background image

10

TROUBLESHOOTING GUIDE

C) Checkpoint faults

1. Power on/off light
2. Compressor on light off

3. Alarm/Service alert light on -

check Display for active
conditions
SERVICE DRYER

LOW PRESSURE

HIGH PRESSURE
NOTE: If high refrigerant pressure
occurs, switch must be manually

LOW TEMPERATURE
(also observed as low reading
on temperature indicator)

HIGH TEMPERATURE
(also observed as high reading on
temperature indicator)

DRAIN

TIME OUT

A) Water downstream of dryer

1. Residual free moisture remaining in

downstream pipelines

2. Air by-pass system is open
3. Inlet and Outlet connections are

reversed

4. Air lines downstream of dryer are

exposed to temperatures below the
dew point.

5. Excessive free moisture (bulk liquid)

at dryer inlet

6. Condensate not being drained
7. Dryer overloaded resulting in

elevated dew point.

8. Refrigeration system not functioning

1. Excessive air flow
2. Freezing of moisture in evaporator

because of refrigeration system
fault

3. Filter loaded with solid particulates

a. Power failure; open circuit

a. Compressor commanded off by

manual switch or programmed
schedule

b. Open circuit
c. Control circuit open on high or low

pressure cutout

Service interval specified has elapsed

a. Hot gas by-pass valve requires

adjustment

b. Low on refrigerant

a. Lack of condenser cooling

Air-cooled - Ambient temperature
too high, clogged condenser fins,
obstructed flow across condenser,
faulty fan motor or fan
control switch.
Water-cooled - Cooling
temperature too high, flow too low,
clogged strainer, faulty water
regulating valve

a. Hot gas by-pass valve

requires adjustment

a. Dryer overloaded

b. Refrigeration system off or not

cooling sufficiently

a. Drain line restricted or frozen
b. Drain mechanism faulty

Dryer left in the Set Mode for longer
than 30 seconds

Blow out system with dry air

Check valve positions
Check for correct connection

Insulate or heat trace air lines exposed
to low ambients or dry air to lower
dew point
Install separator ahead of dryer

See C below

B) High pressure drop across dryer

 

SYMPTOM

POSSIBLE CAUSE(S)

         CORRECTIVE ACTION

See C below

See C below

Check flow rate

See C below
Replace filter element

Check for power to dryer

Check current command status

Check power ro compressor
Check display for fault

Perform scheduled service

Contact qualified technician or
manufacturer’s service department

Check air temperature 6” in front
of condenser
Clean condenser and check for free
air flow
Check fan and switch operation
Check cooling medium temperature
and flow, clean strainer, check
valve operation

Contact qualified technician or
manufacturer’s service department

Check compressed air flow,
temperature, and pressure

Check power to unit, power to
compressor, Low or High pressure
faults Have qualified technician
evaluate system

Open drain line
Turn 3-way valve to horizontal position
and open petcock for manual draining.
Rebuild drain mechanism.
Finish programing and press
Set/Run button

NOTE:  After fault correction, press reset button to clear display

For Sales & Service Call:  705-722-5747  Ext.1

Содержание DRD 200

Страница 1: ...NTENANCE 6 SIZING 6 ENGINEERING DATA 7 ELECTRICAL SCHEMATICS 8 DIMENSIONS WEIGHTS 9 TROUBLESHOOTING 10 PARTS LIST 11 WARRANTY 12 SERVICE DEPARTMENT 724 746 1100 7610 530 11A 9 01 Refrigerated Compressed Air Dryers Models DRD 200 250 300 400 500 750 Instruction Manual c For Sales Service Call 705 722 5747 Ext 1 ...

Страница 2: ...carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you insist that a notation of this loss or damage be made on the delivery receipt by the carrier s agent B UNPACKING Check for Concealed Loss or Damage When a shipment has been delivered to you in apparent good order but concealed damage is found upon unpacking ...

Страница 3: ...r cooled 45 to 130 F 7 to 54 C E Installations in altitudes above 4500 feet 1370 meters Dryer is adjusted to operate in altitudes up to 4500 feet 1370 meters If dryer is installed in an altitude above this and has not been preset at the factory for this altitude contact manufacturer s Service Department NOTE Outdoor installation Standard units are designed for indoor installation Contact manufactu...

Страница 4: ...imum working pressure Do not exceed dryer s Maximum Working Pressure NOTE Install dryer in air system at highest pressure possible e g before pressure reducing valves NOTE Install dryer at coolest compressed air temperature possible Maximum inlet compressed air temperature 120 F 49 C If inlet air exceeds this temperature precool the air with an aftercooler B Air Outlet Connect air outlet to downst...

Страница 5: ...cy of service Typically element changeout is recommended at least annually e Push Set Run button again to exit Set Mode NOTE If dryer is left in the Set Mode for longer than 30 seconds Alarm light will illuminate and TIME OUT will appear on the Interface panel Dryer will resume previous operating mode C Starting dryer IMPORTANT Dryer must be energized 24 hours before starting refrigeration compres...

Страница 6: ...rm that activates if drain fails to discharge f Check drain operation push Drain push to test button to energize electric drain A flow of condensate and or air should be present at the drain outlet E Using the RS 232 port The RS 232 port is used to monitor dryer operation from a host computer A 1 to 1 DB 9 cable is required to connect dryer and computer For PC connections data is transmitted on pi...

Страница 7: ...pliers MODEL 200 250 300 400 500 750 Rated capacity of 60 Hz 200 250 300 400 500 750 air cooled models scfm 50 Hz 170 210 250 340 420 630 TABLE 1 Rated capacity scfm and pressure drop 100 psig inlet pressure 100 F inlet temperature and 100 F ambient temperature Air cooled models water cooled models use 1 15 multiplier if cooling water is below 35 C 95 F Element o ring Separator Element Bowl o ring...

Страница 8: ... Max Min voltage 253 187 253 187 253 187 253 187 Rated Load Amps 8 4 11 5 13 6 22 9 Locked Rotor Amps 51 65 5 75 90 Minimum Circuit Ampacity 10 5 16 9 17 1 31 7 Branch Circuit Fuse Size amps 15 20 25 45 Watts 35 F Evaporator 100 F Ambient 1335 1940 2620 3600 Resistance Ohms Three phase Total 1 77 1 256 1 058 0 853 Nominal Voltage 460 3 60 460 3 60 460 3 60 460 3 60 Max Min Voltage 506 414 506 414 ...

Страница 9: ...eight lb 405 415 416 457 498 625 LEGEND CON CONTACTOR HTR CRANKCASE HEATER MTR COMPRESSOR 1FU FUSE SECONDARY 2FU FUSE PRIMARY 3FU FUSE PRIMARY 1FM FAN MOTOR 1 2FM FAN MOTOR 2 1FPS FAN PRES SWITCH 1 2FPS FAN PRES SWITCH 2 TC1 DEWPOINT TEMPERATURE T1 TRANSFORMER CONTROL T2 TRANSFORMER HDD BOARD SSMP SOLID STATE MOTOR PROTECTION SOL1 DEMAND DRAIN ELECTRICAL SCHEMATIC NOTE Dimensions and Weights are f...

Страница 10: ...ol switch Water cooled Cooling temperature too high flow too low clogged strainer faulty water regulating valve a Hot gas by pass valve requires adjustment a Dryer overloaded b Refrigeration system off or not cooling sufficiently a Drain line restricted or frozen b Drain mechanism faulty Dryer left in the Set Mode for longer than 30 seconds Blow out system with dry air Check valve positions Check ...

Страница 11: ...0 111 25 4130 111 28 Low refrigerant pressure switch 4130 138 22 4130 138 22 4130 138 22 4130 138 22 4130 138 22 4130 138 22 4130 138 22 4130 138 22 High refrigerant pressure switch 4130 138 25 4130 138 25 4130 138 25 4130 138 25 4130 138 25 4130 138 25 4130 138 25 4130 138 25 Fan cutout switch 1 4130 138 23 4130 138 23 4130 138 23 4130 138 23 4130 138 23 4130 138 23 4130 138 23 4130 138 23 Fan cu...

Страница 12: ...uct based on the original date of purchase and or date of manufacture as outlined above There is no other expressed warranty Implied warranties including those of merchantability and fitness for a particular purpose are limited to one 1 year from date of purchase to the extent permitted by law and any and all implied warranties are excluded This is the exclusive remedy Liability for consequential ...

Отзывы: