-
44
-
Over-frequency Response
This series inverter provides “over-frequency response” func�on.
Long pressing the “OFD Mode” to enter the “over-frequency response”
se�ng menu.
Fstop 51.50Hz <<
Fstr 50.50Hz
For example, StrtPT: 50.5Hz, StopPT:
51.5Hz, RecPT: 50.1Hz, when the grid
frequency increases beyond Start: 50.5Hz,
the inverter will linearly reduce the power
output with a gradient of 100% Pmax/Hz
un�l it reaches StopPT: 51.5Hz .
50.0 50.1 50.2 50.3 50.4 50.5 50.6 50.7 50.8 50.9 51.0 51.1 51.2 51.3 51.4 51.5 51.6 51.7 51.8 51.9 52.0
Fig. 11-3
Frq-Watt Mode for Over-frequency Conditions
RecPT
Fstr
Fstop
Rated
Output
Power(kW)
Grid Frequency(Hz)
Hysteresis mode
Parameter
Fstr
Fstop
RecPT
RecGra
Tab. 11-4
Definition of Over-
frequency Response Parameters
Description
The Start frequency value for over-frequency response.
The Stop frequency value for over-frequency response.
Rate of Power recovery(Percentage of active power)
In hysteresis mode, power is restored only when
it is below this frequency
Range
45HZ-65HZ
45HZ-65HZ
45HZ-65HZ
[3,500] 0.01%Pmax/s
OF-Derate ON <-
ARC ON
OF-Derate OFF <-
ARC ON
OFDMode HYS <-
ARC ON