day E Year E History Test Data Start Statistics Fault Record ON OFF Setup PV VA LCD main menu AC output data Interface DC input data Pic 8 1 LCD opera on flow char...

Страница 34: ...check inverter DC voltage DC current AC voltage AC current inverter temperature so ware version informa on You can check the PV informa on the number of strings input MPPT voltage and MPPT current Power Day Total State Standby 0 29 86Kw P 45 Kw 295kWh 25 MWh 6 12 18 24 ID 1601012001 0 0Kw SN 01 2019 05 11 08 00 00 PV1 V 349 9V I 10 3A P 3 6KW PV2 V 313 0V I 8 3A P 2 6KW PV3 V 0V I 0A P 0KW PV4 V 0...

Страница 35: ...n the bo om right corner The first flash means inverter is communica ng with LCD The second flash means LCD is communica ng with wifi plug Ua 234 5V Ia 0 0A Grid Freq 50 00Hz RUN Grid Pic 8 4 Inverter firmware version Pic 8 5 Meter power and load power Meter Power 0W Load Power 0W Day Total ImpEp 0 00kWh 0 00kWh ExpEp 0 00kWh 0 00kWh LoadEp 0 00kWh 0 00kWh PARAMETR Meter SN 0 Total DC Power 3 602W Ver2...

Страница 36: ...1 1 Main Menu 8 2 Sta s cs informa on Pic 8 5 Main Menu Pic 8 6 Sta s cs There are five submenu in the sta s cs Into each submenu through cursor E Day E History E Month E Year Test Data MENU Statistics Statistics Fault Record ON OFF Setup PV VA MENU ...

Страница 37: ...8 E Month Pic 8 9 E Year 2019 04 1 10 20 31 MENU Statistics E Month 01 10MWh 02 03 04 05 06 07 08 09 10 2019 MENU Statistics E Year 01 200KWh 02 03 04 05 06 07 08 09 10 11 12 2019 05 11 MENU Statistics E Day 0 10MWh 6 12 18 24 ...

Страница 38: ...ian s reference Only can keep four fault record in the menu include me customer can deal with it depends on the error code Pic 8 10 E History Pic 8 11Test Data PV1 PV2 HV GFD DiL AVL 126 1k2 19186 19198 24362 9119 36 2 287 6 1k3 1k4 1k5 1k6 vHV BSn ofA ofB 11126 11140 16666 2927 ofC 138 139 140 2057 2248 137 2145 1497 0 24362 12218 2065 2653 2015 2024 MENU Statistics E History 15 5KWh 16 17 18 19 ...

Страница 39: ... ON OFF se ng Pic 8 13 ON OFF se ng MENU ON OFF Turn ON Turn OFF Into each submenu through cursor Pic 8 14 ON set MENU ON OFF Turn ON Turn ON OK Cancel Pic 8 15 OFF set MENU ON OFF Turn OFF Turn OFF OK Cancel ...

Страница 40: ...e ng MENU Setup System Param Run Param Param Protect Param Comm Pic 8 17 System Param MENU Setup System Param Time Set Language Set Display Set Factory data reset Setting Restore 8 5 Parameter se ng Se ng includes system param run param protect param comm param All of these informa on for maintenance reference ...

Страница 41: ...et 2019 05 11 09 36 30 OK Cancel Pic 8 18 System Param 8 5 1 3 Language Set Pic 8 19 Lauguage set 8 5 1 4 Display Set Pic 8 20 Display set Display Set Brightness Delay Delay time 05S OK Cancel Lauguage Set 简体中文 English Angielski ...

Страница 42: ...a reset Confirm to reset Cancel 8 5 1 6 Se ng Restor Pic 8 22 Factory data reset set Setting Restor Confirm to restore Cancel 8 5 2 Running Param Note Password required only for access authorized engineer Un authorized access may avoid the warranty The ini al password is 1234 ...

Страница 43: ...omers don t need to reset it The password is same as 8 4 Running param Pic 8 22 Password PassWord Pic 8 23 Running Param MENU Setup Run Param OK Cancel ActiveP 100 ReactiveP 0 0 PF 1 000 Fun_ISO ON Fun_RCD ON SelfCheck 10S Island ON Meter OFF Limiter OFF E_Coef 0 00 Meter_CT 0 MPPT Num 3 ...

Страница 44: ...ED_4105 UTE_C15 RD_1699 CEI_0_21 G98_G99 AS4777 Reserved CUSTOM AC OverVoltage 1 270 0V Tripping Time 1 100ms AC OverVoltage 2 300 0V Tripping Time 2 100ms AC OverVoltage 3 300 0V Tripping Time 3 100ms CUSTOM AC LowVoltage 1 176 0V Tripping Time 1 100ms AC LowVoltage 2 176 0V Tripping Time 2 100ms AC LowVoltage 3 176 0V Tripping Time 3 100ms ...

Страница 45: ...eq 47 50Hz Rated Voltage 220 380V CUSTOM AC OverFreq 1 52 00Hz Tripping Time 1 2000ms AC OverFreq 2 53 00Hz Tripping Time 2 500ms AC OverFreq 3 54 00Hz Tripping Time 3 200ms CUSTOM AC LowFreq 1 48 00Hz Tripping Time 1 2000ms AC LowFreq 2 47 00Hz Tripping Time 2 500ms AC LowFreq 3 46 00Hz Tripping Time 3 200ms ...

Страница 46: ...essage In this case the inverter may stop feeding energy into the grid The alarm descrip on and their corresponding alarm messages are listed Table 10 1 Warning When the device is running the local temperature is too high and the touch can cause burns Turn off the inverter and wait for it cooling then you can clean and maintain Warning No solvent abrasive materials or corrosive materials can be use...

Страница 47: ...king mode changed Grid mode changed 1 Lost of one phase or AC voltage detec on circuit or relays not closed old inverter not have relays detec on func on 2 Restart the inverter if the error s ll exists please contact your installer or Deye service F20 DC over current fault of the hardware 1 Check whether solar panel output current is within the allowed range 2 Check DC current sensor and its detec...

Страница 48: ...0 AC main contactor failure 1 Check relays and AC voltage of relays 2 Check relays driver circuit Check if the so ware is not suitable for this inverter Old inverter not have relays detec on func on 3 Restart the inverter if the fault s ll exists contact your installer or Deye service F23 AC leakage current is transient over current 1 This fault means the leakage current is above 30mA suddenly Che...

Страница 49: ...tage protec on se ng And Check if the AC cable is too thin Check the voltage difference between LCD and meter F42 AC Line W U low voltage Check the AC voltage protec on se ng Check the voltage difference between LCD and meter Also need to check whether AC cables are all firmly and correctly connected F44 AC Line V W low voltage Check the AC voltage protec on se ng Check the voltage difference between ...

Страница 50: ...ature sensor Check if firmware is suitable for the hardware Check if the inverter is its right model 2 Restart the inverter if the fault s ll exists contact your installer or Deye service F59 AC grid V over current Hardly appear the code Never ever happened so far F60 AC grid W over current Hardly appear the code Never ever happened so far F61 Reactor A phase over current Hardly appear the code Nev...

Страница 51: ... V Rated Grid Frequency Hz Opera ng Phase Rated AC Grid Output Current A Max AC Output Current A Output Power Factor 0 5 47 52 or 57 62 op onal 98 7 98 3 60 60 60 60 4 3 4 4 220 380 230 400 277 460 this may vary with grid standards 50 60 Op onal Three phase 0 8 leading to 0 8 lagging 3 Grid Current THD 700 575 297 Transformerless Size mm W H D 60 Weight kg Topology 1W Night Internal consump on 25 ...

Страница 52: ...Add No 26 30 South Yongjiang Road Beilun 315806 Ningbo China Fax 86 0 574 8622 8852 Tel 86 0 574 8622 8957 E mail service deye com cn Web www deyeinverter com 502012741 Ver 2 1 2021 6 ...