built-in  High-Limit  Control  that  prevents  the  burner  from 
overheating and damaging the furnace. 
 
3.1.2 

Operation in the ELECTRICITY mode: 

 
When  the  three-position  selector  is  on  the  ELECTRICITY 
setting,  the  furnace  operates  like  a  conventional  electric 
warm-air furnace.  When the thermostat is set high enough, 
the  fan  comes  on,  followed  by  each  of  the  elements  in 
sequence.    When  the  call-for-heat  has  been  met,  the 
elements go off-line sequentially, while the fan stays on until 
residual  heat  is  evacuated  from  the  system.    Each  of  the 
elements is individually protected from overheating by way of 
a  Temperature  Limit  Control  in  the  event  of  fan  failure.    A 
removable  panel  under  the  oil  burner  provides  easy  access 
to the electric elements.  
 
Warm  air  from  your  furnace  will  naturally  be  cooler  in  the 
electrical  than  the  oil  mode  since  the  electrical  output  is  5 
kW lower.  It is imperative that airflow adjustments be made 
in the oil mode where it is most critical.  Once the call-for-h-
eat  has  ended,  the  elements  go  off-line  sequentially, 
separated by a 12 second delay. 
 
When  switching  from  oil  to  electricity,  there  is  a  five-minute 
delay  between  burner  shutdown  and  the  elements  coming 
on-line in order to guard against overheating. 
 
3.1.3 

Operation in DUAL-ENERGY mode 

 
When  the  three-position  selector  is  on  the  DUAL-ENERGY 
setting,  the  furnace  micro  processor  is  on-line  with  Hydro.  
When  the  call-for-heat  comes  through,  the  processor 
determines  whether  to  heat  with  oil  or  electricity.  The 
electronic  control  system  can  also  switch  the  furnace  from 
one mode to the other during a heating cycle. It is important 
to note that there is a five minute delay between burner shut 
down and the elements coming on. 
 
3.1.4 

Operation in AUTO-RELIEF mode 

 
A  factory-installed  thermosensor,  located  on  the  left  side  of 
the  inside  top  portion  of  the  component  panel,  relays 
temperature  readings  to  the  board.  The  sensor  requires  no 
adjustment  or  modification.  If,  during  a  period  of  15 
consecutive minutes, the sensor records temperatures under 
38°C (100°F) while the thermostat circuit is closed , the board 
will assess an abnormal operation and implement auto-relief.  
In  basic  terms,  this  means  simply  changing  the  heating 
mode. 
 
When  the  AUTO-RELIEF  indicator  light  comes  on,  the 
furnace has detected a problem with one energy source and 
has  automatically  shifted  to  the  other.  If  the  furnace  is 
operating  electrically,  with  both  the  AUTO-RELIEF  and 
ELECTRIC  lights  on,  there  is  a  burner  problem.  If  the 
furnace is in the oil mode, with both the AUTO-RELIEF and 
OIL lights on, there is a problem with the electrical system. 
 
Twelve  hours  following  detection  of  AUTO-RELIEF,  the 
furnace will try once again to operate with the power source 
indicated  on  the  three-position  switch:    oil,  electricity,  or 
dual-energy,  according  to  the  signal  from  Hydro.  The 
process will repeat itself every twelve hours. Obviously, if the 
problem  persists,  the  furnace  will  remain  in  the 
AUTO-RELIEF mode.  The only way to get out of this mode, 
in  such  a  situation,  is  to  manually  reset  the  furnace  by 
cutting and then restoring the main power supply.  

3.1.5 

Monitor Lights 

 
These  lights,  which  indicate  the  operating  state  of  the 
furnace, are located just below the three-position selector on 
the outside of the electrical compartment door. 
 
OIL light alone 
 
This indicates that the furnace is operating on OIL solely and 
is not in the dual-energy mode. 
 
OIL light with DUAL-ENERGY light 
 
This  indicates  that  the  appliance  is  in  the  DUAL-ENERGY 
mode, but operating on OIL at the moment. 
 
ELECTRICITY light alone 
 
This  indicates  that  the  furnace  is  operating  solely  on 
ELECTRICITY and is not in the dual-energy mode. 
 
ELECTRICITY and DUAL-ENERGY lights 
 
This  indicates  that  the  appliance  is  in  the  DUAL-ENERGY 
mode, but operating on electricity at the moment. 
 
AUTO-RELIEF and OIL lights 
 
When  both  these  lights  are  on,  there  is  a  problem  with  the 
ELECTRICITY mode. The dual-energy light may or may not 
be on. 
 
AUTO-RELIEF and ELECTRICITY lights 
 
When  both  these  lights  are  on,  there  is  a  problem  with  the 
OIL system.  The dual-energy light may or may not be on. 
 
3.1.6 

Operating in the EMERGENCY mode 

 
In the case of an electronic board malfunction or breakdown, 
the emergency mode enables the furnace to run on OIL, by 
using the emergency switch located between the thermostat 
connection  terminal  strip  and  the  ventilation  switch  in  the 
burner  cabinet.  When  the  thermostat  calls  for  heat,  the 
burner is energized and the blower is controlled by the Fan-
Limit Control. 

 

WARNING 

 

The  transfer  to  the  emergency  mode  is  not  automatic, 
but  must  be  effected  manually,  as  required.  The 
EMERGENCY  MODE  must  only  be  used  as  a  temporary 
means  of  heating.  The  problem  that  caused  the 
activation  of  this  mode  in  the  first  place  must  be 
repaired  as  soon  as  possible.  For  further  details  see 
Part 4 of this manual. 

 

 
3.2 

OPERATING IN THE OIL MODE  

 
3.2.1 

Operational checklist 

 
Before  starting  up  the  unit,  be  sure  to  check  that  the 
following items are in compliance: 

1.  The  electrical  installation,  the  oil  supply  system,  the 

venting system, combustion air supply and ventilation; 

2.  The blower access door secured in place; 

Содержание LOW-BOY AME15-79

Страница 1: ...79 AME20 90 AME25 100 DNS 0671 R v A C Fabriqu par Industries Dettson Inc 3400 boulevard Industriel Sherbrooke Qu bec Canada J1L 1V8 www dettson ca INSTALLATEUR TECHNICIEN UTILISER LES RENSEIGNEMENTS...

Страница 2: ...igne de mazout 8 3 2 3 V rification de la combustion 9 3 2 4 V rification de l ajustement du ventilateur 9 3 2 5 V rification des limiteurs de temp rature 10 3 2 6 Ajustement du limiteur 10 3 2 7 V ri...

Страница 3: ...ation de cet appareil par une personne non qualifi e peut endommager l quipement et ou conduire des conditions hasardeuses susceptibles d entra ner des dommages corporels IMPORTANT Toutes les exigence...

Страница 4: ...contr le des odeurs D autre part en plus de l air de combustion une quantit suffisante d air doit tre fournie pour la ventilation incluant l air n cessaire pour le confort et des conditions de travai...

Страница 5: ...11 Chemin es foyers vents et appareils de chauffage au combustible solide et ou CSA B139 Code d installation Cet appareil de chauffage central est homologu pour tre utilis avec un vent de type L temp...

Страница 6: ...ce de votre unit et l amp rage nominal afin de choisir un disjoncteur et une protection de calibre suffisant L unit requiert une alimentation 240 120 Volts AC 60 Hz 3 fils plus mise la terre Installer...

Страница 7: ...S il y a panne de ventilateur ou obstruction excessive dans le conduit d air chaud le g n rateur est muni d un contr le de haute limite qui emp che le br leur de surchauffer et d endommager le g n rat...

Страница 8: ...peut tre allum ou non Voyant AUTO RELEVE et voyant ELECTRICITE Lorsque le voyant AUTO RELEVE est allum en m me temps que le voyant ELECTRICITE ceci signifie qu il y a un probl me sur le mode MAZOUT V...

Страница 9: ...u un quivalent 3 Afin d effectuer la v rification de la combustion suivre les tapes suivantes a Percer un orifice d analyse des gaz de diam tre minimum appropri e environ 9 32 dans le tuyau de raccord...

Страница 10: ...ider le bon fonctionnement de la prise BVSO sur l unit de chauffage seulement 1 Faire fonctionner le br leur 2 D brancher la prise 3 p les identifi e BVSO sur l unit 3 Le br leur doit s arr ter imm di...

Страница 11: ...t pouvez inspecter visuellement ou l aide d un voltm tre chacun des l ments Si vous avez changer un l ment suivez la proc dure suivante 1 D branchez les 2 fils lectriques de l l ment retirer 2 D visse...

Страница 12: ...t adresse du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp...

Страница 13: ...van 0 65 80W 0 75 80W 0 85 80W Ajustement air de combustion bande obturateur 0 7 1 4 0 9 SYST ME LECTRIQUE Volts Hertz Phase 240 120 60 1 Contr le du transformateur 40 VA DONN ES TECHNIQUES DU VENTILA...

Страница 14: ...MENT APPLICATION D GAGEMENT MINIMUM FOURNAISE 15 cm 6 PLENUM D ALIMENTATION 5 cm 2 AUTRE C T FOURNAISE 60 cm 24 ARRI RE FOURNAISE 60 cm 24 DESSUS FOURNAISE OU PLENUM 5 cm 2 DESSOUS FOURNAISE PLANCHER...

Страница 15: ...15 Figure 3 Emplacement des composantes principales Figure 4 Localisation du tiroir d l ments DNS 0202 R v C DNS 0209 R v A...

Страница 16: ...16 Figure 5 D montage du tiroir d l ment...

Страница 17: ...17 Figure 6 Diagramme lectrique...

Страница 18: ...18 Figure 7 Liste de pi ces B50047 Rev A...

Страница 19: ...PLAQUE DE RETENUE 30 B02301 GARNITURE SORTIE DES GAZ 31 B02311 ASS SORTIE DES GAZ 32 B02312 ASS PIEGE A SON COMPLET 33 F07O001 ECROU HEXAGONAL A BRIDE 3 8 16NC LAITON 34 Z99F050 POIGNE ENCASTRE NOIR 3...

Страница 20: ...SUS 70 B01154 PORTE D ACCES 71 B01095 ASS D LEMENTS 72 A00207 11 FIL ELECTRIQUE ROUGE 73 A00201 19 FIL ELECTRIQUE NOIR 74 L04J002 BRIDE DE CABLE 7 8 NOIR 75 B01123 03 TIROIR D L MENT 76 B01123 01 TIRO...

Страница 21: ...Printed on 100 recycled paper DNS 0671 Rev A C Manufactured by Industries Dettson inc 3400 Industrial Boulevard Sherbrooke Quebec Canada J1L 1V8 www dettson ca INSTALLER SERVICE TECHNICIAN USE THE INF...

Страница 22: ...OIL MODE 7 3 2 1 Operational checklist 7 3 2 2 Purging the oil line 8 3 2 3 Combustion check 8 3 2 4 Fan adjustment check 8 3 2 5 Limit Control check 9 3 2 6 Limit Control adjustment 9 3 2 7 BVSO perf...

Страница 23: ...e installation of oil burning equipment wiring and flue connections must be followed some of the codes that may be applicable are CSA B139 Installation code for oil burning equipment ANSI NFPA 31 Inst...

Страница 24: ...equate to provide air for combustion ventilation and dilution of flue gases This determination must be made on an individual installation basis and must take into consideration the overall volume of t...

Страница 25: ...himney the chimney must be of sufficient area to accommodate the total flue products of all appliances vented into the chimney The following requirements are provided for a safe venting system a Ensur...

Страница 26: ...y harm An internal filter rack located in the blower compartment is provided as standard equipment with this furnace A sufficient clearance should be provided for air filter access Refer to Table 2 fo...

Страница 27: ...rner problem If the furnace is in the oil mode with both the AUTO RELIEF and OIL lights on there is a problem with the electrical system Twelve hours following detection of AUTO RELIEF the furnace wil...

Страница 28: ...rformance from the oil burner the following set up procedures must be followed by referring to the Technical Specifications Table 2 in this manual 1 A test kit to measure the smoke flue draft and over...

Страница 29: ...unction of the furnace and cause premature wear of the heat exchanger CAUTION Modification of the factory set limits will void the warranty 3 2 7 BVSO performance test The purpose of the following tes...

Страница 30: ...lace an element follow the steps below 1 Disconnect the 2 wires attached to the element 2 Remove the metal screws that hold the frame on the drawer bottom of the drawer 3 Remove the frame by unscrewin...

Страница 31: ...rvice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F A...

Страница 32: ...le 100 PSIG pump pressure Delavan 0 65 80W 0 75 80W 0 85 80W Combustion air adjustment shutter band 0 7 1 4 0 9 ELECTRICAL SYSTEM Volts Hertz Phase 240 120 60 1 Control transformer 40 VA BLOWER DATA B...

Страница 33: ...E A R A N C E S F U RN A CE 15 c m 6 S U P P LY P L E N U M 5 c m 2 O T HE R S I DE F U RN A CE 60 c m 24 B A C K F U RN A CE 60 c m 24 T O P F U RN A CE O R P LE NU M 5 c m 2 B O T T O M F U RN A CE...

Страница 34: ...14 Figure 3 Location of main componants Figure 4 Location of element drawer DNS 0202 R v C DNS 0209 R v A...

Страница 35: ...15 Figure 5 Element drawer removal...

Страница 36: ...16 Figure 6 Electrical Diagram...

Страница 37: ...17 Figure 7 Parts List B50047 Rev A...

Страница 38: ...ation 29 B02305 Holding plate 30 B02301 Breech plate gasket 31 B02311 Breech plate 32 B02312 Sound trap ass y 33 F07O001 Hex nut brass 34 Z99F050 Recessed handle black 35 Z04F010 Paper filter 16 x 20...

Страница 39: ...70 B01154 Acces door 71 B01095 Electrical element ass y 72 A00207 11 Red w ire 73 A00201 19 Black w ire 74 L04J002 Cable clamp 75 B01123 03 Element draw er 76 B01123 01 Element draw er 77 B01123 02 El...

Страница 40: ...20...

Отзывы: