6.3 STATUS BOARD 

– 95STS

 

The information provided on these pages assumes there IS a problem and there are no issues with the 
95DH Main Controller, the 95STS Status Board or wiring problems.

 

 
 

 

 

 

 

 

 

 

 

 

 

 

                                                                                                              

 
 
 

 

 

 

 

 

 

 

 

 

 

“Power On” LED: When lit indicates that the status board is receiving 
power from the 95DH Main Controller located inside the blower heater. 
If it is not lit - check to ensure the control power circuit is energized 
inside the blower heater. If the circuit is energized check the fuses 
leading up to and on the main controller then check the wiring between 
the blower heater and the status board.

 

“Element 1” LED: When this LED is blinking/pulsing it’s an indication 
that the outdoor temperature is such that the main controller is calling 
for heat. The continuous blinking/pulsing indicates that the blower 
heater is easily maintaining the pre-set discharge temperature.

 

Please Note: 

“Element 2” and “Element 3” LEDs will only be active 

when stage 1 cannot maintain the preset discharge temperature on its 
own and stage 2 and/or stage 3 elements are required. These LEDs will 
not blink/pulse.

 

“Overheat” LED: When lit indicates that an “Overheat” condition has 
occurred. This condition may be the result of either the Crydom Solid 
State Relay failing, the overheat thermostat at the top of the heat 
exchanger has had its wiring corrode off or has opened its internal 
contact (normally closed contact becomes open).

 

Relay Fail test: Turn off the control power and check for current in the 
heating circuit. If a current is measured the relays could be leaking 
across their voltage barrier, have found a current path to ground or 
have completely shorted out.

 

Overheat Sensor test: If the relays are fine check the continuity of the 
overheat thermostat, it should be in a normally closed state to allow 
heating. See Dexon 95DH Main Controller page for location of the 
overheat thermostat wires.

 

Figure 2: 

“Overheat” Indication 

Figure 1: Normal Operations 

Содержание OWMDH Series

Страница 1: ...ystems Inc 5018 80th Ave SE Calgary AB T2C 2X3 www dexoncanada com Phone 403 272 0562 Fax 403 235 0149 Email dexoncan dexoncanada com BLOWER HEATER OWNERS MANUAL OWMDH SERIES PROVIDING SAFETY VENTILATION TO THE WATER WASTER WATER INDUSTRY SINCE 1986 ...

Страница 2: ...INSTALLATION REQUIREMENTS 8 4 2 INSTALLATION INSTRUCTIONS 8 9 4 3 PERFORMANCE CHECK 9 10 11 5 MAINTENANCE 11 5 1 MAINTENANCE INSTRUCTIONS 11 12 6 TROUBLE SHOOTING GUIDES 13 6 1 TROUBLE SHOOTING GUIDE 13 6 2 MAIN CONTROL BOARD 95DH 14 15 6 3 STATUS BOARD 95STS 16 17 18 7 WARRANTY 19 8 DRAWINGS 20 8 1 DIMENSIONS 20 8 2 BOTTOM FOOTPRIN 21 8 3 INTERNAL WIRING 22 8 4 FIELD WIRING 23 8 5 OPTIONAL 95ALM ...

Страница 3: ...with an adjustable 5 range If the discharge temperature drops below 0 C typically the blower heater will shut down to prevent the ventilated space from freezing This equipment is suitable for use in Class 1 Division 2 Gas Groups C and D Temp Code T2C or for Non Hazardous Locations only FEATURES Overheat Protection Low Temperature Shut Down Discharge Temperature Sensor Adjustable Fan Speed in Auto ...

Страница 4: ...e protection When installing servicing ensure all latches are used to secure the door We do not recommend installing on a down pipe smaller than the discharge outlet Ensure there is adequate distance between intake louvers and pressure relief vent gooseneck Follow regular maintenance procedures as outlined in section 5 1 of this manual Locations with higher debris accumulation such as vegetation c...

Страница 5: ... restart when the discharge temperature reaches 2 C typically or more A built in timer overrides this shut down for 7 8 minutes when the unit is manually reset or power is cycled to allow the elements to warm up the discharge temperature This override does not apply when the unit automatically restarts after a Low Temp shut down If the discharge temperature rises above the normal operating range t...

Страница 6: ...odule is included Staged Heating Staged heating is only provided for the larger SMDH IMDH WMDH OWMDH series and the SRVDH IRVDH WRVDH OWRVDH series blower heaters to prevent high current draw and reduce power consumption when not required Stage 2 and Stage 3 heating elements will only be used if Stage 1 is not able to maintain the preset discharge temperature setting and only as required to mainta...

Страница 7: ...eat demand and the LED can be either blinking or constant Element 2 3 indicate stage 2 or 3 are required to maintain the desired temperature These LEDs will not blink they will remain constant WARNING The remote manual mode interface feature is intended to temporarily turn on Manual mode full fan speed for added safety regardless of the position of the Auto Manual toggle switch on the status board...

Страница 8: ...status output alarms Fan Stopped Low Temp and Overheat Optional Alarm Module sold separately 2 A Manual Mode Interface Terminal is available for input from PLC Lid Switch etc dry contact to initiate Manual mode full fan speed Standard Cable length 3 meters with the status board and 8 meters with the blower heater unless requested otherwise Please see status board Trouble Shooting Guide for more in...

Страница 9: ...gram provided allowing enough space between the ground and the unit for ducting transitions or off sets Through wall lining and insulation supplied by others and installed by others as required 2 The unit may be secured to the wall with the four wall mount brackets supplied 3 If not pre mounted install the status board in a suitable enclosure in a non hazardous dry location 4 Run separate conduits...

Страница 10: ...approx 7 8 minutes See Trouble Shooting Guide 6 1 for more information This allows the blower heater to start in cold conditions and will occur every time the unit is reset or powered up 9 If there is a heat demand the Element 1 LED on the status board should light up and should only remain constant momentarily then blink as it meets the demand The element LED will go out every time the demand is ...

Страница 11: ...ondition as described above with ice water or with the Dexon Temp Simulator to drop the discharge temperature to 0 C The Low Temp LED should light up and the fan should shut down followed by a Fan Stopped indication 4 After the unit has shut down turn the fan switch on the status board to Manual this overrides the Low Temp shut down feature The fan will come on at full speed and the Fan Stopped LE...

Страница 12: ...RUCTIONS MAINTENANCE SHOULD ONLY BE PERFORMED BY QUALIFIED PERSONNEL ONCE A YEAR PREFERABLY BEFORE THE COLD WEATHER SETS IN PERFORM THE FOLLOWING MAINTENANCE PROCEDURES 1 Check the status board for the following indications a The Power On LED should be on b The fan switch should be in Auto mode c The Element 1 LED may be off steady on or blinking An off LED would indicate there is no heat demand a...

Страница 13: ...r corrosion and ensure they are secure c Ensure the temperature sensor is inserted all the way to the bottom of the tubing 4 Replace any damaged or corroded parts When complete reinstall the control section and reconnect all wiring 5 Power up the unit and complete the performance check as described under section 4 3 6 Ensure all conduit holes are completely sealed with duct seal and secure door wi...

Страница 14: ... elements and on the Heat Sink above the elements for damage 3 Ensure the unit is not in Manual mode 4 Check that the fan voltage is set as per specifications see quality control test report 5 Check if the Overheat LED is on 1 Restore power 2 Replace damaged Klixon thermostat s if required 3 Set to Auto and press Reset switch 4 Adjust as required 5 If on see Overheat LED below Overheat LED is on 1...

Страница 15: ...om 120Volt Power 120VAC should be present here Low Temp shut down bypass timer LED The LED will blink until the timed delay has ended Note In order to allow time for the heat sensor to reach its set point temperature a 7 8 minute bypass is built into the controller for cold starts If the discharge temperature is below 0 C and the set point is not reached in the allotted time the blower heater will...

Страница 16: ...any adjustments to any potentiometers Note the airflow in Auto mode is preset by Dexon based on airflow requirements and heating capacity Increasing the airflow should only be done if airflow is inadequate due to unforeseen on site piping ducting friction Adjustments should only be made when absolutely necessary and by qualified personnel SP2 Is the set point at which the stage 2 element will enga...

Страница 17: ...g the pre set discharge temperature Please Note Element 2 and Element 3 LEDs will only be active when stage 1 cannot maintain the preset discharge temperature on its own and stage 2 and or stage 3 elements are required These LEDs will not blink pulse Overheat LED When lit indicates that an Overheat condition has occurred This condition may be the result of either the Crydom Solid State Relay faili...

Страница 18: ...at temperatures below 0 C The Low Temp LED can light up due to a lack of heating the heating circuit is off or one or more heat sensors are open This is most commonly due to corroded wire leads in the heat exchanger It could also be caused by a temperature sensor failure a sensor out of calibration or the 95DH main controller has failed The Fan Stopped LED Will light up in the event of a fan failu...

Страница 19: ...rflow rate It is important to note that in Manual mode the Low Temp shut down feature is bypassed disabled to ensure the unit does not shut down while the confined space is occupied This bypass can be used to allow heating even in a Low Temp shut down in order to defrost the fan if frosted up The fan will often restart once thawed Reset Switch This switch is used in order to start a bypass timer b...

Страница 20: ...revent any gases from entering the inside of the unit This includes ducting discharge conduit and bolt holes or any holes that would allow air to migrate into the unit When removing the inside panels for repair or service the discharge duct and any holes must still be covered in such a way as to prevent moisture from entering the body of the Blower Heater or Vent Fan Dexon s sole obligation under ...

Страница 21: ...Dexon Canada Air Systems Inc OWMDH Series Use Manual Version 07 2019 Page 20 8 1 DIMENSION DRAWING 8 DRAWINGS ...

Страница 22: ...Dexon Canada Air Systems Inc OWMDH Series Use Manual Version 07 2019 Page 21 8 2 BOTTOM FOOTPRINT ...

Страница 23: ...Dexon Canada Air Systems Inc OWMDH Series Use Manual Version 07 2019 Page 22 8 3 INTERNAL WIRING ...

Страница 24: ...Dexon Canada Air Systems Inc OWMDH Series Use Manual Version 07 2019 Page 23 8 4 FIELD WIRING ...

Страница 25: ...MM BACK VIEW NTS 114 0 MM NC SIX PIN CONNECTOR MOUNTING HOLES RELAY NO F S RELAY NC C NO C L T RELAY O H NO C NC 46 0 MM SHOWN IN DE ENERGIZED STATE NOTE ALL RELAYS AND CONTACTS ARE CONNECTIONS FOR A COMMON ALARM OUTPUT USING NO BACK VIEW NTS 114 0 MM RELAY F S HOLES MOUNTING CONNECTOR SIX PIN NC NO C L SHOWN IN DE ENERGIZED STATE NOTE ALL RELAYS AND CONTACTS ARE CONNECTIONS FOR SEPARATE ALARM OUT...

Отзывы: