![Devatec ElectroVap MC Series Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/devatec/electrovap-mc-series/electrovap-mc-series_manual_2488619010.webp)
ElectroVap MC
Condensate outlet
9
X
= 1
0
0 mm
X = 1
5
0 mm
Y = 375 mm
X = 100 mm
Y = 550 mm
Y
= 1
3
0 mm
Installation
The following drawings show the water draining
connections that should be made.
Connection to the unit by a hose draining diam25
ELMC 5-30:
1 m hose with 3 hose clamps
ELMC 40-60:
1m+1.20m hose with 6 hose clamps.
ELMC 90:
1m+1.20m+1.80m hose with 9 hose
clamps
Please follow the recommendations hereafter. Drain
hose internal, diam mini
- ELMC 5/8/10/15/20/30
ø 25mm
- ELMC 40/50/60
ø 25 mm
- ELMC 90
ø 25 mm
The drain operates under gravity only. Ensure
drain pipework has a pitch of at least 15°C to
allow the unit to drain efficiently.
The Devatec recommended steam hoses should
be used for connecting the humidifier to the drain
network. Regular replacement is recommended.
The temperature of the water discharged from the
humidifier is between 60°C and 100°C. Ensure the
pipe work used is capable of withstanding such
temperatures.
The discharge hose must be free from any obstacle.
It is recommended that each steam cylinder has its
own drain pipe and tundish arrangements. This will
permit fast and easy identification of a fault within a
cylinder.
The discharged water should be offset from the
underside of the unit as shown. This will prevent
any steam and/or condensation from getting into
the cabinet.