Installation guidelines
Deutschmann Automation GmbH & Co. KG
40
Fieldbus-Gateway UNIGATE
®
CX C4Map - PROFINET V. 1.0
29.9.20
a) In the case of standard screw-type terminals, one lead can be clamped per connection point. It
is best to then use a screwdriver with a blade width of 3.5 mm to firmly tighten the screw.
Permitted cross-sections of the line:
•
Flexible line with wire-end ferrule:
1 x 0.25 ... 1.5 mm²
•
Solid conductor:
1 x 0.25 ... 1.5 mm²
•
Tightening torque:
0.5 ... 0.8 Nm
b) The plug-in connection terminal strip is a combination of standard screw-type terminal and
plug connector. The plug connection section is coded and can thus not be plugged on the
wrong way round.
c) The 9-pin D-SUB plug connector is secured with two screws with "4-40-UNC" thread. It is best
to use a screwdriver with a blade width of 3.5 mm to screw the screw tight.
Tightening torque: 0.2... 0.4 Nm
14.2.2.1 Power supply
The device must be powered with 10..33 V DC.
•
Connect the supply voltage to the 4-pole plug-in screw terminal in accordance with the label-
ling on the device.
14.2.2.2 Equipotential bonding connection
The connection to the potential equalization automatically takes place it is put on the DIN-rail.