Optional temperature control sys
tem
INSTALLATION
For sanitation
: this system holds the water in the cylinder at a temperature of 65°C
(150°F) to prevent bacteria or mold from forming in the cylinder if there is no humidity
demand.
For fast boiling
: when there is a demand for humidity, the water boils more quickly than
with cold water. This produces a faster response to the humidistat and more accurate
control.
For freeze protection
: can prevent freeze-up if the humidifier is subject to cold
environments. (Additional protection required for the water feed and drain lines)
.
The
optional temperature control system
overrides
the automatic pre-set draining
time where
the cylinder(s) is (are) drained
after x hours of stop.
Note : the humidifier temperature must be switched on for this system to operate.
The electrical wiring of the temperature sensor is
made on terminals n° 15 & 16 of the X4 connector of
the main board ref : 500100/03.
For boards with reference inferior to 1_22963
(programm : V2-11-), a 5,11 K.ohm resistance should
be put between terminal 15 & 17 of the X4 connector.
Set supplied in parts
:
T° sensor, X4 connector, stainless steel tube x
Ø40mm or Ø25mm (according to ELMC model) &
clamps.
300mm
17
16
15
X4