ELECTROVAP® KIT MC
41
5.6
WATER INLET VALVE
Maintenance of the water inlet valve is to be done after
the first 50 hours of operation. Thereafter, twice a year
(minimum).
•
Switch the appliance off.
•
Switch off the water supply to the humidifier and
unscrew the water supply hose.
•
Disconnect the power cables from the water inlet
valve of your humidifier (Item 1).
•
Loosen the clamp and remove the water supply
hose. (Item 2)
•
Unscrew the two screws securing the valve (Item 3).
•
Pull out your valve, remove the filter with pliers and
remove the coil (Item 4) by prying it off with a
screwdriver.
•
Run water through the valve body and over the filter
to remove any particles.
Once all these operations completed, please reassemble the unit, taking care to check the condition
of the water supply hose clamp. You can put your appliance back into service.
Ensure that all the clamps are properly tightened whenever the humidifier is maintained.
Fig. 6-6.
Water inlet valve
Содержание ElectroVap KIT MC 15
Страница 1: ...ElectroVap HUMIDIFIERS KIT MC Series Instruction Operation Manual ...
Страница 2: ...ELECTROVAP KIT MC 2 ...
Страница 31: ...ELECTROVAP KIT MC 31 3 8 3 WIRING DIAGRAMS KITMC 5 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Страница 32: ...ELECTROVAP KIT MC 32 KITMC 8 à 20 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Страница 33: ...ELECTROVAP KIT MC 33 KITMC 30 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Страница 34: ...ELECTROVAP KIT MC 34 KITMC 40 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Страница 35: ...ELECTROVAP KIT MC 35 KITMC 50 60 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Страница 46: ...ELECTROVAP KIT MC 46 ...
Страница 47: ...ELECTROVAP KIT MC 47 ...