NAME
DESCRIPTION
Exp_Mode
AVG: Average power of three phase is zero
exported.
MIN: Phase with minimum load power is zero
exported, while the other two phase may be
in purchase mode.
AVG/MIN
1-1000
1-1000
1-16
ON/OFF
1-999kW
OFF/Master/
Slave
ShuntQTY
Generator
G.CT
G.MFR
G.FeedIn
G.Cap
CT_Ra�o
MFR
Shunt
CT ra�o of power grid side meter when extern
CT is applied.
Manufacturer of the grid side meter. Modbus
Address of it should be set as 01.
Parallel mode. Set one inverter as Master,
others are Slave. ONLY need to set the master,
Slave will follow the se�ngs in the master.
Number of inverters in parallel
DG side meter func�on Enable/Disable
CT ra�o of power DG side meter when extern
CT is applied.
Manufacturer of the DG side meter. Modbus
Address of it should be set as 02.
Output power percentage of the DG.
Capacity of the DG.
RANGE
0-110%
0-110%
AUTO/CHNT/
EASTRON
AUTO/CHNT/
EASTRON
Feedin
Percentage of the Feed in power exported
to the grid.
:
Select Meter op�on in Run Param and long press ENTER bu�on to enter this
Meter Se�ng page.
Note