2.0  INSTALLATION 

 

2.1 

LOCATION 

 
The  water  heater  must  be  installed  on  a  level  and 

NON-

COMBUSTIBLE 

surface,  as  close  as  possible  to  the 

chimney.    The  water  heater  must  also  be  located  close  to  a 
suitable  free-flowing  floor  drain.    Where  a  floor  drain  is  not 
adjacent  to  the  water  heater,  a  suitable  drain  pan  must  be 
installed under the water heater.  This drain pan should be at 
least 4’’ (10,2 cm) larger than the diameter of the water heater, 
and  at  least  1’’  (2.5  cm)  deep  providing  access  to  the  drain 
valve.    This  pan  must  be piped to a suitable drain to prevent 
damage  to  property  in  the  event  of  a  water  leak  from  the 
piping, the relief valve, or the water heater. 
 
Sooner  or  later,  all  water  heaters  leak.    The  manufacturer, 
based  on  national  building  codes  has  given  the  necessary 
advice  to  prevent  damage  to  the  building.    Under  no 
circumstances  is  the  manufacturer  to  be  held  liable  for  any 
water damage in connection with this water heater. 

 

Note : 

If  the  temperature  in  the  house  and/or  the 

basement  is  under  16°C  (60°F)  there  is  an  increased 
possibility of condensation inside the chimney. 

 

2.2 

ACCESS FOR MAINTENANCE 

 
Convenient  access  shall  be  provided  to  permit  cleaning  of 
heating  surfaces,  flue  pipe  and  for  burner  maintenance.  
Minimum clearances from combustible material should be:  

 

Table 1 : Minimum clearances 

 

2.3 

SHIPPING COMPONENTS 

 
The  unit  is  shipped  in  two  separate  cartons;  the  first carton 
is for the water heater tank. The second is for the burner the 
aquastat, the wiring harness and the flue adaptor. 
 

2.4 

WATER CONNECTIONS 

 

WARNING 

 

To  avoid  water  damage  and/or  scalding  due  to  relief 
valve  operation,  a  discharge  line  must  be  connected  to 
the  valve  outlet  and  run  to  a  drainage  area.  The 
discharge line shall be installed in such a way that it will 
allow  for  complete  drainage  of  the  valve  and  discharge 
line. 

 

 

Make  the  hot  and  cold  water  connections  to  the  water 
heater.  Do  not  apply  heat  to  the  hot  water  outlet  and  cold 
water inlet, as they contain a plastic sleeve inside. Pressure 
relief valves are installed on all models. 
 

2.5 

FLUE PIPE 

 
The  water  heater  should  be  connected  to  a  chimney  or  an 
approved  pre-fabricated  flue.  The  flue  pipe  should  be  the 

same  size  as  the  flue  outlet  of  the  unit.  It  is  preferable  to 
maintain a pitch or rise from the heater to the chimney of 2.0 
cm  per  1  m  (1/4"  per  foot).  The  flue  pipe  must  not  be 
extended past the inside wall of the chimney. 
 

2.6 

DRAFT REGULATOR 

 
The draft regulator must be installed between the flue outlet 
of  the  water  heater  and  the  chimney.  (Installation 
instructions are furnished with the regulator). 
 

2.7 

BLOCKED VENT SHUT-OFF (BVSO) 

 

For chimney venting 

 

WARNING 

 

It  is  imperative  that  this  device  be  installed  by  a 
qualified technician. 

 

 

This device is designed to detect the insufficient evacuation 
of combustion gases in the event of a vent blockage. In such 
a case the thermal switch will shut down the oil burner.  The 
device will then need to be re-armed MANUALLY. 
 
Refer  to  the  wiring  diagrams  and  the  detailed  instructions 
supplied  with  the  BVSO  for  the  installation  and  wiring 
procedure. The length of wires supplied with the unit is such 
that  the  safety  device  must  be  installed  between  the  flue 
outlet  of  the  appliance  and  the  draft  regulator,  as  indicated 
in the instructions. 
 
It  is  further  imperative  that  the  BVSO  be  maintained 
annually.  Refer  to  the  instructions  supplied  with  the  device 
and paragraph 4.2 of this manual for more details. 
 

2.8 

CHIMNEY 

 
For  information  pertaining  to  chimney  sizes,  elevation, 
conditions,  etc.,  see  C.S.A.  Standard  B-139,  "Installation 
code for oil burning equipment." 

 

WARNING 

 

An  oil-fired  unit  shall  be  connected  to  a  flue  having 
sufficient draft at all times to assure proper operation of 
the unit. 

 

 

2.9 

CONTROLS 

 
Mount the aquastat control on the unit. Set operating control 
between  48°C  (120°F)  and  60°C  (140°F).  The  maximum 
setting  for  all  models  is  60°C  (140°F).  If  required,  set  the 
high-limit  at  a  temperature  of  20  °  F  higher  than  the 
operating control.   
 

2.10 

WIRING 

 
Connect BX harness from aquastat to the side of the burner 
relay junction box. Wire oil burner and controls according to 
the attached wiring diagram. The field supplied wiring should 
be connected to the top of the aquastat on all models. 
 

 

Models 32 and 50

 

Sides 

5,08 cm    (2") 

Rear 

5,08 cm    (2") 

Top 

45,70 cm  (18") 

Front 

61,00 cm  (24") 

Flue 

22,90 cm    (9") 

Содержание CMO32-II

Страница 1: ...USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUT...

Страница 2: ...TANK AND PIPING 5 2 16 VENTILATION AND COMBUSTION AIR 5 3 0 OPERATION 5 3 1 INITIAL START UP 5 3 2 ADJUSTMENTS 5 3 3 SHUT DOWN 5 3 4 BVSO PERFORMANCE TEST 6 3 5 FLAME FAILURE 6 4 0 MAINTENANCE 6 4 1...

Страница 3: ...l or any oil containing gasoline WARNING Never burn garbage or paper in the heating system and never leave rags or paper around the unit a It is the homeowner s responsibility to engage a qualified te...

Страница 4: ...The water heater should be connected to a chimney or an approved pre fabricated flue The flue pipe should be the same size as the flue outlet of the unit It is preferable to maintain a pitch or rise f...

Страница 5: ...istribution system for leaks 2 16 VENTILATION AND COMBUSTION AIR Normally infiltration of air into the home is adequate to provide the necessary volume of air for combustion and ventilation When a uni...

Страница 6: ...Take out strainer cartridge and replace it annually c Re assemble strainer 4 2 BLOCKED VENT SHUT OFF BVSO CLEANING For continued safe operation the Blocked Vent Shut Off System BVSO needs to be inspec...

Страница 7: ...unscrew outer liner 3 Take off the insulation pad and remove the damaged chamber by sliding it out 4 Install the new chamber 5 Re install insulation outer liner access panel and burner Ensure that the...

Страница 8: ...0 FURNACE INFORMATION Model Serial number Installation date Service telephone Day Night Dealer name and address START UP TEST RESULTS CO2 Stack temp Firing rate GPH Smoke Draft at stack Test performed...

Страница 9: ...3 3 8 U Nozzle Delavan 0 65 70A 0 65 70A Pump pressure 135 135 Combustion air adjustment turbulator damper 0 3 5 0 3 5 Nozzle Danfoss 0 55 60AS Delavan 0 65 60W Pump pressure 165 175 Combustion air a...

Страница 10: ...10 Figure 1 Electrical wiring Beckett burner Figure 2 Electrical wiring Riello burners Non disponible sur le Riello R35 3 Not available on the Riello R35 3 DNS 0242 Rev D...

Страница 11: ...o 4 3 4 9 B10074 COLLAR FRONT INTERIOR 10 B10306 COLLAR INSULATION FRONT INTERIOR 11 B03114 01 BVSO ELECTRICAL KIT 12 R02G003 DOUBLE AQUASTAT HONEYWELL L4006G1022 13 G14G007 GASKET 3 3 4 OD 1 ID LDPE...

Страница 12: ...13 B10306 COLLAR INSULATION FRONT INTERIOR 14 B10368 HEAT CHAMBER AND INSULATION ASSEMBLY includes items 0 11 12 13 14 15 15 B10093 REFRACTORY HEAT CHAMBER 16 B10424 CASING INSULATION 17 B10366 CASIN...

Отзывы: