background image

3

SMOKE DETECTORS FOR MINIMUM SECURITY

  

 

 

 

• Install basement detectors at the bottom of the basement stairwell.

• 

Install second-floor detectors at the top of the first-to-second floor stairwell. Be 

sure no door or other obstruction blocks the path of smoke to the detector.

• 

Install additional detectors in your living room, dining room, family room, attic, 

utility and storage rooms.

• 

Install smoke detectors as close to the center of the ceiling as possible. If this is 

not practical, put the detector on the ceiling, no closer than 20 inches (50 cm) 
from any wall or corner, as shown in Figure 5.

• 

If some of your rooms have sloped, peaked, or gabled ceilings, try to mount 

detectors 0.91 meter measured horizontally from the highest point of the ceiling 
as shown Figure 6.

Figure 2: 

One separate smoke 

detector in every bedroom 

and one smoke alarm in the 

floor as a minimum protection

This alarm is only intended to be ceiling mounted or no more than 12 

inches below the ceiling.

This alarm will only indicate the presence of carbon monoxide gas at 

the sensor. Carbon monoxide gas may be present in other areas.

The  user  shall  actuate  the  test  and/  or  alarm  reset/silence  feature 

remotely  (via  an  electronic  signal  or  aerosol  test  gas),  or  by  use  of  a  person’s 
finger or thumb, and that the use of any other instrument(s) is strictly prohibited.

 

 

 
 

  

 
 
 
 
 
 
 
 
 
 
 
 

 

Figure 3: 

One separate smoke 

detector in every room, except 
kitchen and bathroom for 
more security

Figure 4: 

Location for placing 

smoke detector for a 
multi-floor residence

Figure 5: 

Recommended best 

and acceptable locations to 

mount smoke detectors

Figure 6: 

Recommended 

location to mount smoke 

detectors in rooms with 
sloped, gabled,or peaked 
celing

CAUTION 

(As required by the California State Fire Marshall)

“Early warning fire detection is best achieved by the installation of fire detection 
equipment  in  all  rooms  and  areas  of  the  household  as  follows:  (1)  A  smoke 
detector installed in each separate sleeping area (in the vicinity, but outside of the 
bedrooms), and (2) Heat or smoke detectors in the living rooms, dining rooms, 
bedrooms, kitchens, hallways, attics, furnace rooms, closets, utility and, storage 
rooms, basements and attached garages.”

“For your information, the National Fire Alarm and Signaling Code, NFPA 72, reads 
as follows:”

“29.5.1 *Required Detection.”
*29.5.1.1 Where required by applicable laws, codes, or standards for a specific type 
of  occupancy,  approved  single-  and  multiple-station  smoke  alarms  shall  be 
installed as follows:

(1) *In all sleeping rooms and guest rooms
(2) *Outside of each separate dwelling unit sleeping area, within 21 ft (6.4 m) of any 
door to a sleeping room, the distance measured along a path of travel
(3) On every level of a dwelling unit, including basements
(4)  On  every  level  of  a  residential  board  and  care  occupancy  (small  facility), 
including basements and excluding crawl spaces and unfinished attics
(5) *In the living area(s) of a guest suite
(6) In the living area(s) of a residential board and care occupancy
(Reprinted with  permission  from  NFPA  72®,  National  Fire Alarm  and  Signaling 
Code Copyright © 2012 National Fire Protection Association, Quincy, MA 02269. 
This reprinted material is not the complete and official position of the National Fire 
Protection Association, on the referenced subject which is represented only by 
the standard in its entirety.) 
(National  Fire  Alarm  and  Signaling  Code®  and  NFPA  72®  are  registered 
trademarks of the National Fire Protection Association, Inc., Quincy, MA 02269.)

Locations not to install your detector

Nuisance alarms take place when smoke detectors are installed where they will 
not work properly. To avoid nuisance alarms, do not install smoke detectors in the 
following situations:

• Combustion particles are the by-products of something that is burning. Thus, 
in or near areas where combustion particles are present you do not install the 
smoke detectors to avoid nuisance alarms, such as kitchens with few windows 
or poor ventilation, garages where there may be vehicle exhaust, near furnaces, 
hot water heaters, and space heaters.

• 

Do not install smoke detectors less than 20 feet (6 meters) away from places 

where  combustion  particles  are  normally  present,  like  kitchens.  If  a  20-foot 
distance is not possible, e.g. in a mobile home, try to install the detector as far 
away  from  the  combustion  particles  as  possible,  preferably  on  the  wall.  To 
prevent nuisance alarm alarms, provide good ventilation in such places.

• 

When  air  streams  passing  by  kitchens,  the  way  how  a  detector  can  sense 

combustion particles in normal air-flow paths is graphically shown in Figure 7, 
which indicates the correct and incorrect smoke detector locations concerning 
this problem.

Figure 7: 

Recommended 

smoke detector locations to 

avoid air streams with 
combustion particles

WARNING! !

This product is intended for use in ordinary indoor locations of family living units. It 
is  not  designed  to  measure  compliance  with  Occupational  Safety  and  Health 
Administration (OSHA) commercial or industrial standards. OSHA has established 
that continuous exposure levels of 50ppm should not be exceeded in an 8 hour 
period. Individuals with a medical problem may consider using warning devices 
which  provide  audible  and  visual  signals  for  carbon  monoxide  concentrations 
under 30ppm.

(Note: This section is only for model SCAZB-141 and SCAZB-143)

FOR SMOKE DETECTOR

Smoke detectors should be installed in accordance with the NFPA Standard 72 
(National Fire Protection Association, Batterymarch Park, Quincy, MA 02169). For 
complete coverage in residential units, smoke detectors should be installed in all 
rooms,  halls,  storage  areas,  basements,  and  attics  in  each  family  living  unit. 
Minimum coverage is one detector on each floor and one in each sleeping area. 
Here, we have useful tips for you:

• 

Install one separate smoke detector in every bedroom and one smoke detector 

in  the  floor  as  a  minimum  protection.  Install  one  separate  smoke  detector  in 
every room, except kitchen and bathroom for more security, as shown in Figure 
2 and Figure 3.

• 

Install a smoke detector on every floor of a multi-floor home or apartment, as 

shown in Figure 4.

• 

Install a smoke detector inside every bedroom.

• 

Install  smoke  detectors  at  both  ends  of  a  bedroom  hallway  if  the  hallway  is 

more than 40 feet (12 meters) long.

• 

The detector is not to be located within 5 feet (1.5m) of any cooking appliance.

• 

In  damp  or very  humid  areas,  or  near  bathrooms with  showers.  Moisture  in 

humid air can enter the sensing chamber, then turns into droplets upon cooling, 
which  can  cause  nuisance  alarms.  Install  smoke  detectors  at  least  10  feet  (3 
meters) away from bathrooms.

In very cold or very hot areas, including unheated buildings or outdoor rooms. 

If the temperature goes above or below the operating range of smoke detector, 
it will not work properly. The temperature range for your smoke detector is 40
to 100 F (4.4 C to 37.8 C). 

In very dusty or dirty areas, dirt and dust can build up on the detector’s sensing 

chamber,  to  make  it  overly  sensitive.  Additionally,  dust  or  dirt  can  block 
openings to the sensing chamber and keep the detector from sensing smoke. 

Near fresh air vents or very drafty areas like air conditioners, heaters or fans, 

fresh air vents and drafts can drive smoke away from smoke detectors. 

Dead air spaces are often at the top of a peaked roof, or in the corners between 

ceilings and walls. Dead air may prevent smoke from reaching a detector. See 
Figures 5 and 6 for recommended mounting locations.

In insect-infested areas. If insects enter a detector’s sensing chamber, they may 

cause  a  nuisance  alarm. Where  bugs  are  a  problem,  get  rid  of  them  before 
putting up a detector. 

Near  fluorescent  lights,  electrical  “noise”  from  fluorescent  lights  may  cause 

nuisance alarms. Install smoke detectors at least 5 feet (1.5 meters) from such 
lights. 

Your smoke detector is not to be used with smoke alarm guards.

Содержание SMAZB-141

Страница 1: ...2 Situation of smoke alarm not be effective 2 Locations to install your detector 2 Locations not to install your detector 3 Installing your detector 4 Features 4 General maintenance 5 If co alarm activates 5 Actions to take after the problem being corrected 5 Technical information for co alarm 5 If smoke alarm activates 5 Deactivation of detector 6 FCC statement 6 IC statement 6 ISED statement 6 Mo...

Страница 2: ...re related to CO poisoning and should be discussed with all members of the household so that you know what to look for Extreme exposure unconsciousness convulsions cardio respiratory failure death Medium exposure severe throbbing headache drowsiness confusion vomiting fast heart rate Mild exposure slight headache nausea fatigue similar to flu like symptoms Many victims of carbon monoxide poisoning ...

Страница 3: ...ction Association Inc Quincy MA 02269 Locations not to install your detector Nuisance alarms take place when smoke detectors are installed where they will not work properly To avoid nuisance alarms do not install smoke detectors in the following situations Combustion particles are the by products of something that is burning Thus in or near areas where combustion particles are present you do not i...

Страница 4: ...Please follow these steps to install your Smoke CO detector 1 At the place where you are going to install your Smoke CO detector draw a horizontal line six inches 15 cm long 2 Remove the mounting bracket from your unit by rotating it counterclockwise shown in Figure 8 3 Place the bracket so that the two longest hole slots are aligned on the line In each of keyhole slots drawing a mark to locate a ...

Страница 5: ...hnical information for CO alarm According to the UL2034 has already established the carbon monoxide concentrations and exposure time standards for the alarms which is specified below UL2034 At 70ppm the unit must alarm within 60 240 minutes At 150ppm the unit must alarm within 10 50 minutes At 400ppm the unit must alarm within 4 15 minutes Note This section is for model SCAZB 141 SCAZB 143 If smoke...

Страница 6: ...RSS 102 radiation exposure limits set forth for an uncontrolled environment This equipment should be installed and operated with minimum distance 20 cm between the radiator and your body Français L émetteur récepteur exempt de licence contenu dans le présent appareil est conforme aux CNR d Innovation Sciences et Développement économique Canada applicables aux appareils radio exempts de licence L e...

Отзывы: