Table 4: Airflow tables SUPREME Advantage ECM 1HP motor
COOLING OR HEAT PUMP HEATING MODE (WITH HP-EFF SELECTED
1
)
CFM
2
CFM
2
CFM
2
AC / HP SIZE
A/C size AC/HP CFM ADJUST AC/HP CFM ADJUST
AC/HP CFM ADJUST
Adjustment
(TONS)
BLACK wire position
BLACK wire position
BLACK wire position
BLUE wire position
(BLK) = (NOM)
(BLK) = (LO)
(BLK) = (HI)
60
5,0
2000
1800
2200
48
4,0
1600
1440
1760
42
3,5
1400
1260
1540
36
3,0
1200
1080
1320
1
"SYSTEM TYPE"
2
In Cooling - Dehumidification mode (with Jumper
J1
remove), with no 24 VAC input to DH, the CFMs are
reduced by 15%.
The CFMs shown are reduced by 20% if there is 24VAC input to Y1 only (Y/Y2 not powered)
CONTINUOUS FAN
24 VAC (R) input on G only
CFM
1
CFM
1
CFM
1
AC / HP SIZE
A/C size
CONTINUOUS FAN
CONTINUOUS FAN
CONTINUOUS FAN
Selection
(TONS) YELLOW wire position YELLOW wire position
YELLOW wire position
BLUE wire position
(YEL) = (LO)
(YEL) = (MED)
(YEL) = (HI)
60
5,0
1000
1600
2000
48
4,0
800
1280
1600
42
3,5
700
1120
1400
36
3,0
600
960
1200
1
CFM’s when AC/HP CFM ADJUST at NOM position. CFM’s 10% lower or higher if AC/HP CFM ADJUST
at LO or HI position.
ELECTRIC HEATING MODE
24 VAC (R) input on W1 and/or W2 only
CFM
HEAT KW/CFM
POWER
CFM
Second stage
adjustment
(kW)
First Stage
24VAC on W1
RED wire position
24 VAC on W1
1
and/or W2
1
30/27
30
715
1424
30/27
27
715
1424
25
25
675
1345
23
23
620
1235
20
20
477
950
1
Remove the Jumper
J2
when a 2 stages thermostat is used
17