Installation Guide
DEVIcomfort 10T
1
Introduction
DEVIcomfort 10T heating elements are to be
used for floor heating only and always covered by
concrete or similar.
Symbol description referring to product marking.
Direct floor heating
Installation in concrete
Scan the QR code to get the full installation guide,
warranty registration, product information, tips &
tricks, etc. or go to
www.gb.manuals.devi.com
.
2
Safety instructions
DEVIcomfort 10T must always be installed ac-
cording to local building regulations and wiring
rules as well as the guidelines in this installation
manual.
• This appliance can be used by children aged
from 8 years and above and persons with
reduced physical, sensory or mental capabili-
ties or lack of experience and knowledge, if
they have been given supervision or instruc-
tion concerning use of the appliance in a safe
way and understand the hazards involved, by
a person responsible for their safety.
• Children should be supervised to ensure that
they do not play with the appliance.
• Cleaning and user maintenance shall not be
made by children without supervision.
• De-energize all power circuits before installa-
tion and service.
• The screen from each heating element must
be connected to earth in accordance with
local electricity regulations and connected
via a residual current device (RCD).
• RCD trip rating is max. 30 mA.
• DEVIcomfort 10T must be connected via a
switch providing all pole disconnection that
can be locked in the off position.
• The thin mat must be equipped with a cor-
rectly sized fuse or circuit breaker according
to local regulations.
• Never exceed the maximum heat density
(W/m) for the actual application.
• DEVIcomfort 10T are not to be intercon-
nected.
• DEVIcomfort 10T must always be fully
embedded with non-flammable material e.g.
concrete, screed or tile glue by at least 5 mm.
incl. tiles.
• DEVIcomfort 10T must always be controlled
by a thermostat (DEVIreg™ Touch, DEVIreg™
535 or DEVIreg™ 530M) that limits the floor
temperature to max. 35 °C.
• All heating elements installed in the same
room must be laid out with same heat den-
sity (W/m² = same C-C distance) unless they
are connected to separate floor sensors and
thermostats.
• The enclosed label must be filled in and
placed adjacent to the distribution board,
describing location of the heating elements.
The presence of a DEVIcomfort 10T must
• be made evident by affixing caution signs in
the fuse box and in the distribution board or
markings at the power connection fittings.
DEVI VIJUB102
4