ELECTROVAP® KIT MC
27
DIGITAL CONTROL (MODBUS) (display board needed)
Control signal type setting in humidifier menu
RS485
–
HARDWARE CONNECTION
RS485 connection must be plugged on the J2 connector:
•
Terminal 1: Data -
•
Terminal 2: Data +
•
Terminal 3: GND
The SW1 switch is used to turn line resistance on or off. Depending on your needs, these resistances
can be activated or deactivated (see diagram).
1
2
3
4
3
2
1
J2
SW1
On
Off
K4A
X10
Main board
SW1
–2
J2
1 : Data
–
2 : Data +
3 : GND
+5V
680
SW1
–3
120
SW1
–1
680
Fig. B 3-8.
CTRL SIGNAL TYPE
DIGITAL CONTROL
x
XXXX